GENERAL Assist Technical Reference

AAC Chiller Spare Parts Reference

AAC/IK/A, AAC/IK/A/MC and AAC/IK/A/WP - Sizes 19, 110, 113 and 115
Parts identification, model conversion and component applicability | Source issued April 2026
Use this article to identify common service and replacement parts for GENERAL Airstage Applied AAC chillers. Quantities shown in the model columns indicate the quantity used on that model. A dash means the listed part is not shown as applicable to that model in the source parts list.
Important: Confirm the complete unit model, serial number, build date and installed component before ordering. Some components vary by unit size, configuration and production date. Microchannel condenser coils are not assigned a fixed part number in the source and require confirmation through Spare Parts.

1. Model code conversion

GI model references use the CHA prefix. In GENERAL Airstage Applied format, CHA is read as AAC. The size reference also changes as shown below.

GI ReferenceGENERAL Reference
CHA ... 91AAC ... 19
CHA ... 101AAC ... 110
CHA ... 131AAC ... 113
CHA ... 151AAC ... 115
Model FamilyDescription
AAC/IK/ACooling only
AAC/IK/A/MCCooling only with microchannel condensing coil
AAC/IK/A/WPReversible heat pump
How to read the tables: The number under 19 / 110 / 113 / 115 is the quantity fitted to that model. Stock Criticality is reproduced from the source as A, B or C and is not reinterpreted in this article.

2. Compressor section

Compressors - units from 2024

DescriptionCodeCriticality19110113115
Compressor VZH 065 CGANB327658A11--
Compressor VZH 088 CGAMA331348A--11
Compressor Inverter CDS303P11KT4E20H2327660A11--
Compressor Inverter CDS303P15KT4E20H2671004A--11

Compressor service parts

DescriptionCodeCriticalityVZH 052VZH 065VZH 088
Inverter Solenoide Coil 230V322766B--1
Compressor Heater 70W 240V334608B11-
Compressor Heater 80W 240V324790B--1
Oil PVE 320HV 1LT671052B11-
Oil POE 160SZ 2.5LT333007B--1
Compressor Sound Insulation332741C11-
Compressor Sound Insulation332894C--1

3. Refrigerant circuit

DescriptionCodeCriticality19110113115
Electronic Expansion Valve ETS 6-32355200A1---
Electronic Expansion Valve ETS 6-40673000A-111
Coil for Electronic Expansion Valve ETS 6 COIL355803A1111
High Pressure Switch ACB-2UB851MW315457A1 each model
High Pressure Switch Fitting 8380/X01300918B1 each model
Filter Drier ODF 16 DF316/5S673110B1 each model
Sight Glass D.16 3940/5326750B1 each model
Liquid Receiver 7 Lt - heat pump only326667B1 each WP model
4-Way Reversing Valve SHF-35B-67-04 - heat pump only328127B11--
4-Way Reversing Valve SHF-50B-911D2-P - heat pump only332511B--11
4-Way Reversing Valve Coil SQ-A25 22G-00 0870 - heat pump only328037A1 each WP model
Non-Return Valve & Tubes Assy 3132/5 - heat pump only701173B1 each WP model
Liquid Separator D.35 8LT310201B1 each model
Discharge Temperature Sensor SNESAE41502L7-50+150C326721A1 each model
High Pressure Safety Valve 45 Bar355816A1 each model
High Pressure Transducer 0-45Bar / 4-20mA327217A1 each model
High / Low Pressure Transducer Connector + Cable 5MT312622B1 each application
Suction Temperature Sensor Clamp-on SN8DEB23002C0326703A1 each model
Low Pressure Safety Valve 29 Bar354241A1 each model
Low Pressure Transducer 0-30Bar / 4-20mA328005A1 each model
Pressure transducer replacement: Earlier units may use Wika or other transducers. When replacing with the Huba type, also order connector/cable 312622. The source identifies V+ as Blue on both Wika and Huba; signal B changes from Brown on Wika to White on Huba. Verify the installed wiring before modification.

4. Fan section

DescriptionCode19110113115
Fan Motor Only Ø630 A6E630AN01013341561222
Fan Grille3341571222

5. Water section

DescriptionCodeCriticality19110113115
Pump MXH 402E327104B11--
Pump MXH 403/A356116B--11
Water Pump Cable GIK3 4X1mmq L:3500 mm327646B1 each model
Expansion Vessel 5LT 3/4"354827B1 each model
Safety Valve 1/2"M 6 BAR353294B1 each model
Breather Valve 238C 1/4"327003B1 each model
Exhaust Valve 1/2"305977B1 each model
Pump Connection Gasket DN32 - 2"315657B2 each model
Pump Sound Insulation Shell for 327104334380C1 each model

6. Evaporator section

DescriptionCodeCriticality19110113115
Plate Heat Exchanger C62L-34-EZB 1-1/4VI327099B1---
Plate Heat Exchanger C62L-38-EZB 1-1/4VI327100B-1--
Plate Heat Exchanger C62L-44-EZB 1-1/4VI327101B--1-
Plate Heat Exchanger C62L-52-EZB 1-1/4VI327102B---1
Evaporator Insulation C62L-34 / 38 / 44 / 52140084 / 140085 / 140086 / 140087C140084140085140086140087
Water Pressure Differential Switch 50mBar 1/4"325265A1 each model
Water Pressure Differential Switch Connector327123B1 each model
Heater PHE 390X70 35W (230-50/60-1)311473B1 each model
Inlet / Outlet Water Temperature Sensor NTC 10K 3M352652AA1 inlet + 1 outlet each model

7. Condenser coil section

DescriptionCode19110113115
Condenser Coil 0722 1240X950 37T 4R PA2,13358411---
Condenser Coil 0722 1240X950 38T 3R PA2,1326530-222
Condenser Coil - MicrochannelContact Spare PartsConfirm by complete unit details

8. Control panel and electrical parts

The following components are shown as common electrical/control parts across the AAC 19, 110, 113 and 115 range unless otherwise stated.

DescriptionCodeRefCriticalityQty / Notes
Main Control Board with Display SBA646/C (SB641235A1401)355905A1A1 each model
Cable for Main Control Board COLV000042100320801A1B1 each model
Cable for Main Control Board COLV0000E0100320800A1B1 each model
Cable for Main Control Board COLV000133200325808A1B1 each model
Remote Control Panel SKW2202000001 - optional320803AA2/CRB1 each model
Serial Card Bus Adapter 150 BA10000R3700 - optional314295A3/ISB1 each model
Fan Speed Regulator CFS06/I 4-20mA327284A4B1 each model
Expansion Valve Driver XVD420HLAN000334091A5A1 each model
Transformer Fuse CH10 2A aM 500V359125F1A1 each model
Power Contactor Fuse CH22 63A GG 690V327186-A3 each model
Three Phase Relay Safety Fuse CH10 1A GG 500V315851-A3 each model
Pump Fuse CH10 4A AM 500V313198-A1 each model
Fuse Fan Speed Controller CH10 6A AM 500V313190-A1 each model
Sensor Return Water High Temperature NTC 6m R25=10K +1%311507A-A1 each model
Relay REL-MR-12DC/21-21333651VariousA1 per listed position
Relay Base RIF-1-BPT/2X21333646VariousBUsed with multiple relays
Relay REL-MR-230AC/21-21335930KA5 / KC1 / otherA1 per listed position
Relay REL-MR-24AC/21-21333652KA4 / KHEA1 per listed position
Relay 12 V/DC 2 Contacts311339KEXA1 each model
Three Phase Relay DPA51CM44313577KFA1 each model
Relay 2REL-MR-24DC/21-21335929KHPA1 each model
Compressor Inverter Resistor307983-A1 on 19 / 110 / 113; not shown for 115
Main Switch SIRCO 63 A320534-B1 each model
Main Switch Additional Pole 63 M2331282SG1C1 each model
Main Switch Handle S00316614SG1C1 each model
Main Switch Shaft 150 mm334604SG1C1 each model
Domestic Hot Water Sensor NTC 3m R25=10K +1% (B3435)352652ASTDHW1A1 each model - fitted externally
Ambient Temperature Sensor NTC 3m R25=10K +1% (B3435)352652ASTEA1 each model
Controller Return Water High Temperature DR4020 1xNTC 2xDO328843TE1A1 on 19 / 110 / 113; not shown for 115
Transformer 350VA 230/230-24V-50/60-1328206TT1B1 each model
Transformer Safety Fuse T 1.25 A 5x20327331TT1/F2A1 each model
Transformer Safety Fuse T 2 A 5x20327332TT1/F3A1 each model
Transformer Safety Fuse T 2.5 A 6.3x32334453TT1/F4A1 each model

Contactor / overload options shown in source

The source lists multiple manufacturer alternatives. Confirm the fitted component before ordering:

  • 313977 - Contactor DILM9-01 (EATON)
  • 324386 - Contactor LC1D09P7 (SCHNEIDER)
  • 332768 - Contactor AX09-30-01-80 (ABB)
  • 314009 - Overload Protection ZB12-2.4 (1.6-2.4A) (EATON)
  • 324396 - Overload Protection TESYS LRD TOR 1.6-2.5A (SCHNEIDER)
  • 332819 - Overload Protection TA25DU-1.8M (1.3-1.8A) (ABB)

9. Parts ordering checklist

Before submitting a spare-parts request, capture:
  • Complete model number from the rating plate
  • Serial number
  • Cooling-only, microchannel or reversible heat-pump configuration
  • Production/build date where available
  • Existing component manufacturer and component identification
  • Required quantity
  • Photographs of the rating plate and existing component where identification is uncertain
Do not order solely from a shortened model description. For production-dependent items, alternative contactors/overloads, pressure transducer changes or microchannel coils, confirm the installed component and unit details first.
Technical reference based on AAC chiller parts information issued April 2026. Where the installed equipment differs from this reference, escalate to GENERAL Spare Parts / Technical Support for confirmation before ordering.