Function 33 – Heating Thermostat-Off Indoor Fan Control

ARTG30LHTA / ARTG36LHTA / ARTG45LHTA / ARTG54LHTA
Correction of intermittent indoor-fan operation time during heating thermostat-off
Function setting 33 changes how the indoor fan behaves in heating mode after the room has reached set temperature and the heating thermostat switches off.
Heating only: This setting manages air circulation and cool-draft complaints while heating demand is satisfied. It does not change normal fan operation while the system is actively heating.

1. Function 33 setting summary

SettingIndoor-fan behaviour at heating thermostat-offStopping-time cycle
33-00Standard progressive intermittent operation. The fan periodically circulates air and the stop interval increases while heating demand remains satisfied.6 min → 10 min → 17 min
33-01Fixed intermittent operation. The fan continues using the same stop interval rather than progressing to longer intervals.6 min → no change
33-02Shorter intermittent cycle. The fan circulates more frequently.4 min → 6 min → 10 min
33-03Longer intermittent cycle. The fan remains stopped for longer periods between circulation cycles.8 min → 15 min → 27 min
33-04Fan stop. The indoor fan stops completely when the heating thermostat is off.No intermittent circulation
33-05Continuous / non-stop operation. The indoor fan continues its thermostat-off fan behaviour.Factory setting for ARTG LHTA
Important: Generic function tables may label 00–03 as standard, short and long. For ARTG LHTA, use the detailed stopping-time sequences above.

2. What do the three times mean?

The values are the programmed fan stopping intervals used as the heating thermostat remains satisfied. They are not fan speeds and they are not three settings selected independently.
1Heating demand is satisfied. The system enters heating thermostat-off control.
2The fan stops for the first programmed interval. For 33-00, this is approximately six minutes.
3The fan briefly circulates air. This samples room conditions and distributes residual heat.
4If demand remains satisfied, the next interval is applied. Depending on the setting, it remains fixed or progresses through the second and third stages.
The indoor control automatically decides when to move between the programmed intervals. The technician selects only the Function 33 setting.

Example – 33-00

Thermostat OFF → stop about 6 min → brief circulation → stop about 10 min → brief circulation → stop about 17 min

3. Which setting should be used?

RequirementPossible settingConsideration
No complaint; normal distribution required33-05Retain factory setting unless there is a specific comfort issue.
Cool draft after setpoint is reached33-04Stops the fan completely; room sensing and temperature distribution may be affected.
Reduced fan operation without full stop33-00 or 33-0333-03 gives the longest off periods.
More frequent room-air sampling33-02Uses the shortest stop intervals.
Consistent intermittent cycle33-01Maintains an approximately six-minute stop interval.
Do not use Function 33 to mask another fault. Check room-sensor accuracy, sensor selection, airflow, zoning and short cycling before changing the setting.

4. Adjustment process

1Stop the air conditioner.
2Enter the installer/function-setting menu using the procedure for the fitted controller.
3Select Function Number 33.
4Select the required value from 00 to 05 and confirm.
5Record the original and revised settings.
6Isolate power for at least five minutes, then restore power.
7Run in heating, allow the unit to reach setpoint and confirm the thermostat-off fan behaviour.
This article is a practical reference for the ARTG LHTA ducted range. Function availability and factory settings may differ on other indoor-unit families. Always record the original setting and confirm the applicable model documentation before adjustment.