GENERAL AIRSTAGE | TECHNICAL REFERENCE
Single Skin Rooftop Package Units
Model Reference, Specifications and Electrical Drawings
Applicable to the PREMIUM / RAQ single skin range using R410A or R454B refrigerant.
Identify a rooftop package unit by its PREMIUM or RAQ model number and locate the corresponding electrical data, refrigerant information, dimensions and model-specific technical drawings.
Models | Dimensions | Electrical | Refrigerant | Drawings
1. Model Identification
The AIRSTAGE single skin rooftop range is available in 12 sizes. Product documentation may identify the same size using a PREMIUM commercial model number or an RAQ model number.
| Size | R410A Commercial Model | R454B Commercial Model | RAQ Identification |
|---|---|---|---|
| 15 | PREMIUM15 | PREMIUM15-R454B | RAQ/K 15 or RAQ/L 15 |
| 17 | PREMIUM17 | PREMIUM17-R454B | RAQ/K 17 or RAQ/L 17 |
| 110 | PREMIUM110 | PREMIUM110-R454B | RAQ/K 110 or RAQ/L 110 |
| 112 | PREMIUM112 | PREMIUM112-R454B | PREMIUM112-R454B |
| 115 | PREMIUM115 | PREMIUM115-R454B | RAQ/K 115 or RAQ/L 115 |
| 118 | PREMIUM118 | PREMIUM118-R454B | RAQ/K 118 or RAQ/L 118 |
| 120 | PREMIUM120 | PREMIUM120-R454B | RAQ/K 120 or RAQ/L 120 |
| 224 | PREMIUM224 | PREMIUM224-R454B | RAQ/K 224 or RAQ/L 224 |
| 230 | PREMIUM230 | PREMIUM230-R454B | RAQ/K 230 or RAQ/L 230 |
| 234 | PREMIUM234 | PREMIUM234-R454B | RAQ/K 234 or RAQ/L 234 |
| 236 | PREMIUM236 | PREMIUM236-R454B | RAQ/K 236 or RAQ/L 236 |
| 238 | PREMIUM238 | PREMIUM238-R454B | RAQ/K 238 or RAQ/L 238 |
Model suffixes
- K: R410A model identification in the supplied range documents.
- L: R454B model identification in the supplied range documents.
- WP: Reversible heat pump.
- EC: EC inverter plug-fan configuration.
- EC/WP: Reversible heat pump with EC inverter plug-fans.
Always confirm the full model configuration from the nameplate. Not all variations have identical electrical, airflow or accessory requirements.
2. Unit Dimensions and Weights
Overall dimensions below are shown as height x width x depth in millimetres. They are sourced from the supplied PREMIUM quick reference workbook. Operating and transport weights are in kilograms.
| Size | R410A H x W x D | R454B H x W x D | Operating kg | Transport kg |
|---|---|---|---|---|
| 15 | 1180 x 1200 x 1200 | 1210 x 1200 x 1200 | 480 | 495 |
| 17 | 1210 x 1300 x 1450 | 1210 x 1200 x 1450 | 545 | 560 |
| 110 | 1425 x 1200 x 1600 | 1425 x 1200 x 1600 | 595 | 610 |
| 112 | 1425 x 1450 x 1800 | 1425 x 1450 x 1700 | 680 | 695 |
| 115 | 1430 x 1450 x 2000 | 1490 x 1450 x 2000 | 700 | 715 |
| 118 | 1490 x 1750 x 2140 | 1490 x 1750 x 2100 | 805 | 820 |
| 120 | 1490 x 1750 x 2100 | 1490 x 1750 x 2100 | 815 | 830 |
| 224 | 1970 x 1900 x 2100 | 2020 x 1900 x 2100 | 1195 | 1210 |
| 230 | 1970 x 1900 x 2210 | 2020 x 1900 x 2210 | 1255 | 1270 |
| 234 | 2020 x 1900 x 2210 | 2020 x 1900 x 2210 | 1275 | 1290 |
| 236 | 2325 x 1900 x 2330 | 2325 x 1900 x 2330 | 1400 | 1415 |
| 238 | 2325 x 1900 x 2330 | 2325 x 1900 x 2330 | 1505 | 1520 |
Dimensions and weights are reference data only. Verify the approved model drawing, actual configuration and nameplate before preparing a roof structure or lifting plan. Allow for projections, access and service clearances.
3. Electrical Data
The models listed use three-phase electrical power. The electrical drawings identify a nominal 400 V / 50 Hz / 3-phase supply. The actual electrical supply requirements and protection must be verified from the nameplate and unit-specific wiring diagram.
| Size | R410A FLA / LRA (A) | R454B FLA / LRA (A) | Protection (A) |
|---|---|---|---|
| 15 | 13 / 64 | 12 / 63 | 16 |
| 17 | 15 / 91 | 14 / 90 | 20 |
| 110 | 21 / 104 | 20 / 103 | 25 |
| 112 | 26 / 148 | 26 / 148 | 32 |
| 115 | 30 / 154 | 30 / 154 | 40 |
| 118 | 36 / 204 | 36 / 205 | 50 |
| 120 | 36 / 204 | 36 / 205 | 50 |
| 224 | 54 / 177 | 51 / 173 | 63 |
| 230 | 60 / 184 | 60 / 184 | 80 |
| 234 | 66 / 207 | 65 / 206 | 80 |
| 236 | 72 / 239 | 73 / 241 | 100 |
| 238 | 94 / 278 | 93 / 277 | 160 |
4. Refrigerant Charge Reference
The following figures are taken from the corresponding R410A and R454B safety documentation. Quantities are shown in kilograms.
| Size | R410A (kg) | R454B (kg) |
|---|---|---|
| 15 | 3.50 | 7.00 |
| 17 | 5.60 | 8.00 |
| 110 | 6.40 | 9.50 |
| 112 | 8.30 | 12.00 |
| 115 | 9.20 | 13.00 |
| 118 | 11.50 | 12.66 |
| 120 | 13.50 | 13.50 |
| 224 | 17.00 | 28.00 |
| 230 | 23.00 | 26.00 |
| 234 | 30.00 | 30.00 |
| 236 | 29.70 | 33.00 |
| 238 | 38.00 | 38.00 |
Note: These are published reference charges for the documented configurations. Confirm the actual factory charge and circuit information on the fitted equipment before servicing. Do not use this table alone to determine a refrigerant charging quantity.
5. Model-Specific Electrical Drawings
The supplied electrical drawings are grouped by RAQ unit size and are named for both PREMIUM and PREMIUM-R454B commercial variants. Each includes power circuits, auxiliary circuits, safety circuits, controller wiring, external control connections, component lists and electrical panel layouts.
| Unit Size | Electrical Drawing |
|---|---|
| 15 | RAQ15_ED01.pdf |
| 17 | RAQ17_ED01.pdf |
| 110 | RAQ110_ED01.pdf |
| 112 | RAQ112_ED01.pdf |
| 115 | RAQ115_ED01.pdf |
| 118 | RAQ118_ED01.pdf |
| 120 | RAQ120_ED01.pdf |
| 224 | RAQ224_ED01.pdf |
| 230 | RAQ230_ED01.pdf |
| 234 | RAQ234_ED01.pdf |
| 236 | RAQ236_ED01.pdf |
| 238 | RAQ238_ED01.pdf |
Before wiring: Match the electrical drawing to the complete equipment model, serial number, refrigerant configuration and installed options. Site-specific or revised schematics supplied with the unit take precedence over generic reference drawings.
Additional dimensional drawings
Separate GA RTPU SS drawings have been supplied for PREMIUM15, 17, 110, 112, 115, 118, 224, 230 and 236. These drawings identify supply-air (SA) and return-air (RA) positions.
For stock configurations, the quick reference workbook identifies return air on the right and supply air on the left when facing the unit duct connections from outside. Confirm orientation against the applicable drawing.
- R410A and R454B Single Skin PREMIUM Quick Reference Guide V1.xlsx
- AIRSTAGE R410A RAQ SS RTPU Installation and Operation Manual.pdf
- AIRSTAGE R454B RAQ SS RTPU Installation and Operation Manual.pdf
- General Safety WARNINGS and Instructions R410A Version 25-11-05.pdf
- General Safety WARNINGS and Instructions 2508-A.pdf
GENERAL AIRSTAGE | Technical information for qualified installation and service personnel.