GENERAL AIRSTAGE | Technical Reference

MultiPower Chiller & Heat Pump

Service, hydronic, electrical, controller and defrost reference
For GENERAL AIRSTAGE multi-scroll liquid chiller and reversible heat-pump applications.
Purpose: This article consolidates key service-training information for MultiPower chiller and heat-pump systems, including configuration identification, hydronic requirements, electrical checks, BMS interfaces, UNICO controller operation, compressor timers and defrost control.
Safety: Chiller service work includes mains voltage, pressurised refrigerant circuits and pressurised hydronic systems. Work must only be carried out by appropriately qualified personnel. Always use the wiring diagram and installation/operation documentation supplied with the specific unit before changing wiring or parameters.

1. Product variants and factory-fitted options

VariantConfiguration
CHA/KCooling only
CHA/K/WPReversible heat pump
CHA/K/SSLSuper-silenced cooling only
CHA/K/WP/SSLSuper-silenced reversible heat pump
CodeFactory-fitted optionCodeFactory-fitted option
SLUnit silencingRFMCooling-circuit shut-off valve on discharge line
CTCondensing control down to 0°CCCCondensing control down to -20°C
BTLow-water-temperature kitECEC inverter fans
ECHEC inverter fans with high available static pressureDSDesuperheater
RTTotal heat recoveryTXCoil with pre-coated fins
EWExternal water connectionsPSSingle circulating pump
PSIInverter single circulating pumpPDDouble circulating pump
PDIInverter double circulating pumpSSSoft start
ISModbus RTU, RS485 serial interfaceISTModbus TCP/IP, Ethernet port
ISBBACnet MS/TP, RS485 serial interfaceISBTBACnet/IP, Ethernet port
ISLLonWorks, FTT-10 serial interfaceISSSNMP, Ethernet port
IAVRemote set-point, 0–10 V signalIAARemote set-point, 4–20 mA signal
IASRemote signal for second set-point activationIDLDemand limit from digital input
Exact operating envelopes depend on the selected unit configuration and fitted options. Confirm the unit selection data and the specific installation manual before operating outside standard water or ambient conditions.

2. Hydronic system requirements

Water filtration

  • Install the water filter on the machine inlet side.
  • Square-mesh filter maximum opening: 0.8 mm up to DN80.
  • Square-mesh filter maximum opening: 1.6 mm up to DN150.
  • Filters must be cleaned periodically.

Minimum system water volume

Cooling-only version
M > 9.45 × k × n / N × (Qf − q)
Heat-pump version
M > 9.45 × k × n / N × (Qt − q) + 2.37 × (Qt − q)
SymbolMeaning
MMinimum water content (L)
kFactor accounting for the water-temperature difference between evaporator/condenser inlet and outlet
nPartition coefficient: n=1 up to 4 compressors; n=2 for units with more than 4 compressors
NNumber of compressors
QfCooling capacity (kW)
QtHeating capacity (kW)
qPermanent thermal load in the system (kW); use q=0 if unknown
ΔT (K)345678910
k1111.051.101.151.201.25
  • For process applications, the source recommends 50% higher water content to stabilise outlet temperature.
  • If circuit volume is insufficient, add an inertial storage/buffer tank so total system volume reaches the calculated requirement.

Water quality guidance

Water quality is critical to unit performance and heat-exchanger life. The source rates compatibility for AISI 316L and copper using: 1 = good corrosion resistance, 2 = corrosion may occur when multiple adverse factors are present, 3 = use not recommended.

ParameterRangeAISI 316LCopper
pH<622
6–7.522
7.5–911
>912
Alkalinity (HCO3)<70 mg/L12
70–300 mg/L11
>300 mg/L12
Sulphate (SO4²−)<70 mg/L11
70–300 mg/L13
>300 mg/L13
Alkalinity / sulphateHCO3− / SO4²− >111
HCO3− / SO4²− <113
Electrical conductivity<10 µS/cm12
10–500 µS/cm11
>500 µS/cm12
Ammonium (NH4)<2 mg/L11
2–20 mg/L12
>20 mg/L13
Free chlorine (Cl2)<1 mg/L11
1–5 mg/L31
>5 mg/L33
Hydrogen sulphide (H2S)<0.05 mg/L11
>0.05 mg/L13
Free carbon dioxide (CO2)<5 mg/L11
5–20 mg/L12
>20 mg/L13
Nitrate (NO3)<100 mg/L11
>100 mg/L12
Iron (Fe)<0.2 mg/L11
>0.2 mg/L12
Aluminium (Al)<0.2 mg/L11
>0.2 mg/L12
Manganese (Mn)<0.1 mg/L11
>0.1 mg/L12

Filling a hydronic-kit system

  1. Ensure the main switch is OFF before work begins.
  2. If the hydronic kit is fitted, confirm the pump drain shut-off valve is closed.
  3. Confirm drain valves are closed and air-vent valves are open.
  4. Open the water-system shut-off valves and begin filling.
  5. When water reaches the vent valves, close the vents and bring system pressure to approximately 1–1.5 bar.
  6. The referenced safety-valve calibration is 6 bar.
  7. After pressure stabilises, close the fill valve and check all joints for leaks.

Flow switch and pump sequence

  • The chiller must only operate when water flow is proven.
  • If an external flow switch is required, the source identifies connection at X2 41A–42A.
  • Remote circulating-pump control is shown from the controller at 115–116, 230 V AC output.
  • The pump must start before the chiller and stop after the chiller. Recommended minimum run-on delay: 60 seconds.

3. Freeze protection and glycol

If the system cannot be drained during periods where freezing is possible, or operation is required with water temperatures below 5°C, the source specifies the use of ethylene glycol. Glycol changes system capacity, absorbed power, water flow and pressure drop, so correction factors must be applied.

Glycol10%20%30%40%50%
Tc – Freezing temperature (°C)-4.5-9.5-15.5-21.5-32.5
CQ – Cooling-capacity factor0.9750.9530.9310.9140.882
CP – Electrical-power factor0.9980.9950.9900.9850.975
CG – Water-flow factor1.011.041.081.141.20
Cp – Pressure-drop factor1.051.131.211.261.32
Antifreeze parameter (AIS): Factory setting shown is 3.0°C. When glycol is used, the source states the AIS value must be set to the fluid freezing temperature plus 6 K. The minimum allowable AIS setting must correspond with the glycol percentage in the unit selection data. When an ICE alarm is active, the water pumps will start.

The source recommends checking glycol concentration with a refractometer or equivalent instrument.

4. Electrical, BMS and control interfaces

Three-phase supply and phase monitor

  • Verify L1, L2 and L3 against the unit data plate. The source allows a voltage tolerance of ±5%.
  • Check fuse-holder caps and all power connections inside the electrical enclosure for correct tightness.
  • Where crankcase heaters are fitted, confirm operation. The source check is approximately 10–15°C above ambient at the compressor base.
  • For three-phase versions, verify correct rotation. The source states clockwise when viewed from the motor fan side; if incorrect, swap any two phase conductors below the main switch.
  • 3-phase relay shown: DPA51CM (RF1). LED indication: Green = power ON; Yellow = 3-phase sequence OK.

Compressor oil-heating timer

The controller includes a 180-minute compressor oil-heating delay on initial energisation. Do not remove power during the countdown: the timer will restart at 180 minutes. If a normal-operation power failure exceeds 60 minutes, the timer restarts from 180 minutes. The source states this timer function cannot be deactivated.

The BMS digital-control diagram associates terminals 7–8 with the compressor oil-heating timer bridge. Confirm the unit-specific wiring diagram before altering any bridge or input.

BMS / remote control

Terminal groupFunction shown in training material
X2Remote On/Off; Emergency; general alarm contact (free voltage)
X5Remote display (CR option). For CR installation, the source instructs removal of the 120 Ω electrical resistor.

Electronic expansion-valve control

The training material shows an EKE-1D / EKE-2U based electronic expansion-valve control arrangement. Key items identified are:

  • MD: EKE-1D driver
  • BC1: battery charger / backup module
  • ALD1: AC/DC converter
  • TP3: suction pressure sensor
  • SVT1: suction temperature sensor
  • VT1: electronic thermostatic valve

For the EKE-2U backup arrangement, the source shows ALD1 output adjusted to 24 V DC and the backup module connected to the valve supply. Load-switch position is dependent on valve type and the number of valves; use the unit wiring documentation before changing the switch position.

Main internal service items

AreaItems identified in the source
Refrigerant circuitScroll compressors, suction line, EEV/liquid line, 4-way reversing valve, refrigerant service valves and refrigerant relief valves
ProtectionWater differential pressure switch and manual-reset high-pressure switch
Hydronic kitCirculating pump, insulated hydronic piping and drainage point
Electrical panelMain terminal blocks, main switch, compressor contactors, controller/instrument panel and power-entry points

5. UNICO electronic controller

Training material shown is based on software version 1.05.00, covering chiller and heat-pump configurations with up to 12 scroll compressors, including an inverter scroll plus one or two On/Off scroll compressors.

Water-temperature control

  • EWT (return pipe): controls On/Off compressors.
  • LWT (leaving pipe): controls the inverter plus On/Off compressors.
ParameterFunctionValue shown
SC1Cooling temperature set-point7.5°C
SCLMinimum cooling set-point limit6.0°C
SCHMaximum cooling set-point limit20.0°C
SH1Heating temperature set-point44.5°C
SHLMinimum heating set-point limit35.0°C
SHHMaximum heating set-point limit48.0°C
rC1Cooling proportional band5.0 K
rH1Heating proportional band5.0 K
Modbus note: The source states the SCL, SCH, SHL and SHH limits are not respected when the set-point is adjusted through Modbus. Verify remote-control strategy and site limits before commissioning remote set-point control.

Compressor timing parameters

CodeFunctionValue shown
CT0Minimum ON interval between different compressors30 s
CT1Minimum OFF interval between different compressors2 s
CT2Minimum OFF time for a single compressor60 s
CT3Minimum ON time for a single compressor180 s
CT4Minimum time between two ON cycles of the same compressor300 s
CT5Maximum difference in compressor running hours1440 min
CT6Compressor start delay from evaporator pump30 s
C50Maximum compressor running-hours value10 kh

Evaporator-pump timing

CodeFunctionValue shown
P02Pump OFF delay after compressors stop60 s
P03 / P04Pump burst pulse timesMarked “Not used”
P21Pump rotation type2 – HOUr
P22Maximum run hours to force pump rotation24 h

Starting the unit

The training material identifies four supported start methods:

  • Select Turn ON from the Start menu.
  • Press and hold the UP arrow for 3 seconds.
  • Close the configured digital input.
  • Start via Modbus/BMS.

Status and alarm menus

The Unit Status menu provides access to Input/Output, Compressor Status, Expansion Valve 1/2, Hour Counters, Refrigerant, Water, Sink/Source Regulation and Defrost Status screens. The Alarms Status menu provides Active Alarms, Reset Alarms and Alarm History.

Compressor statusMeaning
ON / OFFNormal compressor running / stopped state
AlarmCompressor is in alarm
CT0, CT1, CT2, CT3, CT4, CT6Compressor is waiting for the corresponding timing parameter to elapse
PdownCompressor is in pump-down phase
DISABCompressor disabled by parameter

6. Heat-pump defrost logic

Defrost demand is determined from refrigerant-circuit conditions, with suction pressure used as a key input. The controller verifies the start condition for a defined period, operates the reversing sequence, maintains a minimum defrost period and terminates defrost based on the configured stop condition or maximum time.

CodeDefrost functionValue shown
d17Number of compressors active during defrost5
d40Defrost start set-point compensation1 – YES
d09Defrost start pressure set-point4.5 barg
d41Defrost pressure set low3.5 barg
d42Defrost temperature set low-5.0°C
d43Defrost pressure set high4.6 barg
d44Defrost temperature set high5.0°C
d10Defrost stop pressure set-point26.0 barg
d13Defrost start verification time180 s
d14Minimum defrost time30 s
d15Maximum defrost time7 min
d16Minimum time between two defrosts on the same refrigerant circuit25 min
d20Dripping / post-defrost waiting time30 s
d23Compressor power for circuit in defrost100%
d30Simultaneous defrosting mode2 – Ed
d31Fan speed while dripping (with relevant fan-control option)50%

d30 simultaneous-defrost modes

  • 0 – NO: one refrigerant system defrosts at a time.
  • 1 – ES: both circuits defrost simultaneously; defrost ends when the output condition is reached on a single circuit.
  • 2 – ED: both circuits defrost simultaneously; defrost ends when the output condition is reached on both circuits.

The source identifies d32, d33 and d34 as not used in this application.

Reversing-valve timing

CodeFunctionValue shown
rE1Changeover delay10 s
rEdChangeover delay in defrost10 s

7. Service quick-check sequence

StepCheckWhat to confirm
1Unit identificationConfirm exact model/configuration, serial data, power supply, refrigerant and fitted options from the unit label.
2Hydronic circuitFlow available, filter clean, isolation valves open, water pressure stable and system water volume adequate.
3Freeze protectionConfirm glycol concentration where required and verify AIS against the fluid freezing point and selection data.
4Power supplyL1/L2/L3 within the specified tolerance, correct phase sequence, secure connections and correct heater operation.
5Oil-heating timerConfirm the 180-minute oil-heating delay has completed after initial power-up or an outage longer than 60 minutes.
6Controller statusReview Active Alarms and Alarm History, then check compressor status. A CT code means the compressor is waiting on the associated timer.
7Live valuesReview Refrigerant, Water, Input/Output, Expansion Valve and Defrost Status screens before changing parameters.
8BMS commandIf remotely controlled, confirm On/Off input, emergency circuit, remote set-point source and BMS communications are not preventing operation.
Parameter caution: Values shown above are the values displayed in the service-training material. They are a technical reference, not a direction to overwrite the configuration of every unit. Unit-specific selections, options, software revisions and factory configuration take precedence.

GENERAL AIRSTAGE Technical Reference | MultiPower Chiller & Heat Pump