General Assist Technical Reference

anywAiR iO to RTPU

Installation, wiring, SMT-770 configuration and communication checks
For General / AIRSTAGE rooftop package-unit applications using Rubix Compute and Smart Temp SMT-770
The anywAiR iO solution interfaces the RTPU Danfoss controller with the Smart Temp SMT-770 through the Rubix Compute gateway. The system uses separate power supplies and RS485/Modbus communication paths that must be wired and configured correctly.
Qualified personnel only: This installation includes 240 V AC, 24 V AC, 24 V DC and RS485 wiring. Isolate all supplies before installation and confirm polarity before energising equipment.

1. System overview

ComponentPowerCommunication
Danfoss RTPU controllerExisting RTPU supplyRS485 to Rubix Compute
Rubix Compute anywAiR iO24 V DC485-1 to RTPU; Ethernet to optional modem/router
Smart Temp SMT-77024 V ACRS485 to RTPU X5 D1+ / D1-
24 V DC power supply240 V AC inputSupplies Rubix and optional modem

2. RTPU terminal X5 wiring

TerminalFunctionConnection
24V24 V AC activeSMT-770 Power 24
224 V AC neutral/commonSMT-770 Power 24C
D1+RS485 / Modbus positiveSMT-770 COMS A
D1-RS485 / Modbus negativeSMT-770 COMS B
0V / 240V240 V AC supply24 V DC power-supply input
Confirm all RTPU X5 terminal labels against the actual unit wiring diagram before connection. Do not assume terminal position from wire colour alone.

3. Rubix Compute wiring

Rubix terminalConnection
Power +24 V DC positive
Power -24 V DC negative
485-1 terminal 1RS485 positive (+)
485-1 terminal 2RS485 negative (-)
485-1 terminal 3Ground / reference
485-2Do not use
ETH-1Use for optional modem/router connection
 
The 24 V DC power supply feeds both the Rubix Compute and the optional modem. The power supply receives 240 V AC at L and N and provides 24 V DC from the +V and -V output terminals.

Rubix status check

  • Confirm the local slide switch is in the right-hand position.
  • Confirm both indicated status LEDs are illuminated.
  • Confirm 24 V DC polarity before connecting the Rubix.
  • Confirm RS485 polarity and grounding.

4. SMT-770 wiring and configuration

SMT-770 terminalConnection
COMS ARS485 positive / RTPU D1+
COMS BRS485 negative / RTPU D1-
Power 2424 V AC active
Power 24C24 V AC common / neutral

SMT-770 DIP switches

SwitchRequired positionPurpose
1OFFFactory position
2ONFactory position
3ONFactory position
4ONFactory position
5ONFactory position
6ONProgrammable controller / 7-day timer enabled
7OFFFactory position
8OFFFactory position
 
Switches 1, 2, 3, 4, 5, 7 and 8 must remain in the specified factory positions. Altering them can change the thermostat operating profile and may disrupt Modbus mapping.

Entering the installer menu

1Press and hold O/RIDE for 15 seconds.
2The display shows 88:15. Use the arrow buttons to change it to 88:21.
3Press O/RIDE to enter the installer menu.
4Use O/RIDE to move forward and PROG to move backwards through menu items.
5Use the up and down arrows to change values.
6Press MODE or FAN, or wait 60 seconds, to exit.
 

Required Modbus settings

MenuSettingValue
AdModbus address7
bdModbus baud rate19.2 / 19200
PAParity0 / None

Common SMT-770 functions

FunctionPurpose
LCKeyboard lock level
HLMaximum heating setpoint
CLMinimum cooling setpoint
CFCelsius / Fahrenheit display
C1Internal sensor calibration
tC12-hour or 24-hour clock
tdRoom and set-temperature display selection
AHAfter-hours override duration

5. SMT-770 seven-day timer

DIP switch 6 must be ON for the programmable seven-day timer.
1Hold PROG for approximately 3 seconds.
2Set the required unit start time.
3Set the required stop time.
4Copy the programmed times to the required days of the week.
 
When the timer is active, START or STOP appears in the top-left of the display. The O/RIDE button can temporarily operate the system outside scheduled hours. The illustrated configuration uses a 120-minute override.

6. Communication troubleshooting

The satellite/communication symbol on the SMT-770 display indicates communication status. If it is missing or crossed out, complete the following checks.
1Confirm 24 V AC supply at SMT-770 Power 24 and 24C.
2Confirm RS485 polarity from COMS A/B to D1+/D1-.
3Confirm SMT-770 DIP switches match the required positions.
4Confirm Rubix has 24 V DC power and both status LEDs are illuminated.
5Confirm Danfoss parity, Modbus address and baud rate.
6Confirm SMT-770 Ad = 7, bd = 19.2 and PA = 0.

7. Important operating notes

  • Fan speed cannot be changed directly from the SMT-770.
  • Default temperature sensing is from the RTPU return-air sensor.
  • Changing sensing to the wall controller requires Rubix programming and should be specified before shipment.
  • The configured setpoint range is generally 18°C to 30°C.
  • Modbus points can be adjusted remotely when a router is connected and authorised access is available.
  • Rubix V2.0 units are configured for 19200 baud and are labelled V2.0 on the enclosure and packaging.
  • Always use the latest installation instructions and confirm the Rubix software version before changing baud settings.

8. Commissioning checklist

CheckDone
240 V AC isolated and verified before wiring
24 V DC polarity confirmed at Rubix
24 V AC measured at SMT-770
RS485 polarity confirmed at all devices
Rubix connected through 485-1 only
SMT-770 DIP switches verified
Modbus address, baud and parity verified
Satellite/communication icon present
Start, stop, mode and setpoint commands tested
Timer and override tested where enabled
This article is based on the supplied General Australia and New Zealand installation diagrams. Confirm the applicable RTPU wiring diagram, Danfoss configuration, Rubix software version and current installation instructions before completing or modifying the installation.