GENERAL AIRSTAGE Technical Reference
ARTH36-60KHTA High Static Three Phase
Design & Technical Manual - key specifications, airflow, controls and installation data
Indoor: ARTH36KHTA / ARTH45KHTA / ARTH54KHTA / ARTH60KHTA | Outdoor: AOTH36KRTA / AOTH45KRTA / AOTH54KRTA / AOTH60KRTA
This article provides a quick technical reference for the R32 high static three-phase ducted range. It summarises the most commonly required design, selection, installation and control information from Design & Technical Manual DR_AR083EF_01.
Important: This article is a quick reference only. Installation, refrigerant handling, electrical work and commissioning must be completed by appropriately qualified personnel and in accordance with the applicable installation manuals, regulations and local standards.
1. Model combinations
| System size | Indoor unit | Outdoor unit | Power supply |
|---|
| 36 | ARTH36KHTA | AOTH36KRTA | 380-415 V 3N~, 50 Hz |
| 45 | ARTH45KHTA | AOTH45KRTA | 380-415 V 3N~, 50 Hz |
| 54 | ARTH54KHTA | AOTH54KRTA | 380-415 V 3N~, 50 Hz |
| 60 | ARTH60KHTA | AOTH60KRTA | 380-415 V 3N~, 50 Hz |
2. Key system specifications
| Model | Rated cooling | Rated heating | High airflow | Static pressure range |
|---|
| ARTH36KHTA | 10.0 kW | 11.2 kW | 2,500 m³/h (695 L/s) | 60-210 Pa |
| ARTH45KHTA | 12.5 kW | 14.0 kW | 3,250 m³/h (903 L/s) | 60-260 Pa |
| ARTH54KHTA | 14.0 kW | 15.5 kW | 3,550 m³/h (986 L/s) | 60-260 Pa |
| ARTH60KHTA | 15.5 kW | 18.0 kW | 3,550 m³/h (986 L/s) | 60-260 Pa |
Indoor operating range: Cooling 18-32°C, maximum 80% RH; Heating 16-30°C. The standard static pressure is 60 Pa.
3. Airflow and external static pressure
The indoor fan external static pressure is set using Function 26. Select the value that matches the resistance of the installed duct system and confirm operation against the fan performance curves in the full technical manual.
| Function 26 setting | Static pressure | Notes |
|---|
| 06-21 | 60-210 Pa | Available across the range; 210 Pa is the maximum for the 36 model. |
| 22-26 | 220-260 Pa | 45, 54 and 60 models only. |
| 31 | Standard - 60 Pa | Factory setting. |
| 32 | Automatic airflow adjustment | Use where automatic airflow adjustment is required by the installation. |
Do not simply increase static pressure to correct poor airflow. Confirm duct sizing, filters, grilles, dampers and total external resistance first. Setting static pressure above the model's maximum range is treated as the maximum available setting.
4. Indoor dimensions and service access
| Indoor unit | Net dimensions (H x W x D) | Net weight |
|---|
| ARTH36KHTA | 400 x 1,050 x 500 mm | 39 kg |
| ARTH45KHTA / ARTH54KHTA / ARTH60KHTA | 425 x 1,250 x 490 mm | 53 kg |
Allow the installation and maintenance clearances specified in the manual. Service access must be retained around the control box, fan section, filters and drain components. Do not install wiring, lighting or other obstructions inside the required maintenance space.
R32 room-size requirement: The minimum permitted room floor area depends on the total refrigerant charge and installation height. Check the minimum room-size table in the technical/installation documentation whenever total system charge is being determined.
5. Refrigerant piping and charge
| Item | Specification |
|---|
| Refrigerant | R32 |
| Liquid pipe | 9.52 mm (3/8 in) |
| Gas pipe | 15.88 mm (5/8 in) |
| Factory pre-charge pipe length | 30 m |
| Maximum pipe length | 50 m |
| Maximum height difference | 30 m |
| Additional refrigerant above 30 m | 40 g/m - maximum additional charge 800 g at 50 m total pipe length |
| Outdoor unit | Factory R32 charge | Outdoor dimensions (H x W x D) | Net weight |
|---|
| AOTH36KRTA | 1.9 kg | 788 x 940 x 320 mm | 53 kg |
| AOTH45KRTA / AOTH54KRTA | 2.7 kg | 998 x 940 x 320 mm | 67 kg |
| AOTH60KRTA | 3.4 kg | 1,418 x 970 x 370 mm | 96 kg |
6. Outdoor operating and electrical data
Outdoor operating range: Cooling -10 to 50°C; Heating -15 to 24°C. These figures are based on outdoor-unit suction temperature and protective operation may occur near or outside operating limits.
| Outdoor | Maximum operating current | Starting current | Outdoor airflow |
|---|
| AOTH36KRTA | 10.5 A | 5.2 A | 3,750 m³/h |
| AOTH45KRTA | 14.0 A | 6.4 A | 4,450 m³/h |
| AOTH54KRTA | 14.0 A | 7.7 A | 4,450 m³/h |
| AOTH60KRTA | 14.5 A | 7.9 A | 7,000 m³/h |
The manual shows a 16 A circuit-breaker example, 2.5 mm² power cable and 1.5 mm² connection cable with a listed limited wiring length of 51 m. Electrical cable and protection selection must still comply with the applicable local electrical regulations and installation requirements.
7. Controls, external input/output and group control
The indoor unit supports wired control, optional wireless control and integration with external devices. Group control can connect up to 16 indoor units with a total remote-controller cable length of up to 500 m. Manual addressing is limited to 15 indoor units.
| Indoor control point | Available function |
|---|
| Indoor terminal | Operation/Stop or Forced Stop using dry-contact input. |
| CN47 | Operation status, error status, indoor fan operation status or external heater output depending on Function 60. |
| UTY-XCSX External I/O PCB | Expanded external input/output including Operation/Stop, Forced Thermostat Off, error, fan status and external heater output. |
Outdoor external control
Using the optional UTY-XWZXZ3 External Connect Kit, the outdoor unit can accept external control or provide status outputs:
- Low Noise Mode input
- Peak Cut Mode input
- Error Status output
- Compressor Status output
Low Noise and Peak Cut inputs use an external contact and the connected device must be within 10 m of the outdoor control PCB. Outdoor status outputs are 12 V DC, 50 mA or less.
8. Common indoor function settings
| Function | Purpose |
|---|
| 11 | Filter sign interval / no indication |
| 26 | External static pressure / automatic airflow adjustment |
| 30 / 31 | Indoor-unit room temperature sensor correction - cooling / heating |
| 35 / 36 | Wired remote-controller sensor correction - cooling / heating |
| 40 | Auto restart |
| 42 / 48 | Room temperature sensor selection |
| 43 | Cold air prevention |
| 46 | External input control - Operation/Stop or Forced Stop |
| 49 | Indoor fan energy-saving control during cooling |
| 60 | External output terminal function |
| 68 / 69 | Auto mode type and dual-setpoint deadband |
After changing indoor function settings: Turn the power off, wait at least 30 seconds, then restore power. Function changes do not become active until the system has been power-cycled.
9. Compatible controllers and optional parts
Controllers
| UTY-RNRT | Touch-panel wired remote controller, non-polar 2-wire. |
| UTY-RNRYT | Touch-panel wired remote controller, non-polar 2-wire. |
| UTY-RVNYN | Wired remote controller, polar 3-wire. |
| UTY-RSRYT / UTY-RHRYT | Simple non-polar 2-wire remote controllers. |
| UTY-RSNYN | Simple polar 3-wire remote controller. |
| UTY-LBTYM | IR receiver kit with wireless remote controller; connects to CN48. |
Other options
- UTY-XSZXT - Remote sensor
- UTD-LF60KA - Long-life filter for 36 model
- UTY-XWZXZG - Indoor external connect kit
- UTY-XCSX - External input/output PCB
- UTZ-GXEA - External I/O PCB box
- UTY-CDPXZC / UTY-CDPXZD - 3-wire zone control interface
- UTY-CDRXZC / UTY-CDRXZD - 2-wire zone control interface
- UTY-VMSX - Modbus converter
- UTY-VKSX - KNX converter
- UTY-VTGX / UTY-VTGXV - Network converters
- UTY-TERX - External switch controller
- UTY-XWZXZ3 - Outdoor external connect kit
10. What the full Design & Technical Manual contains
The full manual should be used whenever detailed engineering data is required. It includes dimensional drawings, installation-space diagrams, wiring schematics, cooling and heating capacity tables, detailed fan-performance curves, sound data, refrigerant circuits, piping compensation data, external I/O diagrams and outdoor local-setting procedures.
| Indoor section | Outdoor section |
|---|
| Specifications, dimensions, installation/maintenance space, wiring diagrams, capacity tables, fan performance, airflow, noise, safety devices, external I/O, group connection, remote controllers, function settings, accessories and options. | Specifications, dimensions, installation space, refrigerant circuit, wiring diagrams, capacity compensation, additional charge calculation, airflow, noise, electrical characteristics, safety devices, external I/O, low-noise/peak-cut settings, accessories and options. |
Source: Design & Technical Manual DR_AR083EF_01 - ARTH36KHTA / ARTH45KHTA / ARTH54KHTA / ARTH60KHTA with AOTH36KRTA / AOTH45KRTA / AOTH54KRTA / AOTH60KRTA, dated 19 January 2023. Product specifications and design may change without notice.