GENERAL AIRSTAGE | TECHNICAL REFERENCE

ARTH18KMTAP / ARTH24KMTAP

Ducted Inverter Heat Pump – Design & Technical Manual

Outdoor Units: AOTH18KBTA / AOTH24KBTA

Technical Manual DR_AR056EF_01 | 25 October 2021 | R32 Refrigerant

About this technical reference

This guide provides installation, performance, refrigerant, electrical and control information for the ARTH18KMTAP and ARTH24KMTAP ducted air conditioning systems.

It is intended for qualified installation and service technicians.

1. Applicable Models

Indoor UnitOutdoor UnitSystem
ARTH18KMTAPAOTH18KBTA5.0 kW Cooling / 6.0 kW Heating
ARTH24KMTAPAOTH24KBTA7.1 kW Cooling / 8.0 kW Heating

2. Technical Specifications

Specification18 Class24 Class
Rated cooling capacity5.0 kW7.1 kW
Cooling capacity range0.9–6.4 kW1.8–8.1 kW
Rated heating capacity6.0 kW8.0 kW
Heating capacity range0.9–7.8 kW2.0–9.1 kW
Rated cooling input1.37 kW2.15 kW
Rated heating input1.58 kW2.19 kW
Rated cooling current5.9 A9.1 A
Rated heating current6.8 A9.2 A
Maximum operating current12.7 A13.6 A
Power supply220–240 V AC, 50 Hz
Allowable voltage198–264 V
RefrigerantR32

3. Indoor Unit Dimensions & Airflow

Indoor dimensions: 240 H × 1,000 W × 700 D mm

Indoor unit weight: 32 kg

External static pressure: 50–150 Pa

Fan SpeedARTH18KMTAPARTH24KMTAP
High1,080 m³/h1,500 m³/h
Medium860 m³/h1,170 m³/h
Low760 m³/h1,020 m³/h
Quiet650 m³/h860 m³/h
Technical Note – Airflow

Actual airflow will depend on ductwork resistance and the selected external static pressure setting. Refer to the fan performance curves in the design and technical manual when commissioning or investigating airflow issues.

4. External Static Pressure Settings

External static pressure is configured using Function 26 through the wired remote controller.

FunctionSettingDescription
260550 Pa
260660 Pa
260770 Pa
260880 Pa
260990 Pa
2610100 Pa
2611110 Pa
2612120 Pa
2613130 Pa
2614140 Pa
2615150 Pa
2631Standard 50 Pa – Factory Default
2632Automatic airflow adjustment

5. Refrigerant & Piping Specifications

SpecificationAOTH18KBTAAOTH24KBTA
RefrigerantR32
Factory refrigerant charge1,020 g1,250 g
Pre-charged pipe length20 m
Maximum piping length30 m
Maximum height difference20 m25 m
Liquid pipe6.35 mm (1/4 inch)
Gas pipe12.70 mm (1/2 inch)
Connection methodFlare
Important – Additional Refrigerant

For pipe runs exceeding the factory pre-charge length of 20 m, calculate the additional refrigerant according to Section 7, page 63 of the design and technical manual. Do not estimate the charge.

Only appropriately licensed personnel should undertake refrigerant handling.

6. Operating Temperature Range

ModeOutdoor Temperature Range
Cooling-10°C to +50°C
Heating-15°C to +24°C

The specified cooling range is subject to the manufacturer's outdoor unit suction temperature conditions. Protective operation may occur outside the stated operating range.

7. Function Settings

Function settings can be configured using the compatible wired remote controller.

FunctionDescription
11Filter notification interval
26External static pressure
30 / 31Indoor temperature sensor correction – Cooling / Heating
35 / 36Wired controller temperature sensor correction
40Automatic restart following power interruption
42Temperature sensor switching
43Cold air prevention
44Wireless controller custom code
46External input operation / forced stop
48Auxiliary temperature sensor selection
49Indoor fan energy-saving control during cooling
60External output functions

Function 42 – Temperature Sensor Selection

SettingDescription
00Indoor unit temperature sensor – Factory Default
01Both indoor and wired remote controller sensors

Function 48 – Auxiliary Temperature Sensor

SettingDescription
00Both sensors
01Wired remote controller sensor only – Factory Default

Important: Function 48 requires Function 42 to be configured as 01.

Function 46 – External Input Control

SettingDescription
00Operation / Stop mode 1 – Factory Default
01Setting prohibited
02Forced stop
03Operation / Stop mode 2

Function 60 – External Output

SettingOutput Function
00Operation status – Factory Default
01–08Setting prohibited
09Error status
10Indoor fan operating status
11External heater output

8. External Input and Output Connections

The indoor PCB supports external input and output functions through designated terminals and connectors.

ConnectionFunction
Indoor input terminal 1–2Operation / Stop or Forced Stop
CN47External output connection
CN75Optional external input/output PCB connection

CN47 output specifications:

  • High output: DC 12 V ± 2 V
  • Low output: 0 V
  • Maximum permissible current: 50 mA
  • Recommended cable: Twisted pair, 22 AWG
  • Maximum output cable length: 25 m

External input cable: Twisted pair 22 AWG, maximum 150 m, separated from power cabling.

For optional UTY-XCSX external input/output PCB wiring, refer to the manual's detailed dry-contact, applied-voltage and relay wiring diagrams.

9. Group Control

The wired controller group connection arrangement supports:

  • Up to 16 indoor units in a group control system.
  • Maximum total remote controller cable length: 500 m.
  • Non-polar 2-wire remote controller connection.
  • Polar 3-wire remote controller connection.
Important – Addressing

Non-polar 2-wire systems use automatic controller address allocation during initial startup. Polar 3-wire systems require appropriate remote controller addressing. In manual addressing arrangements, the manual specifies a maximum of 15 indoor units.

10. Outdoor Unit Specifications

SpecificationAOTH18KBTAAOTH24KBTA
Dimensions H × W × D632 × 799 × 290 mm716 × 820 × 315 mm
Net weight36 kg42 kg
Compressor typeDC Twin Rotary
Cooling outdoor airflow2,020 m³/h2,150 m³/h
Heating outdoor airflow1,830 m³/h2,440 m³/h
Sound pressure – Cooling48 dB(A)48 dB(A)
Sound pressure – Heating49 dB(A)50 dB(A)

11. Compatible Controllers

ModelDescription
UTY-RNRT*Touchscreen wired controller – Non-polar 2-wire
UTY-RNRYT*Wired controller – Non-polar 2-wire
UTY-RVNYNWired controller – Polar 3-wire
UTY-RSRYTSimple wired controller – Non-polar 2-wire
UTY-RHRYTSimple wired controller – Non-polar 2-wire
UTY-RSNYNSimple wired controller – Polar 3-wire
UTY-LBTYMWireless remote and IR receiver kit

12. Optional Accessories and Interfaces

AccessoryDescription
UTY-XSZXRemote temperature sensor
UTD-LFDBLong-life air filter
UTY-XWZXZGExternal output connection kit
UTY-XCSXExternal input/output PCB
UTZ-GXDAExternal input/output PCB box
UTY-CDPXZC / UTY-CDPXZDZone control interface – Polar 3-wire
UTY-CDRXZC / UTY-CDRXZDZone control interface – Non-polar 2-wire
UTY-VMSXModbus converter
UTY-VKSXKNX converter
UTY-VTGX / UTY-VTGXVNetwork converters
UTY-TERXExternal switch controller

13. Service and Commissioning Notes

Recommended service checks
  1. Confirm the indoor and outdoor model pairing.
  2. Verify supply voltage and power connections.
  3. Check return air, supply air and ductwork restrictions.
  4. Confirm Function 26 external static pressure settings.
  5. Check refrigerant pipe length and any additional charge requirement.
  6. Confirm temperature sensor selection and controller function settings.
  7. Check external control signals where fitted.
  8. Review installation clearances and outdoor unit airflow restrictions.
  9. Refer to the applicable wiring diagrams before electrical diagnosis.
Safety Notice

Always isolate the power supply before accessing internal electrical components. Refrigerant, electrical and mechanical servicing must be undertaken by appropriately qualified personnel.

Refer to the relevant installation manual and the complete technical manual for detailed diagrams, installation requirements and model-specific service procedures.

GENERAL AIRSTAGE

Technical Reference: ARTH18KMTAP / ARTH24KMTAP

Source: Design & Technical Manual DR_AR056EF_01 – 25 October 2021

Specifications and product information may be subject to change.