GENERAL AIRSTAGE | TECHNICAL REFERENCE

ARTH24KMTAP / AOTH24KCTA

Ducted Inverter Heat Pump – Design & Technical Manual

R32 Refrigerant | Technical Manual DR_AR057EF_01 | 25 October 2021

About this technical reference

This guide provides key specifications, piping requirements, refrigerant charging information, electrical characteristics, airflow settings, function settings, external control connections and compatible accessories for the ARTH24KMTAP / AOTH24KCTA ducted system.

Important: This article applies specifically to the AOTH24KCTA outdoor unit. Do not substitute refrigerant charging, electrical or control specifications from the AOTH24KBTA model. Installation and servicing must be performed by appropriately qualified personnel.

1. Applicable Models

ComponentModel
Indoor unitARTH24KMTAP
Outdoor unitAOTH24KCTA
System typeDucted R32 inverter heat pump
Rated capacity7.1 kW Cooling / 8.0 kW Heating

2. System Technical Specifications

SpecificationValue
Rated cooling capacity7.1 kW
Cooling capacity range3.3–8.5 kW
Rated heating capacity8.0 kW
Heating capacity range3.6–10.5 kW
Rated cooling input1.85 kW
Rated heating input1.93 kW
Maximum cooling input2.72 kW
Maximum heating input2.89 kW
Rated cooling current8.0 A
Rated heating current8.4 A
Maximum operating current20 A
Supply voltage220–240 V AC, 50 Hz
Permissible voltage range198–264 V
EER – Cooling3.84
COP – Heating4.15
RefrigerantR32

Rated specifications are based on manufacturer test conditions, including a 7.5 m pipe length, zero height difference and 50 Pa standard static pressure.

3. Indoor Unit Dimensions and Airflow

Indoor unit dimensions: 240 H × 1,000 W × 700 D mm

Net weight: 32 kg

Fan type: Twin Sirocco fan

External static pressure range: 50–150 Pa

Fan Speedm³/hL/sCFM
High1,500417883
Medium1,170325689
Low1,020283600
Quiet860239506

Indoor Sound Pressure

HighMediumLowQuiet
38 dB(A)33 dB(A)30 dB(A)27 dB(A)
Airflow commissioning: Actual airflow depends on duct resistance and the selected external static pressure. Refer to the fan performance curves on technical manual pages 10–12 when selecting the appropriate static pressure setting.

4. Static Pressure Settings – Function 26

The external static pressure is selected through the wired remote controller using Function 26.

Setting ValueStatic Pressure
0550 Pa
0660 Pa
0770 Pa
0880 Pa
0990 Pa
10100 Pa
11110 Pa
12120 Pa
13130 Pa
14140 Pa
15150 Pa
31Standard 50 Pa – Factory Default
32Automatic airflow adjustment

Settings 16–30 are treated as 150 Pa. Select the setting according to the system duct resistance and the manufacturer's fan performance data.

5. Refrigerant and Piping Requirements

SpecificationAOTH24KCTA
RefrigerantR32
Factory charge1,800 g
Pre-charged pipe length30 m
Maximum pipe length75 m
Maximum height difference30 m
Liquid pipe diameter6.35 mm (1/4 inch)
Gas pipe diameter12.70 mm (1/2 inch)
Connection typeFlare

Additional R32 Refrigerant Charge

Charging rule: No additional charge is required for pipe lengths of 30 m or less. For pipe lengths exceeding 30 m, additional refrigerant is calculated at 20 g per metre above 30 m.
Pipe LengthAdditional R32Total Charge
30 m or less0 g1,800 g
40 m200 g2,000 g
50 m400 g2,200 g
60 m600 g2,400 g
70 m800 g2,600 g
75 m maximum900 g2,700 g

Formula: Additional charge (g) = (Pipe length in metres − 30) × 20, where pipe length exceeds 30 m.

Refrigerant safety: R32 refrigerant handling must comply with applicable regulations. Evacuation, leak testing and charging must be performed using suitable equipment and by appropriately licensed personnel.

6. Outdoor Unit Dimensions and Operating Range

SpecificationValue
Outdoor dimensions H × W × D998 × 940 × 320 mm
Net weight63 kg
CompressorDC Twin Rotary
Cooling outdoor airflow3,910 m³/h
Heating outdoor airflow3,770 m³/h
Cooling sound pressure48 dB(A)
Heating sound pressure50 dB(A)
Cooling outdoor temperature range-10°C to +50°C
Heating outdoor temperature range-15°C to +24°C

Outdoor Installation Clearances

Refer to the installation space diagrams on technical manual pages 50–53. Required clearances vary according to the direction and number of surrounding obstructions.

Installation ScenarioRequirement
Rear obstruction only, top open100 mm minimum rear
Front obstruction only, top open500 mm minimum front
Rear and front obstruction, top open100 mm rear and 500 mm front minimum
Multiple outdoor units250 mm minimum between units; additional clearances depend on arrangement
Mounting above ground50 mm or more above floor level
Important: Do not rely on the simplified clearance table alone for installations with overhead obstacles, multiple units or restricted discharge airflow. Confirm the full installation space diagram for the actual site arrangement.

7. Electrical Characteristics

SpecificationAOTH24KCTA
Supply voltage220–240 V AC
Frequency50 Hz
Maximum operating current20 A
Starting current8.4 A
Circuit breaker – Manual specification25 A
Power cable – Manual reference4.0 mm²
Interconnecting cable – Manual reference1.5 mm²
Interconnecting cable reference length76 m
Electrical installation: The cable sizes and circuit breaker shown are the manufacturer's sample specification. Actual cable selection, circuit protection and installation must comply with applicable local electrical standards, installation conditions and voltage-drop requirements. The manual specifies voltage drop below 2%.

8. Indoor Unit Function Settings

Function settings are accessible through the compatible wired remote controller.

FunctionPurpose
11Filter sign interval
26External static pressure
30 / 31Indoor sensor correction – Cooling / Heating
35 / 36Wired remote sensor correction – Cooling / Heating
40Auto restart
42Temperature sensor selection
43Cold air prevention
44Wireless controller custom code
46External input control
48Auxiliary temperature sensor control
49Cooling fan energy-saving control
60External output selection

Function 42 – Temperature Sensor Selection

SettingDescription
00Indoor unit sensor only – Factory Default
01Both indoor unit and wired remote sensor

Function 48 – Auxiliary Sensor Selection

SettingDescription
00Both sensors
01Wired remote sensor only – Factory Default

Note: Function 48 requires Function 42 to be set to 01 and the remote controller temperature sensor to be enabled.

Function 46 – External Input Control

SettingDescription
00Operation / Stop mode 1 – Factory Default
01Setting prohibited
02Forced stop
03Operation / Stop mode 2 – Remote controller disabled for stop condition

Function 60 – External Output Selection

SettingFunction
00Operation status – Factory Default
01–08Setting prohibited
09Error status
10Indoor fan operation status
11External heater output

Other Important Function Settings

FunctionSettingDescription
4000 / 01Auto restart enabled / disabled (00 default)
4300 / 01Cold air prevention enabled / disabled (00 default)
4900 / 01 / 02Energy-saving fan control disabled / enabled / remote controller selection (02 default)
Applying function settings: After changing indoor unit function settings, turn the power off, wait at least 30 seconds and restore power. The manufacturer states that the changes will not become effective without a power cycle.

9. Indoor PCB External Input / Output

ConnectionPurpose
Terminals 1–2Operation / Stop / Forced Stop input
CN47External output – Operation, error, fan or heater status
CN75Optional external input/output PCB

External input wiring: Twisted pair 22 AWG, maximum 150 m. Route separately from power cables.

CN47 output: High DC 12 V ± 2 V, low 0 V, maximum 50 mA, maximum cable length 25 m.

Optional UTY-XCSX PCB: Supports dry contact or applied-voltage inputs and external output contacts. Refer to manual pages 16–26 for the correct input/output combinations, wiring diagrams and rotary switch positions.

10. Group Control and Addressing

  • Up to 16 indoor units can be connected in a remote controller group.
  • Maximum combined remote controller cable length: 500 m.
  • Non-polar 2-wire controllers use automatic indoor address setting.
  • Polar 3-wire systems use manual remote controller address allocation.
  • Manual addressing is limited to 15 indoor units, as specified in the manual.
  • Each manually addressed indoor unit must have a unique address.

The indoor PCB SW100 DIP switches 1–4 provide remote controller address settings 00–15. Factory setting is address 00, with all four switches OFF.

Indoor PCB SW101

SwitchFunction
1Drainage function: OFF enabled (factory), ON disabled
2Setting change prohibited
3Auxiliary heater fan delay: ON enabled, OFF disabled (factory)
4Setting change prohibited

11. AOTH24KCTA Outdoor PCB Controls

The AOTH24KCTA includes outdoor control functions that are configured through the outdoor PCB and optional external control connections.

Outdoor PCB External Connections

ConnectorFunction
P580Low noise mode external input
PA580Peak cut mode external input
P590Error status external output
PA590Compressor operating status external output

Outdoor PCB Push Buttons

SwitchNameFunction
S134MODESwitches between local settings and error code display
S133SELECTSelects settings and display items
S132ENTERConfirms selected items
S131EXITReturns to operation status display
S130PUMP DOWNPump-down operation

Low Noise Mode

Low noise mode reduces outdoor operating noise when activated through the external control input and configured at the outdoor PCB.

  1. Stop the air conditioner before performing outdoor local settings.
  2. Press and hold MODE (S134) for at least 3 seconds.
  3. Confirm the POWER/MODE LED blinks 9 times, then press ENTER (S132).
  4. Use SELECT (S133) to locate Low Noise Mode and confirm with ENTER.
  5. Select the required low noise level.
  6. Press ENTER to confirm and EXIT to return to normal operation display.

Two low noise levels are available: Mode 1 – Low and Mode 2 – Lower. Refer to technical manual page 68 for the required LED indication pattern.

Peak Cut Mode

Peak cut mode limits current demand through a dedicated external input and outdoor PCB setting.

  1. Stop the air conditioner before performing settings.
  2. Enter local setting mode using MODE (S134) for at least 3 seconds.
  3. Confirm POWER/MODE blinks 9 times, then press ENTER.
  4. Use SELECT to locate Peak Cut Mode.
  5. Press ENTER and select the required peak cut level using the displayed LED indications.
  6. Confirm and return to normal operating display using EXIT.

Refer to technical manual page 69 for the peak cut setting and LED indication combinations.

Outdoor control safety: The outdoor PCB contains live electrical components. Only suitably qualified personnel should access the PCB or perform local configuration. Refer to the manufacturer's full procedures before operating pump-down or altering protective functions.

12. Safety Devices and Protection

ProtectionOperation
Indoor PCB fuse250 V, 5 A
Indoor fan motor protectionStops at 115 ±15°C; restarts at 70°C
Outdoor fan motor thermal protectionStops at 150 ±15°C; restarts at 120 ±15°C
Compressor discharge temperature protectionStops at 110°C; restart after 7 minutes
Compressor temperature protectionStops at 108°C; restarts at 80°C or less
Outdoor temperature protection in Cooling/DryStops at -20°C; restarts at -15°C

Protection operation should be investigated before attempting to restore normal operation. Do not bypass safety devices.

13. Compatible Controllers and Accessories

Remote Controllers

ModelDescription
UTY-RNRT*Touchscreen wired controller – Non-polar 2-wire
UTY-RNRYT*Wired controller – Non-polar 2-wire
UTY-RVNYNWired controller – Polar 3-wire
UTY-RSRYTSimple controller – Non-polar 2-wire
UTY-RHRYTSimple controller – Non-polar 2-wire
UTY-RSNYNSimple controller – Polar 3-wire
UTY-LBTYMWireless remote and IR receiver kit

Optional Interface Accessories

ModelDescription
UTY-XSZXRemote temperature sensor
UTD-LFDBLong-life filter
UTY-XWZXZGIndoor external output connect kit
UTY-XCSXIndoor external input/output PCB
UTZ-GXDAExternal input/output PCB box
UTY-CDPXZC / UTY-CDPXZDZone interface – Polar 3-wire
UTY-CDRXZC / UTY-CDRXZDZone interface – Non-polar 2-wire
UTY-VMSXModbus converter
UTY-VKSXKNX converter
UTY-VTGX / UTY-VTGXVNetwork converter
UTY-TERXExternal switch controller
UTY-XWZXZ3Outdoor external input/output connect kit

14. Commissioning and Service Checklist

Recommended checks
  1. Confirm indoor model ARTH24KMTAP and outdoor model AOTH24KCTA.
  2. Confirm supply voltage, circuit protection and correct wiring.
  3. Verify installation clearances and outdoor airflow paths.
  4. Confirm pipe sizes, pipe length and height difference.
  5. Calculate additional R32 charge for pipe lengths above 30 m.
  6. Complete the required pressure testing, evacuation and leak checks.
  7. Confirm indoor airflow and Function 26 static pressure setting.
  8. Verify controller temperature sensor selection and operation.
  9. Check group addressing and any external control wiring.
  10. Verify outdoor low noise or peak cut settings if fitted.
  11. Confirm cooling and heating performance under the actual operating conditions.
  12. Record commissioning results for future technical reference.

15. Manual Reference Guide

For detailed electrical wiring diagrams, refrigerant circuits, capacity tables, service clearances and PCB LED patterns, use the relevant sections of technical manual DR_AR057EF_01.

Technical TopicManual Page
Indoor specifications2–3
Indoor dimensions and maintenance space4–7
Indoor wiring diagram8
Capacity tables9
Fan performance curves10–13
Indoor external input/output16–26
Group control27–28
Indoor function settings31–40
Controller and accessory compatibility42–45
Outdoor specifications and dimensions48–49
Outdoor installation clearances50–53
Refrigerant circuit and wiring diagram54–55
Pipe length compensation56
Additional R32 charge57
Electrical characteristics and protections60–61
Outdoor external input/output62–65
Outdoor PCB local function settings66–69
Safety and technical limitation

This article is a technical reference summary and does not replace the manufacturer's installation manual, detailed wiring diagrams, safety procedures or applicable regulations. Confirm model-specific data before servicing.