GENERAL AIRSTAGE TECHNICAL REFERENCE ARTG45LHTA / ARTG54LHTA with AOTG45LATL / AOTG54LATL Specifications, dimensions, refrigerant system, diagnostics, test procedures, parts and accessories |
Applicable combinations Indoor: ARTG45LHTA / ARTG54LHTA Outdoor: AOTG45LATL / AOTG54LATL |
|
Quick navigation Specifications Dimensions Refrigerant Electrical Diagnostics Test Run Pump Down Indoor Parts Outdoor Parts Accessories |
1. Specifications |
| Item | ARTG45LHTA + AOTG45LATL | ARTG54LHTA + AOTG54LATL | | Power source | 240 V, 50 Hz, single phase | | Cooling capacity | 12.5 kW | 14.0 kW | | Heating capacity | 14.0 kW | 16.0 kW | | Running current - Cooling | 16.9 A | 19.5 A | | Running current - Heating | 16.0 A | 18.6 A | | Input power - Cooling | 4.03 kW | 4.66 kW | | Input power - Heating | 3.80 kW | 4.44 kW | | E.E.R - Cooling | 3.10 kW/kW | 3.00 kW/kW | | C.O.P - Heating | 3.68 kW/kW | 3.60 kW/kW | | Moisture removal | 1.0 L/hr | 1.0 L/hr | | Indoor air circulation | 3,250 m³/h | 3,550 m³/h | | Outdoor air circulation - Cooling | 6,750 m³/h | 6,750 m³/h | | Outdoor air circulation - Heating | 6,200 m³/h | 6,850 m³/h | | Maximum current | 22.5 A | 23.5 A |
|
Noise levels |
| Location | Mode | ARTG45LHTA | ARTG54LHTA | | Indoor | High / Medium / Low | 43 / 39 / 35 dB | 45 / 40 / 36 dB | | Outdoor | Cooling | 55 dB | 55 dB | | Outdoor | Heating | 55 dB | 56 dB |
|
Fan motor references Indoor discrimination: MFG-54AVN ARTG45LHTA: High 1040/1000 rpm, Medium 880/840 rpm, Low 740/700 rpm ARTG54LHTA: High 1090/1050 rpm, Medium 900/860 rpm, Low 780/740 rpm
Outdoor discrimination: MFE-45VVT Cooling: Upper 850 rpm, Lower 800 rpm Heating AOTG45LATL: Upper 780 rpm, Lower 750 rpm Heating AOTG54LATL: Upper 850 rpm, Lower 830 rpm |
|
2. Dimensions |
| Unit | Dimensions H × W × D | Weight | Additional detail | | Indoor | 425 × 1,250 × 490 mm | 61 kg shipping / 54 kg net | Drain hose ID 23.4 mm / OD 25.4 mm | | Outdoor | 1,290 × 900 × 330 mm | 94 kg shipping / 86 kg net | — |
|
3. Refrigerant system |
| Item | Specification | | Compressor | Hermetic inverter, 6-pole, 3-phase DC motor, twin rotary | | Compressor discrimination | N-TF30HD1A | | Compressor weight | 15.4 kg including oil | | Refrigerant | R410A | | Factory charge | 3,350 g | | Additional charge | 40 g/m | | Maximum pipe height | 30 m | | Gas pipe | 15.88 mm (5/8") | | Liquid pipe | 9.52 mm (3/8") |
|
| Pipe length | Total refrigerant charge | | 20 m | 3,350 g | | 30 m | 3,750 g | | 40 m | 4,150 g | | 50 m | 4,550 g |
|
4. Electrical and circuit references |
Use the source wiring diagrams for detailed connector pinouts and PCB-level tracing. The available references cover:- Indoor and outdoor overall circuit diagrams
- Indoor control PCB
- Outdoor inverter, power-supply and transistor PCBs
- Indicator PCB and LED/button layout
|
|
5. Error detection and diagnostics |
Wired remote controller |
| When a fault occurs, the wired controller shows an error code with Er in the set-temperature display and identifies the affected indoor-unit number. |
|
Outdoor LED diagnostic workflow |
| Confirm the outdoor ERROR LED is blinking | | ↓ | Press ENTER once to step into the detailed fault display. | | ↓ | | Record the states of POWER, ERROR, PUMP DOWN, LOW NOISE, PEAK CUT and MODE LEDs L1-L6 | | ↓ | | Match the blink count and LED state to the service-manual fault table | | ↓ | Diagnose the identified group Communication, sensor, inverter, pressure, fan motor, valve or refrigerant system. |
|
6. Outdoor-unit test run |
Pre-checks |
- Outdoor unit securely installed
- Gas-leak inspection completed
- Pipe and drain insulation completed
- Drain discharge confirmed
- Cables and earth conductor connected correctly
- No airflow obstruction
- Correct refrigerant charge
- Gas and liquid stop valves fully open
- Crankcase heater energised for more than 6 hours
|
|
| Power ON and enter standby | | ↓ | Press ENTER for more than 3 seconds to enter test-run setting mode. | | ↓ | Use SELECT to choose COOL or HEAT Perform the first test run in COOL. | | ↓ | | Press ENTER to start | | ↓ | | Check noise, vibration and discharge-air temperature | | ↓ | | Press ENTER again to stop |
|
7. Outdoor-unit pump down |
| Safety: Do not touch electrical components other than the display-board buttons. Ensure the compressor is stopped before removing refrigerant piping. Never disconnect piping while the compressor is operating with valves open. |
|
| Confirm liquid and gas 3-way valves are fully open | | ↓ | | Turn power ON and wait 3 minutes | | ↓ | | Press PUMP DOWN for at least 3 seconds | | ↓ | | Approximately 3 minutes after compressor start, fully close the liquid valve | | ↓ | | When the LED state changes again, fully close the gas valve | | ↓ | | Compressor and fans stop automatically. Turn power OFF. |
|
| To stop pump down, press PUMP DOWN again. If the sequence stops due to a fault: switch power OFF, reopen both valves, wait 3 minutes, restore power and retry. If pump down cannot be completed, recover refrigerant through the service port. |
|
8. Indoor-unit parts |
| Description | Part number | | Panel Top Sub Assy | 9380191001 | | Panel Rear Sub Assy | 9380205005 | | Panel Side R Sub Assy | 9380194002 | | Panel Side L Sub Assy | 9380203001 | | Pipe Panel | 9380262008 | | Drain Pan Sub Assy | 9380193005 | | S Drain Pan Sub Assy | 9380204008 | | Hook | 9372055007 | | Remote Control | 9318593020 | | Front Panel Assy | 9380271000 | | Sirocco Fan | 9372059029 | | Fan Motor | 9603087012 | | Controller PCB Assy - 45 | 9708281032 | | Controller PCB Assy - 54 | 9708281049 | | Power Supply PCB Assy | 9708279015 | | Filter PCB Assy | 9708277028 | | Thermistor | 9704265012 | | Pipe Thermistor | 9900558000 | | Room Thermistor | 9703299254 | | Evaporator Sub Assy | 9380206002 |
|
9. Outdoor-unit parts |
| Description | Part number | | Top Panel Sub Assy | 9374417056 | | Front Panel Sub Assy | 9374414109 | | Service Panel Sub Assy | 9374415090 | | Right Panel Sub Assy | 9374416189 | | Motor DC Brushless | 9602843039 | | Propeller Fan Assy | 9366378020 | | Base Assy | 9374166220 | | Drain Assy | 9303029015 | | Drain Cap | 313166024302 | | Inverter PCB Assy - 45 | 9708690032 | | Inverter PCB Assy - 54 | 9708690049 | | Indicator PCB Assy | 9708678016 | | Power Supply PCB Assy | 9708688015 | | Capacitor PCB Assy | 9707257083 | | ACTPM | 9707592016 | | Transistor PCB Assy | 9708647043 | | Thermistor - Outdoor | 9900210069 | | Thermistor Assy - Heat Exchanger | 9900599027 | | Thermistor Assy - Discharge / Compressor | 9900598013 | | Compressor | 9810153005 | | Accumulator | 9379014021 | | Expansion Valve Assy | 9370947243 | | Expansion Valve Coil | 9970096044 | | 4-way Valve Assy | 9374425235 | | Pressure Switch | 9900186012 | | Pressure Sensor | 9900505080 |
|
10. Accessories and optional parts |
| Category | Items | | Indoor accessories | Special nuts A - large ×4, special nuts A - small ×4, large and small coupler insulation, binders, remote control and mounting screws | | Optional parts | Wired remote control UTY-RNNYN, remote sensor UTY-XSZX, external control set UTD-ECS5A | | Outdoor accessories | Drain pipe ×1, drain caps ×2, binders ×3 and one-touch bushes ×2 |
|
| Service note: This article is a consolidated field reference. Always confirm live measurements, connector pinouts, detailed error patterns and replacement part suitability against the applicable service manual, wiring diagram and current parts system before completing repairs. |
|