VRF Quick Commissioning Guide

Outdoor Addressing, Auto Addressing & Capacity / Connection Check

Purpose: This quick guide covers the main commissioning steps required to set the outdoor refrigerant address, automatically address indoor units and complete the indoor unit capacity / connection check.

1. Set Outdoor Unit Refrigerant Address

Each VRF system must have a unique refrigerant circuit address.

SystemREF AD x10REF AD x1
Single VRF system00
First system on multi-system site01
Second system on multi-system site02
Note: Factory setting is 00. For multiple systems, continue sequentially as required.

2. Indoor Unit Auto Addressing

Use the push buttons on the outdoor unit PCB.

PRESS MODE / EXIT
↓
F1
↓
PRESS SELECT
↓
F2
↓
PRESS SELECT
↓
F3
↓
PRESS ENTER
↓
11--
↓
PUSH AND HOLD ENTER
↓
run
Auto addressing can take up to 10 minutes.
Once complete, confirm the number of indoor units found and ensure there are no addressing errors.

3. Indoor Unit Capacity / Connection Check

Before starting: Ensure all indoor units are switched OFF.
PRESS MODE / EXIT
↓
F1
↓
PRESS SELECT
↓
F2
↓
PRESS SELECT
↓
F3
↓
PRESS ENTER
↓
00--
↓
PRESS SELECT
↓
12--
↓
PUSH AND HOLD ENTER
↓
run

Check Indoor Unit Count

U  8

Example: 8 indoor units detected

Check Capacity Ratio

PRESS SELECT

C120

Example: 120% connected indoor unit capacity

Confirm Result

PRESS ENTER

PASS

If the display shows Err, press ENTER to view the error detail.

ErrorDescription
22.1Connecting indoor units capacity error
24.2Connecting number of indoor unit error
26.1Dual / duplicate address exists
Quick Reference
Auto Addressing: F3 → 11 → Hold ENTER → run
Capacity Check: F3 → 12 → Hold ENTER → run
Confirm: Indoor Count → Capacity Ratio → PASS