GENERAL AIRSTAGE | CONTROLS REFERENCE
RTPU Controls and anywAiR iO
External Inputs, Modbus RS485, SMT-770 and UTY-RTPU-ANYWIO
Applicable to AIRSTAGE PREMIUM and RAQ single skin rooftop package units using R410A or R454B.
1. Available Control Methods
| Method | Application |
|---|---|
| Danfoss local control | Commissioning, parameter adjustment and direct unit operation. |
| External dry contacts | Remote on/off, heating/cooling selection and emergency stop. |
| Modbus RS485 | Integration with a BMS or compatible external control system. |
| anywAiR iO | Optional programmed controls integration with the Smart Temp SMT-770. |
2. External Inputs – Terminal X2
The supplied single skin controls reference identifies the following dry-contact inputs.
| X2 Terminals | Open Circuit | Closed Circuit |
|---|---|---|
| 1 and 2 | Forced stop | Remote start enabled |
| 5 and 6 | Cooling mode | Heating mode |
| 7 and 8 | Emergency stop active | Emergency stop inactive |
- When remote forced stop is not being used, terminals 1 and 2 should be bridged as specified in the control reference.
- When emergency stop is not being externally controlled, terminals 7 and 8 should be bridged as specified in the control reference.
- Do not use the external heat/cool selection input when an in-room controller is also installed, as directed by the control reference.
3. Modbus RS485 Integration
Rooftop units can be integrated with building management systems using Modbus RTU over RS485.
| Protocol | Modbus RTU slave |
| Default address | 10 |
| Default baud rate | 19200 |
| Default serial configuration | 8N1 |
A BMS must be appropriately mapped and programmed for the required operating commands, temperature controls, schedules and feedback. A full Modbus points list should be obtained through GENERAL Technical Support where required.
A third-party temperature sensor may be connected to the documented X1-103 and X1-104 inputs for compatible applications. Verify the sensor type and controller programming before connection.
4. Optional UTY-RTPU-ANYWIO Kit
The UTY-RTPU-ANYWIO is an optional control package designed to interface the rooftop unit with an SMT-770 room controller through an anywAiR iO Rubix Compute device.
Kit Components
- anywAiR iO Rubix Compute controller.
- 240 V AC to 24 V DC power supply.
- Smart Temp SMT-770 room controller.
Control Architecture
| Danfoss RTPU Controller Internal machine control |
| RS485 / Modbus |
| anywAiR iO Rubix Compute 24 V DC supply |
| Integrated control and communication arrangement |
| Smart Temp SMT-770 24 V AC room controller |
This is a functional overview only. Follow the UTY-RTPU-ANYWIO installation wiring diagram for the actual wiring connections.
5. Wiring Reference
| Device | Connection | Function |
|---|---|---|
| RTPU X5 | 24V / 2 | 24 V AC for SMT-770 |
| RTPU X5 | D1+ / D1- | RS485 communication |
| RTPU X5 | 0V / 240V | Supply for 24 V DC power supply |
| SMT-770 | COMS A / COMS B | RS485 + / RS485 - |
| SMT-770 | 24 / 24C | 24 V AC active / common |
| Rubix Compute | 485-1 | RS485 connection |
| Rubix Compute | ETH-1 | Optional Ethernet modem connection |
Do not use the Rubix Compute 485-2 connection for this application. Verify that the 24 V AC and 24 V DC power supplies are not interchanged.
6. SMT-770 Configuration
The supplied installation instructions specify:
| Modbus address (ad) | 7 |
| Baud rate (bd) | 192 (19200 baud) |
| Parity (pa) | 0 (None) |
To access the installer settings, the UTY-RTPU-ANYWIO guide instructs technicians to hold the O/RIDE button for approximately 15 seconds and follow the installer-menu PIN procedure detailed in the manual.
The supplied guide documents DIP switch 6 as ON when the seven-day timer function is required. The remaining DIP switches must be left in the documented application-specific positions.
7. Rubix Compute and Danfoss Setup
- Rubix Compute must be powered from the correct 24 V DC supply.
- Use RS485 port 485-1.
- Verify RS485 positive, negative and ground connections against the wiring schematic.
- Confirm that the device switch and status LEDs are in the required state.
- Configure the Danfoss controller for Modbus address 10 and 19200 baud unless an approved project-specific configuration requires otherwise.
- The installation manual specifies Danfoss serial format 8N1.
8. Communication Troubleshooting
If the expected communication indicator is absent or the local controller is not communicating:
- Verify 24 V AC at the SMT-770.
- Verify 24 V DC at Rubix Compute.
- Confirm RS485 cable continuity and polarity.
- Confirm controller addresses are correct.
- Confirm baud rate and parity settings.
- Verify Rubix Compute status LEDs and switch settings.
- Check for conflicting devices or incorrect BMS configuration.
- Confirm machine operation independently before diagnosing complex external control issues.
- R410A and R454B AIRSTAGE_RTPU_Control_Logic V1.pdf
- Install manual - VERSION 3 - suited to half page.pdf
- RTPU Commissioning instructions 1.4.pdf
GENERAL AIRSTAGE | Controls reference for qualified technicians.