GENERAL AIRSTAGE Technical Reference

ARTH36-60KHTA High Static Three Phase

Design & Technical Manual - key specifications, airflow, controls and installation data
Indoor: ARTH36KHTA / ARTH45KHTA / ARTH54KHTA / ARTH60KHTA  |  Outdoor: AOTH36KRTA / AOTH45KRTA / AOTH54KRTA / AOTH60KRTA
This article provides a quick technical reference for the R32 high static three-phase ducted range. It summarises the most commonly required design, selection, installation and control information from Design & Technical Manual DR_AR083EF_01.
Important: This article is a quick reference only. Installation, refrigerant handling, electrical work and commissioning must be completed by appropriately qualified personnel and in accordance with the applicable installation manuals, regulations and local standards.

1. Model combinations

System sizeIndoor unitOutdoor unitPower supply
36ARTH36KHTAAOTH36KRTA380-415 V 3N~, 50 Hz
45ARTH45KHTAAOTH45KRTA380-415 V 3N~, 50 Hz
54ARTH54KHTAAOTH54KRTA380-415 V 3N~, 50 Hz
60ARTH60KHTAAOTH60KRTA380-415 V 3N~, 50 Hz

2. Key system specifications

ModelRated coolingRated heatingHigh airflowStatic pressure range
ARTH36KHTA10.0 kW11.2 kW2,500 m³/h (695 L/s)60-210 Pa
ARTH45KHTA12.5 kW14.0 kW3,250 m³/h (903 L/s)60-260 Pa
ARTH54KHTA14.0 kW15.5 kW3,550 m³/h (986 L/s)60-260 Pa
ARTH60KHTA15.5 kW18.0 kW3,550 m³/h (986 L/s)60-260 Pa
Indoor operating range: Cooling 18-32°C, maximum 80% RH; Heating 16-30°C. The standard static pressure is 60 Pa.

3. Airflow and external static pressure

The indoor fan external static pressure is set using Function 26. Select the value that matches the resistance of the installed duct system and confirm operation against the fan performance curves in the full technical manual.

Function 26 settingStatic pressureNotes
06-2160-210 PaAvailable across the range; 210 Pa is the maximum for the 36 model.
22-26220-260 Pa45, 54 and 60 models only.
31Standard - 60 PaFactory setting.
32Automatic airflow adjustmentUse where automatic airflow adjustment is required by the installation.
Do not simply increase static pressure to correct poor airflow. Confirm duct sizing, filters, grilles, dampers and total external resistance first. Setting static pressure above the model's maximum range is treated as the maximum available setting.

4. Indoor dimensions and service access

Indoor unitNet dimensions (H x W x D)Net weight
ARTH36KHTA400 x 1,050 x 500 mm39 kg
ARTH45KHTA / ARTH54KHTA / ARTH60KHTA425 x 1,250 x 490 mm53 kg

Allow the installation and maintenance clearances specified in the manual. Service access must be retained around the control box, fan section, filters and drain components. Do not install wiring, lighting or other obstructions inside the required maintenance space.

R32 room-size requirement: The minimum permitted room floor area depends on the total refrigerant charge and installation height. Check the minimum room-size table in the technical/installation documentation whenever total system charge is being determined.

5. Refrigerant piping and charge

ItemSpecification
RefrigerantR32
Liquid pipe9.52 mm (3/8 in)
Gas pipe15.88 mm (5/8 in)
Factory pre-charge pipe length30 m
Maximum pipe length50 m
Maximum height difference30 m
Additional refrigerant above 30 m40 g/m - maximum additional charge 800 g at 50 m total pipe length
Outdoor unitFactory R32 chargeOutdoor dimensions (H x W x D)Net weight
AOTH36KRTA1.9 kg788 x 940 x 320 mm53 kg
AOTH45KRTA / AOTH54KRTA2.7 kg998 x 940 x 320 mm67 kg
AOTH60KRTA3.4 kg1,418 x 970 x 370 mm96 kg

6. Outdoor operating and electrical data

Outdoor operating range: Cooling -10 to 50°C; Heating -15 to 24°C. These figures are based on outdoor-unit suction temperature and protective operation may occur near or outside operating limits.
OutdoorMaximum operating currentStarting currentOutdoor airflow
AOTH36KRTA10.5 A5.2 A3,750 m³/h
AOTH45KRTA14.0 A6.4 A4,450 m³/h
AOTH54KRTA14.0 A7.7 A4,450 m³/h
AOTH60KRTA14.5 A7.9 A7,000 m³/h
The manual shows a 16 A circuit-breaker example, 2.5 mm² power cable and 1.5 mm² connection cable with a listed limited wiring length of 51 m. Electrical cable and protection selection must still comply with the applicable local electrical regulations and installation requirements.

7. Controls, external input/output and group control

The indoor unit supports wired control, optional wireless control and integration with external devices. Group control can connect up to 16 indoor units with a total remote-controller cable length of up to 500 m. Manual addressing is limited to 15 indoor units.

Indoor control pointAvailable function
Indoor terminalOperation/Stop or Forced Stop using dry-contact input.
CN47Operation status, error status, indoor fan operation status or external heater output depending on Function 60.
UTY-XCSX External I/O PCBExpanded external input/output including Operation/Stop, Forced Thermostat Off, error, fan status and external heater output.

Outdoor external control

Using the optional UTY-XWZXZ3 External Connect Kit, the outdoor unit can accept external control or provide status outputs:

  • Low Noise Mode input
  • Peak Cut Mode input
  • Error Status output
  • Compressor Status output

Low Noise and Peak Cut inputs use an external contact and the connected device must be within 10 m of the outdoor control PCB. Outdoor status outputs are 12 V DC, 50 mA or less.

8. Common indoor function settings

FunctionPurpose
11Filter sign interval / no indication
26External static pressure / automatic airflow adjustment
30 / 31Indoor-unit room temperature sensor correction - cooling / heating
35 / 36Wired remote-controller sensor correction - cooling / heating
40Auto restart
42 / 48Room temperature sensor selection
43Cold air prevention
46External input control - Operation/Stop or Forced Stop
49Indoor fan energy-saving control during cooling
60External output terminal function
68 / 69Auto mode type and dual-setpoint deadband
After changing indoor function settings: Turn the power off, wait at least 30 seconds, then restore power. Function changes do not become active until the system has been power-cycled.

9. Compatible controllers and optional parts

Controllers

UTY-RNRTTouch-panel wired remote controller, non-polar 2-wire.
UTY-RNRYTTouch-panel wired remote controller, non-polar 2-wire.
UTY-RVNYNWired remote controller, polar 3-wire.
UTY-RSRYT / UTY-RHRYTSimple non-polar 2-wire remote controllers.
UTY-RSNYNSimple polar 3-wire remote controller.
UTY-LBTYMIR receiver kit with wireless remote controller; connects to CN48.

Other options

  • UTY-XSZXT - Remote sensor
  • UTD-LF60KA - Long-life filter for 36 model
  • UTY-XWZXZG - Indoor external connect kit
  • UTY-XCSX - External input/output PCB
  • UTZ-GXEA - External I/O PCB box
  • UTY-CDPXZC / UTY-CDPXZD - 3-wire zone control interface
  • UTY-CDRXZC / UTY-CDRXZD - 2-wire zone control interface
  • UTY-VMSX - Modbus converter
  • UTY-VKSX - KNX converter
  • UTY-VTGX / UTY-VTGXV - Network converters
  • UTY-TERX - External switch controller
  • UTY-XWZXZ3 - Outdoor external connect kit

10. What the full Design & Technical Manual contains

The full manual should be used whenever detailed engineering data is required. It includes dimensional drawings, installation-space diagrams, wiring schematics, cooling and heating capacity tables, detailed fan-performance curves, sound data, refrigerant circuits, piping compensation data, external I/O diagrams and outdoor local-setting procedures.
Indoor sectionOutdoor section
Specifications, dimensions, installation/maintenance space, wiring diagrams, capacity tables, fan performance, airflow, noise, safety devices, external I/O, group connection, remote controllers, function settings, accessories and options.Specifications, dimensions, installation space, refrigerant circuit, wiring diagrams, capacity compensation, additional charge calculation, airflow, noise, electrical characteristics, safety devices, external I/O, low-noise/peak-cut settings, accessories and options.
Source: Design & Technical Manual DR_AR083EF_01 - ARTH36KHTA / ARTH45KHTA / ARTH54KHTA / ARTH60KHTA with AOTH36KRTA / AOTH45KRTA / AOTH54KRTA / AOTH60KRTA, dated 19 January 2023. Product specifications and design may change without notice.