General Assist Technical Reference

BACnet Gateway UTY-VBGX

System requirement for VRF systems with four outdoor units
Service Bulletin VRF-0185  |  Issued 24 August 2026
Important limitation: The UTY-VBGX hardware BACnet Gateway cannot register the fourth outdoor unit (Subordinate 3) when a refrigerant circuit contains four outdoor units. In this configuration, connection to a Building Management System (BMS) is not possible.

1. Quick answer

Affected BACnet GatewayUTY-VBGX (Hardware)
Affected configurationOne refrigerant circuit containing four outdoor units
What happensThe fourth outdoor unit, Subordinate 3, cannot be registered in the refrigerant circuit.
BMS connectionNot possible for the affected four-outdoor-unit refrigerant circuit using UTY-VBGX.
AlternativeConsider UTY-ABGXZ1 (Software) BACnet Gateway.

2. Affected systems

This limitation applies when the UTY-VBGX hardware BACnet Gateway is being used with a VRF refrigerant circuit that has four outdoor units.

Series identified in the bulletin as supporting a four-outdoor-unit configuration:
  • VC-V Series
  • V-V Series
Outdoor unit positionRegistration with UTY-VBGX
PrimaryRegistered
Subordinate 1Registered
Subordinate 2Registered
Subordinate 3 (4th outdoor unit)Cannot be registered
Because the fourth outdoor unit cannot be registered, the affected refrigerant circuit cannot be connected to the BMS through the UTY-VBGX hardware gateway.

3. Workaround

If a VRF refrigerant circuit with four outdoor units must be connected to BACnet, consider using the UTY-ABGXZ1 software BACnet Gateway as the alternative model.

The service bulletin does not provide a hardware modification, setting change or commissioning procedure that will make the fourth outdoor unit register with the UTY-VBGX.

4. Check before specifying or commissioning

1Confirm the BACnet Gateway model being used.
2Confirm how many outdoor units are connected within each refrigerant circuit.
3If the circuit has four outdoor units and UTY-VBGX is proposed, do not proceed on the assumption that the fourth outdoor unit can be registered.
4Where BACnet/BMS connection is required for that circuit, consider UTY-ABGXZ1 (Software) instead.

5. Future update

GENERAL is investigating the issue. If a solution is confirmed for the affected UTY-VBGX hardware BACnet Gateway, an updated response plan, including any permanent solution, will be provided.

Source: Service Bulletin VRF-0185 — System Requirements for Using BACnet Gateway, issued 24 August 2026.