General Assist Technical Reference

Missing Wired Remote Controller Cable

Replacement connecting cable - Part No. 9708582016
For selected AIRSTAGE high wall indoor units using a 3-wire wired remote controller connection
Quick answer: If the wired remote controller connecting lead is missing, the replacement part required is 9708582016. This is the short adaptor/connecting cable that plugs into the indoor unit control board and provides the connection point for the wired remote controller cable.
Installation note: Electrical work and control wiring must be completed by appropriately qualified personnel. Isolate power to the indoor unit before accessing the control PCB or connecting the remote controller wiring.

1. Part required

ItemDetails
Part number9708582016
DescriptionWired remote controller connecting cable / adaptor lead
PurposeConnects the field wired remote controller cable to the indoor unit control board connector
Controller wiring3-wire type - Red, White and Black

2. Applicable indoor unit models

The supplied parts reference identifies the connecting cable for the following models:

ASYA18GACHASYA18LACHASYA24GACH
ASYA24LACHASYA30GACHASYA30LACH
If the indoor unit model is not listed above, confirm the correct accessory/parts listing before ordering. Do not assume this lead is common to all indoor units.

3. How the cable is connected

The connecting cable plugs into the designated connector on the indoor unit control board. The wired remote controller cable is then joined to the accessory lead.

Remote controller cableConnecting cable 9708582016
RedRed
WhiteWhite
BlackBlack
  1. Isolate power to the indoor unit.
  2. Access the indoor unit control PCB.
  3. Locate the wired remote controller connector on the control unit.
  4. Plug the connector end of part 9708582016 into the control board.
  5. Join the remote controller cable to the accessory lead colour-for-colour: Red to Red, White to White and Black to Black.
  6. Solder and insulate the connected parts as shown in the installation instruction.
  7. Route and secure the wiring so it cannot contact sharp edges or moving components.
  8. Set the indoor unit DIP switch SW1 as required by the applicable wired remote controller installation instructions.
  9. Reassemble the unit, restore power and test remote controller operation.
Important: Do not mix the Red, White and Black conductors. The supplied wiring diagram shows the conductors connected colour-for-colour and the joints soldered and insulated.

4. Dual control or group control

For dual-control or group-control arrangements, the remote controller wiring is branched/spliced into the accessory connecting cable as shown in the installation diagram. All joints must be secure and insulated.

Because the exact controller addressing and DIP switch configuration can vary with the system arrangement, follow the applicable indoor unit and wired remote controller installation instructions for the final SW1 and controller settings.

5. What to do if the cable is missing

Order/request replacement part:
9708582016
Wired remote controller connecting cable / adaptor lead

When requesting the replacement, provide the indoor unit model and serial number so the part application can be checked before dispatch.

6. Common question

Can the wired remote controller be connected directly without this lead?

For the models listed in this article, the supplied documentation shows the accessory connecting cable between the remote controller field wiring and the control unit connector. If this lead is missing, replace it with the correct part rather than modifying the control board connection.

This article is based on the supplied installation diagrams and parts reference for the wired remote controller connecting cable. Always confirm the applicable installation manual and control settings for the exact indoor unit and remote controller being installed.