GENERAL AIRSTAGE | Technical Reference

Group Connection for Split & Multi Split Models

Remote controller group wiring, cable sizing and multi-split restrictions
Reference: Product News RAC-16-001  |  Issued 19 February 2016
This bulletin confirms that group connection of remote controllers is permitted on the applicable split and multi-split models listed below, subject to the wiring, addressing and refrigerant-system requirements in this article.
Important: Group connection on a multi-split system is permitted only within the same refrigerant system. Do not connect the remote-controller group wiring across separate refrigerant systems.

1. Applicable systems

System typeApplicable products
Split modelsWall mounted LT / LU / LM / LF series and floor type models listed in the bulletin appendix.
Multi-split models2-room, 3-room, 4-room and 8-room multi type systems, subject to the restrictions in Section 5.
Production dateModels produced in 2013 or later are applicable.
Cassette and ducted modelsGroup connection was already available for cassette and duct models when this bulletin was issued.

2. Remote controller wiring requirements

Electrical work: Installation must comply with applicable national wiring regulations and must be carried out by authorised personnel.

The maximum total remote-controller cable length for the wall-mounted and floor-type group connection is 300 m (984 ft). Cable cross-section must increase when the total length exceeds 100 m.

Total remote controller cable lengthRequired cable cross-section
100 m (328 ft) or less0.3-0.8 mm² (AWG 18-22)
100-200 m (328-656 ft)0.5-0.8 mm² (AWG 18-20)
200-300 m (656-984 ft)0.8 mm² (AWG 18)

Crimp terminal specification

The bulletin specifies the following crimping terminal and insulation cap, or an equivalent part that fulfils the application:

ManufacturerJ.S.T. MFG. CO., LTD
Part numberCE2 (CE-230V)
Conductor material / finishOxygen-free copper, tin coated
Insulating materialUL94-0
Contact resistance1.2 mΩ or less
Tension strength40 N or more
Ratchet hand toolYS-1614

3. Group wiring method

Typical group connection
Indoor unit 1↔Indoor unit 2↔Other indoor units / wired remote controller
Remote controller group wiring is interconnected between the applicable indoor units and controller.
  • A communication kit is required for compact wall-mounted types.
  • The wiring example in the bulletin uses a 2-wire connector, Service Part No. 9705932012.
  • When using the wall-mounted communication kit, store the crimp terminals inside the communication kit.
  • Conceal group-connection wiring inside the wall or protect it using trunking with a thickness of 1 mm or more.
  • Bundle the wiring with a cable tie so external force is not applied to the crimp terminals. The splice position must provide 10 N or greater tensile strength.

4. Wireless remote controller RC addressing

For group connection using wireless remote controllers, set an individual RC address through the indoor-unit function setting procedure.

SettingFunction numberSetting value
RC (Remote Controller) address0000-15   (Factory setting: 00)
1Enter the wireless remote controller Function Setting mode. Refer to the applicable indoor-unit installation manual for the exact entry procedure.
2Select Function Number 00.
3Set the required RC address from 00 to 15.
A temporary error may be displayed immediately after power is turned on while the group-connection settings are incomplete. The bulletin states that this error will clear automatically once the subsequent function setting is completed.

5. Multi-split group connection rules

RuleRequirement
AApply the wall-mounted / floor-type wiring requirements in Sections 2 and 3.
BGroup connection is allowed only within the same refrigerant system.
CDO NOT bridge the remote-controller group wiring between separate refrigerant systems.
DGroup connection is permitted on an 8-room multi system, but the UTY-DMM*M home controller cannot be connected at the same time.
Allowed - same refrigerant system
Indoor 1 ↔ Indoor 2 ↔ Wired RC
All indoor units are connected to the same outdoor refrigerant system.
Not allowed - separate refrigerant systems
System A indoor ✖ System B indoor
Do not interconnect the remote-controller group wiring across different refrigerant systems.

6. Commissioning checklist

✓Confirm the indoor model is covered by this bulletin and was produced in 2013 or later.
✓Confirm total remote-controller cable length does not exceed 300 m and cable size matches the total length.
✓Confirm crimp joints are insulated, protected from strain and secured to the specified tensile requirement.
✓For compact wall-mounted models, confirm the required communication kit is fitted.
✓Where wireless remote controllers are used, confirm RC addresses are correctly assigned using Function 00.
✓For multi-split systems, confirm all grouped indoor units are on the same refrigerant system.
✓On an 8-room multi system, confirm a UTY-DMM*M home controller is not being used simultaneously with the group connection.

7. Applicable model list from RAC-16-001

The original bulletin appendix lists the following 141 model references. The 2013-or-later production requirement still applies.
Models 1-50Models 51-100Models 101-141
1ASAG18LFCA51ASHG30LFCA101ASWG12LMCB
2ASAG24LFCA52ASQG09LTCB-W102ASWG18LFCA
3ASBG18LFCA53ASQG12LTCB-N103ASWG18LFCB
4ASBG24LFCA54ASQG12LTCB-W104ASWG24LFCB
5ASBG07LMCA55ASQG09LUCB105ASYG07LMCA
6ASBG07LMCA56ASQG12LUCB106ASYG09LMCA
7ASBG09LMCA57ASQG07LMCB107ASYG09LMCB
8ASBG09LMCA58ASQG09LMCA108ASYG12LMCA
9ASBG12LMCA59ASQG09LMCA-W109ASYG12LMCB
10ASBG12LMCA60ASQG09LMCB110ASYG14LMCA
11ASCG25LTCA61ASQG09LMCC111ASYG14LMCB
12ASCG32LTCA62ASQG12LMCA112ASYG09LTCA
13ASCG40LTCA63ASQG12LMCA-W113ASYG09LTCB
14ASCG07LMCA64ASQG12LMCB114ASYG12LTCA
15ASCG22LMT65ASQG12LMCC115ASYG12LTCB
16ASCG09LMCA66ASQG18LMCA-W116ASYG14LTCB
17ASCG28LMT67ASQG24LMCA-W117ASYG07LUCA
18ASCG12LMCA68ASQG18LFCA118ASYG09LUCA
19ASCG36LMT69ASQG24LFCA119ASYG12LUCA
20ASCG14LMCA70ASTG09LUCB120ASYG14LUCA
21ASCG40LMT71ASTG14LUCB121ASYG18LFCA
22ASCG18LFCA72ASTG18LUCB122ASYG24LFCA
23ASCG18LFCB73ASTG09KMCA123ASYG24LFCC
24ASCG22LFCA74ASTG09KUCA124ASYG30LFCA
25ASCG24LFCA75ASTG12KMCA125AGBG09LVCA
26ASCG30LFCA76ASTG12KUCA126AGBG12LVCA
27ASGG18LFCA77ASTG18KMCA127AGHG09LVCA
28ASGG18LFCD78ASTG18KUCA128AGHG09LVCB
29ASGG24LFCA79ASTG22KMCA129AGHG12LVCA
30ASGG24LFCD80ASTG24KMCA130AGHG12LVCB
31ASGG30LFCD81ASTG30KMTA131AGHG14LVCA
32ASHG09LTCA82ASTG34KMTA132AGHG14LVCB
33ASHG09LTCB83ASTG18LFCA133AGU9RLF
34ASHG12LTCA84ASTG24LFCC134AGU12RLF
35ASHG12LTCB85ASTG30LFCC135AGU15RLF
36ASHG14LTCB86ASTG34LFCC136AGYG09LVCA
37ASHG07LUCA87ASU9RLS2137AGYG09LVCB
38ASHG09LUCA88ASU12RLS2138AGYG12LVCA
39ASHG12LUCA89ASU15RLS2139AGYG12LVCB
40ASHG14LUCA90ASU7RLF1140AGYG14LVCA
41ASHG07LMCA91ASU9RLF1141AGYG14LVCB
42ASHG09LMCA92ASU12RLF1 
43ASHG09LMCB93ASU18RLF 
44ASHG12LMCA94ASU24RLF 
45ASHG12LMCB95ASWG09LTCA 
46ASHG14LMCA96ASWG14LTCA 
47ASHG14LMCB97ASWG18LTCA 
48ASHG18LFCA98ASWG09LMCA 
49ASHG24LFCA99ASWG09LMCB 
50ASHG24LFCC100ASWG12LMCA 
Technical note: This article is based on Product News RAC-16-001. Always confirm the exact model, current installation manual and applicable electrical requirements before carrying out wiring changes. Installation and testing must be completed by appropriately authorised personnel.