Zoneconnex - Quick Start Guide

Installation, commissioning, zone setup, Droplets and troubleshooting
For Zoneconnex zone control systems using the TouchPoint LCD and anywAiR Zone app
Zoneconnex is a Wi-Fi zone control solution that connects directly to the compatible indoor unit PCB through the UART port. It can control up to 10 x 24VAC RJ12 zone motors and supports optional wireless DROPLET temperature and humidity sensors.
Important: Commissioning can be completed without the home's Wi-Fi network operating. The Zoneconnex TouchPoint LCD can emit its own Wi-Fi access point for installer setup.

1. Key features

  • Cost-effective Wi-Fi zone control with standalone commissioning.
  • Direct connection to the indoor unit PCB UART port.
  • Controls up to 10 x 24VAC RJ12 zone motors.
  • Optional wireless DROPLET sensors for room temperature and humidity.
  • Maximum of 10 DROPLET sensors per unit.
  • Automatic averaging where more than one DROPLET is assigned to a zone.
DROPLET sensor model: TS-ZC1

2. Package contents - UTY-ZCAW1

ItemDetails
Zoneconnex ControllerInstalled in ceiling
LoRa AntennaSupplied
TouchPoint LCDWall-mounted user interface
24VAC Power SupplySupplied and prewired
LCD Cable15 m, 4-core, 24 AWG power/communication cable
UART Cable2 m PAP-04V-S communication cable
Fixings8 x M3 x 25 mm pan head self-tapping screws

3. Before you start

To configure a Zoneconnex zone controller, confirm the following:

  • The Zoneconnex controller is installed and connected to a compatible air conditioner.
  • The air conditioner and Zoneconnex controller can both be powered.
  • The anywAiR Zone app is installed on a compatible Apple or Android smartphone or tablet.
Home Wi-Fi is not required for initial commissioning. The system can be commissioned first and connected to the home Wi-Fi network later.

4. Electrical and communication connections

Incoming power

TerminalConnection
124VAC Live or 24V DC +
224VAC Neutral or 24V DC -

Note: The supplied transformer is prewired.

UART connection to indoor unit

Zoneconnex TerminalCable
3Black
4White
5Yellow
6Not used - do not terminate the red cable
Connect to the indoor unit CN65 or CN75 terminal, depending on the indoor unit model. Do not terminate the red UART cable.

TouchPoint LCD connection

TouchPoint LCDControl BoxCable Colour
110Green
211White
312Red
413Black

These connections are prewired from the factory. The terminals are push-button terminal blocks; use a small flat-blade screwdriver to release and install the cable.

RS485 connection

Do not use for standard residential applications. The RS485 port is intended for commercial applications and is unlikely to be required in residential installations at this stage.

5. Connect Zoneconnex to Wi-Fi

  1. On the TouchPoint LCD, press the WiFi tab.
  2. Press Scan WiFi.
  3. Select the required network and press Connect.
  4. Enter the network password using the on-screen keyboard.
  5. Press Connect.

Once connected, the TouchPoint LCD displays network information including:

  • QR code
  • Signal strength
  • Connection speed
  • Security type
  • Channel

6. Enter Installer Mode

At the TouchPoint LCD

  1. Press the System Info tab.
  2. Tap anywhere in the system area of the screen 8 times.
  3. Enter the dealer password: 898989.
  4. Confirm to enter Installer Mode.
Dealer password: 898989. The training guide identifies this as the factory password across all Zoneconnex systems.

Connect the phone to Installer Mode

  1. Once the TouchPoint LCD Installer Mode page is displayed, the LCD emits a Wi-Fi signal.
  2. Open the anywAiR Zone app.
  3. Select Continue as Installer.
  4. Confirm the caution prompt by selecting Continue.
  5. Scan the Connect WiFi QR code displayed on the TouchPoint LCD. The smartphone connects to the LCD Wi-Fi.
  6. Scan the API Access QR code to access the installer backend.
  7. Begin system configuration on the smartphone.

7. Initial zone setup

When Installer Mode is opened for the first time, enter:

  • Number of zones: 1 to 10
  • Number of relief zones: 0 to 3
Although 0 relief zones can be selected, the training guide recommends explaining the benefit of a relief zone to the homeowner/end user as a safety option in case all zones are accidentally turned off.

Zone configuration options

For each zone, the installer can:

  • Name the zone.
  • Set it as a Primary Zone where a DROPLET is present.
  • Set it as a Relief Zone.
  • Adjust minimum airflow.
  • Adjust maximum airflow.
  • Adjust the zone open-to-close time.
  • Assign a DROPLET sensor, if fitted.
Automatic damper assignment: Zone 1 is assigned to Damper 1, Zone 2 to Damper 2, and so on up to the number of zones selected.

Multiple dampers can be connected to the same zone. The training guide notes this can be useful in larger homes where rooms may be at opposite ends of the house.

Summary Zone page

Once the zones have been configured, the Summary Zone page allows the installer to:

  • Review commissioned zones.
  • Select a zone to edit its settings.
  • Add a missed zone using + Add.
  • Add and assign DROPLET sensors.

8. DROPLET sensors

DROPLET sensors are optional and are not supplied as standard with the Zoneconnex system.

  • Add a DROPLET by scanning its QR code or entering/scanning its UUID (8-character alphanumeric code).
  • A DROPLET can remain unassigned and operate as a standalone temperature sensor.
  • A DROPLET can be assigned to a zone.
  • DROPLETs measure temperature and humidity.
  • DROPLETs are not used for VAV control; they are temperature/humidity sensing points.
  • A DROPLET can be set as the Primary sensing point instead of the return-air sensor.
  • No indoor-unit Function Setting changes are required when using a DROPLET as the Primary sensing point.

9. Installer preferences

The Preferences page provides the following settings:

SettingFunction
TimezoneAutomatically selected when connected to Wi-Fi, or can be edited manually if not connected.
Show Current TemperatureDisplays the indoor unit return-air temperature on the TouchPoint LCD and smartphone app.
Global Damper Stroke TimeDefault is 15 seconds open-to-close across all dampers. Adjustment is not recommended unless actual damper travel time has been measured.
Firmware UpdateOver-the-air update on current firmware. Intended for technician use.
Soft ResetClears unit credentials, including previous owners, members and guests. Zone and DROPLET configuration remains saved.
Factory ResetFull reset. All device settings are cleared back to factory condition.

10. Firmware updates

If an update is available while in Installer Mode, the installer may be prompted to update the ACBM and TouchPoint LCD.

During a firmware update: Do not disconnect power, turn the unit off, move away from the TouchPoint LCD with the smartphone, or allow the smartphone to disconnect from the TouchPoint LCD.

Follow the on-screen prompts and wait for the completion notification.

11. Finish installation

  1. Complete zone configuration, DROPLET setup and preferences.
  2. Return to the Installer Mode home page.
  3. Select Finish Installation.
  4. When prompted, select Accept.

The settings are then saved to the ACBM module and TouchPoint LCD. The TouchPoint LCD returns to the normal home page and the smartphone app exits Installer Mode and returns to the login page.

12. Temperature sensing configuration

Default setting: When installing the anywAiR Zoneconnex TouchPoint LCD only, the air conditioner's factory temperature sensing must remain set to the return-air sensor.
  • If the supplied UTY-RNRY* wall controller is also installed, it may be configured through the function settings menu as the sensing point.
  • The UTY-RNRY* controller operates alongside the Zoneconnex TouchPoint LCD.
  • Changes made on either controller are mirrored on the other controller, except for zone control on the UTY controller.
  • If a DROPLET is present and configured as Primary, the ACBM logic overrides the UTY-RNRY* as the sensing point.

13. Errors and faults

  • The TouchPoint LCD displays air-conditioner error codes in GENERAL's native 2-digit and 3-digit format.
  • If the system is disconnected from the cloud, a power cycle of the Zoneconnex and local Wi-Fi router may restore connection.
  • A communication issue between the ACBM and indoor unit will generate an error.
  • Where an ACBM-to-indoor-unit communication fault is present, control from the TouchPoint LCD home page and smartphone app is not permitted.

14. Commissioning checklist

CheckItem
Zoneconnex controller and indoor unit can both be powered.
UART cable is connected to the correct CN65/CN75 terminal and red cable is not terminated.
TouchPoint LCD communication cable is connected.
anywAiR Zone app is installed on the installer device.
Correct number of zones and relief zones has been entered.
Zone names, airflow limits and damper stroke times have been checked.
DROPLETs have been added and assigned where fitted.
Temperature sensing configuration is correct.
Wi-Fi is connected where available.
Available firmware updates have been completed without interruption.
Finish Installation has been selected and settings saved.

15. Zone installation notes

ZoneRoomSensorZoneRoomSensor
1  6  
2  7  
3  8  
4  9  
5  10  
Source: Zoneconnex - Quick Start Guide - Tech Assist Training, September 2026.