GENERAL AIRSTAGE TECHNICAL REFERENCE
Dunham Bush Centrifugal Chiller
Modbus / BACnet High-Level Interface Mapping
Searchable reference for BMS integration, commissioning and fault interpretation. Addresses and scale factors are reproduced from mapping document version 2024-09-15.
Point MappingFactory SetupStatus TablesAlarm Index
Register Notes and Conventions
Type codes: D = Digital, A = Analogue, I = Integer.
R/W: R = Read only; R/W = Read and write.
* Design dependent - refer to the unit wiring diagram.
** Optional add-on - refer to the unit wiring diagram.
*** BACnet extended setup is required.
Alarm severity: superscript 1 = critical alarm; superscript 2 = warning alarm.
Modbus / BACnet Point Mapping
Modbus AddressBACnet Address***TYPER/WUnitScaleDESCRIPTION
DIGITAL READING-UNITS
10002100001DR--Remote Start/Stop Status
10003100002DR--Local Start/Stop Status
10004100003DR--Chilled Water Flow Status
10005100004DR--Condenser Water Flow Status
10007100006DR--Remote Start High Level Status*
10008100007DR--Local Start High Level Status*
10009100008DR--Off High Level Status*
10092100091DR--Critical Alarm ON
10093100092DR--Chilled Water Pump ON
10094100093DR--Condenser Water Pump ON
10095100094DR--Cooling Tower ON
10131100130DR--Unit Critical Alarm
10181100180DR--DBLAN Present (Option - Applicable to Master/Slave Only)
10182100181DR--DBLAN Unit 1 Present (Option - Applicable to Master/Slave Only)
10183100182DR--DBLAN Unit 2 Present (Option - Applicable to Master/Slave Only)
10184100183DR--DBLAN Unit 3 Present (Option - Applicable to Master/Slave Only)
10185100184DR--DBLAN Unit 4 Present (Option - Applicable to Master/Slave Only)
10186100185DR--DBLAN Unit 5 Present (Option - Applicable to Master/Slave Only)
10187100186DR--DBLAN Unit 6 Present (Option - Applicable to Master/Slave Only)
10188100187DR--DBLAN Unit 7 Present (Option - Applicable to Master/Slave Only)
10189100188DR--DBLAN Unit 8 Present (Option - Applicable to Master/Slave Only)
10190100189DR--DBLAN Start Next Unit (Option - Applicable to Master/Slave Only)
10194100193DR/W--BMS Remote Start/Stop Command
10195100194DR/W--Reset Alarm
10197100196DR--Unit of Measurement - Temperature (0-Fahrenheit; 1-Centigrade)
10198100197DR--Unit of Measurement - Pressure (0-psi; 1-Bar)
DIGITAL READING-COMPRESSOR 1
10021100020DR--Compressor 1 Run Status
11116101115DR--Compressor 1 Fault
10023100022DR--Compressor 1 Online
10047100046DR--Compressor 1 Interlock
10097100096DR--Compressor 1 Vapor Injection Solenoid ON*
ANALOG READING-UNITS
40002100001ARoC or oFx 0.1Leaving Chilled Water Temperature
40003100002ARoC or oFx 0.1Entering Chilled Water Temperature
40004100003ARoC or oFx 0.1Leaving Condenser Water Temperature
40005100004ARoC or oFx 0.1Entering Condenser Water Temperature
40058100057ARPSI or BARx 0.1System 1 Cooler Pressure
40133100132ARPSI or BARx 0.1System 1 Condenser Pressure
40010100009ARoC or oFx 0.1Leaving Chilled Water Temperature Reset (Optional Add-On - Chilled Water Reset + Demand Limit)
40995100994AR/WoC or oFx 0.1Leaving Chilled Water Temperature Written Setpoint (Optional Add-On - Chilled Water Reset + Demand Limit; Touchscreen Controlable)
40011100010AR%x 0.1Demand Limit (Optional Add-On - Chilled Water Reset + Demand Limit)
40994100993AR/W%x 0.1Demand Limit Written Setpoint (Optional Add-On - Chilled Water Reset + Demand Limit; Touchscreen Controlable)
40019100018ARoC or oFx 0.1Cooler Approach
40021100020ARoC or oFx 0.1Condenser Approach
40093100092AR%x 0.1Liquid Line In Valve Opening %
40107100106AR%x 0.1Liquid Line 2 In Valve Opening % **
40280100279AR%x 0.1Liquid Line Out Valve Opening % **
40362100361AR%x 0.1Liquid Line 2 Out Valve Opening % **
41049101048AR%x 0.1HGBP Valve Opening % **
40076100075ARPSI or BARx 0.1Liquid Line Pressure**
40079100078ARoC or oFx 0.1Liquid Line Temperature**
40085100084ARoC or oFx 0.1Liquid Line Subcool**
40131100130ARoC or oFx 0.1Leaving Chilled Water Control Target
40153100152AR%x 0.1Unit Capacity
40154100153AR%x 0.1Stop Next Capacity (Option - Applicable to Master/Slave Only)
40191100190AR/WoC or oFx 0.1Leaving Chilled Water Temperature Control Setpoint (Cooling Mode Application)
40192100191ARoC or oFx 0.1Leaving Chilled Water Temperature Deadband Positive
40193100192ARoC or oFx 0.1Leaving Chilled Water Temperature Deadband Negative
40194100193ARoC or oFx 0.1Leaving Chilled Water Temperature Deadband Restart
40195100194ARoC or oFx 0.1Leaving Chilled Water Temperature Deadband Stop Unit
ANALOG READING-COMPRESSOR 1
40012100011ARPSI or BARx 0.1Compressor 1 Suction Pressure
40366100365ARoC or oFx 0.1Compressor 1 Suction Temperature
40015100014ARPSI or BARx 0.1Compressor 1 Discharge Pressure
40034100033ARoC or oFx 0.1Compressor 1 Discharge Temperature
40385100384ARkWx 0.1Compressor 1 Actual Power
40032100031ARAmperex 1.0Compressor 1 3-Phase Running Amps
40147100146AR%x 0.1Compressor 1 Capacity
40863100862AR%x 0.1Compressor 1 Stage Valve Opening % *
40516100515AR%x 0.1Compressor 1 Vapor Injection Opening % *
INTEGER READING-UNITS
45005200003IR-x 1.0Number of Unit Running in DBLAN (Option - Applicable to Master/Slave Only)
45954200952IR/W-x 1.0Remote/Off/Local High Level Control* 0 = Off 1 = Remote 2 = Local
45008200006IRsecx 1.0Unit Target Response
45010200008IR-x 1.0System Status (See Table 4 details)
45013200011IRsecx 1.0Next Compressor Turn On Delay
45014200012IRsecx 1.01st Compressor Turn On Delay
45049200047IR-x 1.0DBLAN Unit No. (Option - Applicable to Master/Slave Only)
45052200050IR-x 1.0Lead Compressor
INTEGER READING-SYSTEM 1
45006200004IR-x 1.0System 1 Liquid Line Status (See Table 2 details)(Applicable to DCLCD/DCLCD-V with Economizer Only)
45050200048IRsecx 1.0System 1 Liquid Line Response (Applicable to DCLCD/DCLCD-V with Economizer Only)
INTEGER READING-COMPRESSOR 1
45003200001IR-x 1.0Compressor 1 Status 1 (See Table 1 details)
45011200009IR-x 1.0Compressor 1 Status 2 (See Table 3 details)
45012200010IRsecx 1.0Compressor 1 Off Cycle Delay
45018200016IRhoursx 1.0Compressor 1 Run Hour (Daily)
45019200017IRhoursx1000x 1.0Compressor 1 Run Hour (Totalx1000) (See Note 1)
45020200018IRhoursx 1.0Compressor 1 Run Hour (Total) (See Note 1)
45021200019IR-x 1.0No. of Compressor 1 runnning cycle (Daily)
45022200020IR-x 1.0No. of Compressor 1 runnning cycle (Total)
45023200021IRmonthx 1.0Compressor 1 Last ON Time (month)
45024200022IRdayx 1.0Compressor 1 Last ON Time (day)
45025200023IRhoursx 1.0Compressor 1 Last ON Time (hours)
45026200024IRminutesx 1.0Compressor 1 Last ON Time (minutes)
45027200025IRmonthx 1.0Compressor 1 Last OFF Time (month)
45028200026IRdayx 1.0Compressor 1 Last OFF Time (day)
45029200027IRhoursx 1.0Compressor 1 Last OFF Time (hours)
45030200028IRminutesx 1.0Compressor 1 Last OFF Time (minutes)
Factory Communication Settings
BACnet MS/TP Factory Setup
BACnet TCP/IP / Modbus TCP/IP Factory Setup
Modbus RTU Factory Setup
Data bits / Stop bits / Parity8 / 2 / None
Baud rate / ID address19200 / 1
Device ID range77001 to 77999
Modbus TCP/IP addresses172.16.0.1 to 172.16.0.999
Subnet255.255.0.0
Device ID range77001 to 77999
MS/TP ID range1 to 999 (document also lists 1 to 1000)
Max master / Baud rate127 / 38400
Run-hour calculation: Compressor total running hours = (Total x1000 register x 1000) + Total register.
Integer Status Value Tables
Table 1 - Compressor Operation Status
Integer ValueDescription
0Off
1On-Hold
2On-Unload
3On-Load
4Alarm
5Opening EEV
6Switch off
7Low LVG CHW restart temperature
Table 4 - System Status
Integer ValueDescription
0Off by Config
1On
2Off-R/O/L Input
3Off-No CHW Flow
4Off-No Stop
5Off-On/Off Schedule
6Off-High Level Control
7Off-PCR trip
8Powerup Delay
9Off-DBLan Network Control
10-
11Off-No CDW Flow
12Off-Ref. leak warmup delay
Table 3 - Compressor Status 2
Integer ValueDescription
0Ok
1Hold-Pressure
2Unload-Pressure
3Hold-Amp
4Unload-Amp
5-
6Ramp
Table 2 - Liquid Line Status
Integer ValueDescription
0Off
1Hold-Normal
2Open-Normal
3Close-Normal
4EEV Slove Over
5Open-High Approach
6Close-Low Approach
7Close-High Approach Ext.
8Open-Hold Low Pressure
9Close-Unload Capacity %
10Open-Load Capacity %
11Open - Low pressure unload
12Open - during Off HGBP
Alarm Trigger Registers
Modbus AddressBACnet AddressTYPER/WUnitScaleDESCRIPTION
INTEGER READING-UNITS
45180200178IR-x 1.0Alarm Trigger (See Alarm Table 1 details)
45181200179IR-x 1.0Alarm Trigger (See Alarm Table 2 details)
INTEGER READING-SYSTEM 1
45183200181IR-x 1.0Alarm Trigger (See Alarm Table 3 details)
45951200949IR-x 1.0Alarm Trigger (See Alarm Table 8 details)
INTEGER READING-COMPRESSOR 1
45186200184IR-x 1.0Alarm Trigger (See Alarm Table 4 details)
45083200081IRx 1.0Alarm Trigger (See Alarm Table 5 details)
45078200076IRx 1.0Alarm Trigger (See Alarm Table 6 details)
45077200075IRx 1.0Alarm Trigger (See Alarm Table 7 details)
INTEGER READING-COMPRESSOR 2
45188200186IR-x 1.0Alarm Trigger (See Alarm Table 4 details)
45084200082IRx 1.0Alarm Trigger (See Alarm Table 5 details)
45079200077IRx 1.0Alarm Trigger (See Alarm Table 6 details)
45080200078IRx 1.0Alarm Trigger (See Alarm Table 7 details)
INTEGER READING-COMPRESSOR 3
45190200188IR-x 1.0Alarm Trigger (See Alarm Table 4 details)
45085200083IRx 1.0Alarm Trigger (See Alarm Table 5 details)
45081200079IRx 1.0Alarm Trigger (See Alarm Table 6 details)
45082200080IRx 1.0Alarm Trigger (See Alarm Table 7 details)
INTEGER READING-COMPRESSOR 4
45564200562IR-x 1.0Alarm Trigger (See Alarm Table 4 details)
45566200564IRx 1.0Alarm Trigger (See Alarm Table 5 details)
45565200563IRx 1.0Alarm Trigger (See Alarm Table 6 details)
45879200877IRx 1.0Alarm Trigger (See Alarm Table 7 details)
INTEGER READING-COMPRESSOR 5
46031201029IR-x 1.0Alarm Trigger (See Alarm Table 4 details)
46032201030IRx 1.0Alarm Trigger (See Alarm Table 5 details)
46033201031IRx 1.0Alarm Trigger (See Alarm Table 6 details)
46034201032IRx 1.0Alarm Trigger (See Alarm Table 7 details)
Alarm Bit Index
Alarm Table 1 - Unit Alarm
Refer to Modbus Address 45180 Bacnet Address 200178
Bit No.Alarm Description
0¹Leaving Chilled Water Temperature Sensor Failure
1²Entering Chilled Water Temperature Sensor Failure
2²Leaving Condenser Water Temperature Sensor Failure
3²Entering Condenser Water Temperature Failure
4¹No Chilled Water Flow Alarm
5¹Chilled Water Pump Starter Alarm
6¹No Condenser Water Flow Alarm
7¹Condenser Water Pump Starter Alarm
8¹Power Lossed Alarm
9²A Unit Offline in DBLAN Network Alarm
10¹Leaving Chilled Water Temperature Freeze Alarm
11²Serial Port Alarm
12¹Cooler Differential Pressure Sensor Failure
13¹Condenser Differential Pressure Sensor Failure
14¹No Cooler Differential Pressure Alarm
15¹No Condenser Differential Pressure Alarm
Alarm Table 2 - Unit Alarm
Refer to Modbus Address 45181 Bacnet Address 200179
Bit No.Alarm Description
0¹Unauthorized Main Controller/Software
1¹Unauthorized Expansion Board 1
2¹Unauthorized Expansion Board 2
3¹Refrigerant Leak Sensor Failure
4¹Refrigerant Leak High Alarm
5¹Ambient Temperature Sensor Failure
6¹Free Cool Temperature Sensor Failure
7¹UPS Alarm
8¹Economizer Pressure Sensor Failure
9¹Shunt Trip Alarm
10¹Cooler Pressure Sensor Failure
11¹Condenser Pressure Sensor Failure
12¹Cooler Outlet Pressure Sensor Failure
13¹Cooler Inlet Pressure Sensor Failure
14¹Cond Outlet Pressure Sensor Failure
15¹Cond Inlet Pressure Sensor Failure
Alarm Table 3 - System Alarm
Refer to Modbus Address 45183 Bacnet Address 200181
Bit No.Alarm Description
0¹Refrigerant Level Sensor Failure
1¹Liquid Line Pressure Failure
2¹Liquid Line Temperature Failure
3¹EEV1 Offline (Line In 1)
4¹EEV1 EEPROM Error (Line In 1)
5¹EEV1 Motor Error (Line In 1)
6¹EEV2 Offline (Line In 2)
7¹EEV2 EEPROM Error (Line In 2)
8¹EEV2 Motor Error (Line In 2)
9¹EEV3 Offline (Line Out 1)
10¹EEV3 EEPROM Error (Line Out 1)
11¹EEV3 Motor Error (Line Out 1)
12¹EEV4 Offline (Line Out 2)
13¹EEV4 EEPROM Error (Line Out 2)
14¹EEV4 Motor Error (Line Out 2)
15¹EEV9 Offline (HGBP Valve)
Alarm Table 8 - System Alarm
Refer to Modbus Address 45951 Bacnet Address 200949
Bit No.Alarm Description
0¹EEV9 EEPROM Error (HGBP Valve)
1¹EEV9 Motor Error (HGBP Valve)
2
3
4
5
6
7
8
9
10
11
12
13
14
15N/A
Alarm Table 4 - Compressor Alarm
Refer to Modbus Address Comp 1 = 45186 Bacnet Address Comp 1 = 200184
Bit No.Alarm Description
0¹No Starter Feedback
1¹No Stop Alarm
2¹High Pressure Ratio During Startup
3¹Over Number Lockout per-Day. Please Contact DBI
4²Compressor Service Alarm
5¹High Inverter Temperature Alarm
6¹High Discharge Temperature Alarm
7¹Low Suction Pressure Alarm
8¹High Discharge Pressure Alarm
9¹High 3-Phase Amp Alarm
10¹High Cavity Temperature Alarm
11¹High Pressure Ratio Cutout Alarm
12¹High SCR Temperature Alarm
13¹Compresser Lockout & Power Cycle Required
14¹High Motor Winding Temprature Alarm
15¹High Suction Superheat Alarm
Alarm Table 5 - Compressor Alarm
Refer to Modbus Address Comp 1 = 45083 Bacnet Address Comp 1 = 200081
Bit No.Alarm Description
0¹High Earth Leakage Current Alarm
1¹High Softstart Temperature Alarm
2¹Compressor Calibration
3¹Bearing Self Test
4¹Compressor Axial Distance Alarm
5¹Compressor Axial Load Alarm
6¹Compressor Front x-axis Distance Alarm
7¹Compressor Front y-axis Distance Alarm
8¹Compressor Front x-axis Load Alarm
9¹Compressor Front y-axis Load Alarm
10¹Compressor Rear x-axis Distance Alarm
11¹Compressor Rear y-axis Distance Alarm
12¹Compressor Rear x-axis Load Alarm
13¹Compressor Rear y-axis Load Alarm
14¹Motor Single Phase Overcurrent Alarm
15¹DCBus Overvoltage Alarm
Alarm Table 6 - Compressor Alarm
Refer to Modbus Address Comp 1 = 45078 Bacnet Address Comp 1 = 200076
Bit No.Alarm Description
0¹Motor Overcurrent Alarm
1¹Inverter Error Signal
2¹Rotor Locked & Motor Current Phase Not Aligned
3¹Bearing Fault
4¹Motor Voltage Generates No Current
5¹DCBus Under/Overvoltage
6¹24VDC Under/Overvoltage
7¹Low Motor Back EMF
8¹EEPROM Error
9¹Generator Mode
10¹SCR Phase Loss
11²Compressor Booting Up
12¹Inverter Temperature Sensor Failure
13¹Cavity Temperature Sensor Failure
14¹Suction Temperature Sensor Failure
15¹Discharge Temperature Sensor Failure
Alarm Table 7 - Compressor Alarm
Refer to Modbus Address Comp 1 = 45077 Bacnet Address Comp 1 = 200075
Bit No.Alarm Description
0¹Suction Pressure Sensor Failure
1¹Discharge Pressure Sensor Failure
2¹Invalid Bearing Calibratrion
3¹Inverter Cooling Control Fault
4¹Motor Cooling Control Fault
5¹Softstart Temperature Sensor Failure
6¹EEV VI Offline
7¹EEV VI EEPROM Error
8¹EEV VI Motor Error
9¹Vapor Injection Pressure Sensor Failure
10¹Vapor Injection Temperature Sensor Failure
11-
12-
13-
14-
15-
Use the project wiring diagram and approved controls documentation to confirm design-dependent and optional points before commissioning.