GENERAL AIRSTAGE TECHNICAL REFERENCE
ASTG09KMTC / ASTG12KMTC
with AOTG09KMTC / AOTG12KMTC
Specifications, dimensions, refrigerant circuit, electrical checks, diagnostics, R32 precautions, parts and accessories
Applicable combinations
Indoor: ASTG09KMTC / ASTG12KMTC
Outdoor: AOTG09KMTC / AOTG12KMTC
Refrigerant: R32
Power supply: 240 V, 50 Hz, supplied to outdoor unit
Quick navigation
Specifications Dimensions Refrigerant Electrical Resistance Checks Diagnostics R32 Safety Indoor Parts Outdoor Parts Accessories
1. Key specifications
ItemASTG09KMTCASTG12KMTC
Available voltage range198–264 V
Star rating index5.03.5
Cooling capacity - Rated2.5 kW3.5 kW
Cooling capacity - Min–Max0.9–3.6 kW0.9–4.1 kW
Heating capacity - Rated3.2 kW4.1 kW
Heating capacity - Min–Max0.9–5.3 kW0.9–6.1 kW
Input power - Cooling0.53 kW0.89 kW
Input power - Heating0.66 kW0.79 kW
Current - Cooling3.0 A4.2 A
Current - Heating3.5 A4.0 A
EER - Cooling4.713.93
COP - Heating4.844.68
Maximum operating current - Cooling6.0 A6.5 A
Maximum operating current - Heating7.5 A9.0 A
Outdoor unit summary
ItemAOTG09KMTCAOTG12KMTC
Refrigerant charge850 g850 g
Pre-charge pipe length15 m15 m
Maximum pipe length20 m20 m
Maximum height difference15 m15 m
Operating range - Cooling-10 to 46°C-10 to 46°C
Operating range - Heating-15 to 24°C-15 to 24°C
Sound pressure - Cool / Heat46 / 46 dB(A)49 / 49 dB(A)
2. Dimensions and weights
UnitNet dimensionsGross dimensionsWeight
Indoor270 × 834 × 222 mm277 × 914 × 332 mm10 kg net / 13 kg gross
Outdoor542 × 799 × 290 mm602 × 940 × 375 mm32 kg net / 35 kg gross
3. Refrigerant circuit and sensors
Major refrigerant components
Compressor, outdoor heat exchanger, expansion valve and coil, 2-way valve, 3-way valve and 4-way valve.
Sensor referenceFunction
ThDDischarge temperature
ThOOutdoor temperature
ThHOOutdoor heat exchanger outlet temperature
ThHMOutdoor heat exchanger middle temperature
ThRRoom temperature
ThPIIndoor pipe temperature
4. Electrical and PCB references
LocationModelIdentifier
Indoor control unitASTG09KMTCEZ-01836HSE
Indoor control unitASTG12KMTCEZ-01837HSE
Indoor main PCBASTG09KMTCK18RA-1806HSE-C1
Indoor main PCBASTG12KMTCK18RA-1807HSE-C1
Communication PCBBothK14YM-1500HSE-CA0
Outdoor inverter assemblyAOTG09KMTCEZ-018FHUE
Outdoor inverter assemblyAOTG12KMTCEZ-0187HUE
Outdoor main PCBAOTG09KMTCK17LG-1803HUE-C1
Outdoor main PCBAOTG12KMTCK17LG-1800HUE-C1
5. Field electrical checks
ComponentTest pointsReference resistanceReference temperature
Compressor windingU–V1.975 Ω25°C
Compressor windingV–W1.975 Ω25°C
Compressor windingU–W1.975 Ω25°C
Expansion valve coilRed–Blue46.0 Ω20°C
Expansion valve coilRed–Orange46.0 Ω20°C
Expansion valve coilRed–Yellow46.0 Ω20°C
Expansion valve coilRed–White46.0 Ω20°C
Measurement note: Isolate power, disconnect the component from the circuit and allow temperatures to stabilise before measuring. Compare all compressor windings with each other; significant imbalance is as important as the absolute value.
6. Error detection and diagnostics
For wireless-remote installations, the indoor operation, timer and economy lamps flash in coded patterns. Count each flash group carefully and allow the sequence to repeat before recording the fault.
Operation lampTimer lampEconomy lampFault description
63Inverter error
64Active filter / PFC circuit error
68Rush-current limiting resistor temperature rise error
71Discharge temperature sensor error
72Compressor temperature sensor error
78Pressure sensor error
79High-pressure switch error
81Outdoor fan motor 1 error
834-way valve error
84Expansion valve coil error
91Serial communication error
94Indoor unit power-supply interruption error
104High-pressure error
105Low-pressure error
7. R32 service precautions
Flammable refrigerant: Work on the refrigerant circuit must be undertaken by appropriately licensed personnel using procedures and equipment suitable for R32.
Before opening the refrigerant circuit
Confirm valid refrigerant-handling certification and R32 competence
Remove ignition sources and assess the work area
Ventilate the area and avoid confined-space work where practicable
Check the area with a detector suitable for flammable refrigerants
Continue monitoring during refrigerant work
8. Indoor-unit parts
ItemPart numberPart name
19387480009Bracket panel
29387471007Louver spring
39333704005Grille clamper R
49333608006Bush
59387714036Step motor holder assy
69901011047Step motor
79332861006Shaft cover
89387590050Drain pan total assy
99387476002Screw cap
109387479003U/D louver assy
119387478020Under cover R
129387756050Intake grille assy
139387477023Under cover L
149387473001Air filter
159387597035Wire cover assy
169333719009Grille clamper L
179316177017Drain cap
189316904002Drain hose assy
199318912005Remote controller holder
209332438673Remote controller
509387587012Base assy
519383765032WLAN adapter holder assy
52 - 099711141071Main PCB - 09 model
52 - 129711141088Main PCB - 12 model
539387488012Cable guide
549711146038Display assy
559711147011Indicator PCB
569317755061Pyroelectric sensor
579382134006Front panel cover B assy
589387753028Display case assy
599306489045Terminal
609603631017Brushless motor
619387589009Motor case assy
629317250009Air clean filter assy
639332911008Electric filter holder
649387593150Evaporator total assy
659900627041Thermistor assy
669387467000Room thermistor holder
679333628004Bearing D assy
689387055016Crossflow fan assy
9709626054Wire with connector
9. Outdoor-unit parts
ItemPart numberPart name
19322556028Top panel assy
29322811011Protective net
39306488130Terminal
49900435028Terminal
5 - 099710924187Main PCB - 09 model
5 - 129710924156Main PCB - 12 model
69900727062Thermistor assy
79900565060Thermistor assy
89900583019Reactor assy
99322418005Heat sink
109322570055Switch cover assy
119322552204Cabinet right assy
129322144003Drain pipe
139322314024Base assy
149319151007Emblem
159322135001Blow grille
169322555014Front panel assy
179322136008Propeller fan
189603553005Brushless motor
199322553010Motor bracket assy
209322275011Condenser total assy
5093224440044-way valve assy
519970195006Solenoid
529970173028Expansion valve coil
539322463029Pulse motor valve assy
5493224740012-way valve assy
5593224750083-way valve assy
569322427007Compressor assy
9322535009S-insulator B
9322536020S-insulator F
9322537003S-insulator H
9323045002S-insulator V
10. Accessories and optional parts
CategoryItems
Indoor standard accessoriesOperating instructions, installation instructions, wall-hook bracket, remote controller, remote holder, batteries ×2, large tapping screws ×5, small tapping screws ×2, cloth tape, filter holders ×2 and air-cleaning filter
Outdoor standard accessoriesInstallation instructions, cable tie and drain pipe
Optional partModelNotes
External connect kitUTY-XWZXZ5Communication kit required
External input/output PCBUTY-XCSXZ2Interface PCB
Communication kitUTY-TWRXZ2Enables non-polar 2-core wired remote control
Wireless LAN adapterUTY-TFSXF3Mobile-device management support
Service note: This article is a consolidated field reference. Confirm detailed connector pinouts, thermistor curves, complete error patterns and current replacement-part applicability against the relevant service manual, wiring diagram and parts system before completing repairs.