Ducted Connection Dimensions Dimensions
Print
Modified on: Wed, 15 Jul, 2026 at 12:17 PM
GENERAL AIRSTAGE Ducted Connection Dimensions Guide Quick reference for indoor and outdoor model matching, static pressure range, and duct connection sizes. | Use this guide before ordering or fabricating ductwork. Confirm the complete indoor model number and verify whether the required dimensions apply to the supply-air or return-air connection. |
| Quick navigation BulkheadMid StaticHigh Static 3 PhaseHigh PerformanceHigh Static 1 Phase | | Bulkhead | | Indoor model | Outdoor model | Static pressure modes | Recommended range (Pa) | Supply-air connection (mm) | Return-air connection (mm) | | ARTH09KLLAP | AOTH09KBTA | 10 | 0–90 | 650 × 150 | 575 × 174 | | ARTH12KLLAP | AOTH12KBTA | 10 | 0–90 | 650 × 150 | 575 × 174 | | ARTH18KLLAP | AOTH18KBTA | 10 | 0–90 | 850 × 150 | 775 × 174 | | ARTH09KSLAP | AOTH09KBTA | 4 | 0–30 | 650 × 150 | 575 × 174 | | ARTH12KSLAP | AOTH12KBTA | 6 | 0–30 | 650 × 150 | 575 × 174 | | ARTH18KSLAP | AOTH18KBTA | 6 | 0–50 | 850 × 150 | 775 × 174 |
| | Mid Static Duct — Single Phase | | Indoor model | Outdoor model | Static pressure modes | Recommended range (Pa) | Supply-air connection (mm) | Return-air connection (mm) | | ARTH18KMTAP | AOTH18KBTA | 10 | 50–150 | 790 × 177 | 895 × 195 | | ARTH24KMTAP | AOTH24KBTA | 10 | 50–150 | 790 × 177 | 895 × 195 | | ARTH24KMTAP | AOTH24KCTA | 10 | 50–150 | 790 × 177 | 895 × 195 | | ARTH30KMTAP | AOTH30KBTA | 10 | 50–150 | 1190 × 177 | 1295 × 195 | | ARTH30KMTAP | AOTH30KCTA | 10 | 50–150 | 1190 × 177 | 1295 × 195 | | ARTH36KMTAP | AOTH36KBTA | 10 | 50–150 | 1190 × 177 | 1295 × 195 | | ARTH45KMTAP | AOTH45KBTA | 10 | 50–150 | 1190 × 177 | 1295 × 195 | | ARTH54KMTAP | AOTH54KBTA | 10 | 50–150 | 1190 × 177 | 1295 × 195 |
| | High Static — Three Phase | | Indoor model | Outdoor model | Static pressure modes | Recommended range (Pa) | Supply-air connection (mm) | Return-air connection (mm) | | ARTH36KHTA | AOTH36KRTA | 16 | 60–210 | 850 × 295 | 865 × 325 | | ARTH45KHTA | AOTH45KRTA | 21 | 60–260 | 921 × 304 | 1062 × 351 | | ARTH54KHTA | AOTH54KRTA | 21 | 60–260 | 921 × 304 | 1062 × 351 | | ARTH60KHTA | AOTH60KRTA | 21 | 60–260 | 921 × 304 | 1062 × 351 | | ARTH65KHTA | AOTH65KRTA | 16 | 60–200 | 1162 × 277 | 1295 × 316 | | ARTH72KHTA | AOTH72KRTA | 16 | 60–200 | 1162 × 277 | 1295 × 316 | | ARTH90KHTA | AOTH90KRTA | 16 | 60–200 | 1162 × 277 | 1295 × 316 |
| | High Static — Single Phase (High Performance) | | Indoor model | Outdoor model | Static pressure modes | Recommended range (Pa) | Supply-air connection (mm) | Return-air connection (mm) | | ARTH30KHTA | AOTH30KCTA | 16 | 60–210 | 850 × 295 | 865 × 325 | | ARTH36KHTA | AOTH36KCTA | 16 | 60–210 | 850 × 295 | 865 × 325 | | ARTH45KHTA | AOTH45KCTA | 21 | 60–260 | 921 × 304 | 1062 × 351 | | ARTH54KHTA | AOTH54KCTA | 21 | 60–260 | 921 × 304 | 1062 × 351 | | ARTH60KHTB | AOTH60KCTA | 20 | 60–250 | 1162 × 277 | 1295 × 316 |
| | High Static — Single Phase | | Indoor model | Outdoor model | Static pressure modes | Recommended range (Pa) | Supply-air connection (mm) | Return-air connection (mm) | | ARTH24KHTA | AOTH24KBTA | 16 | 60–210 | 850 × 295 | 865 × 325 | | ARTH30KHTA | AOTH30KBTA | 16 | 60–210 | 850 × 295 | 865 × 325 | | ARTH36KHTA | AOTH36KBTA | 16 | 60–210 | 850 × 295 | 865 × 325 | | ARTH45KHTA | AOTH45KBTA | 21 | 60–260 | 921 × 304 | 1062 × 351 | | ARTH54KHTA | AOTH54KBTA | 21 | 60–260 | 921 × 304 | 1062 × 351 | | ARTH60KHTA | AOTH60KBTA | 21 | 60–260 | 921 × 304 | 1062 × 351 | | ARTH65KHTA | AOTH65KBTA | 16 | 60–200 | 1162 × 277 | 1295 × 316 |
| | Important: Dimensions are shown as width × height in millimetres. Confirm the current installation manual and the physical unit before fabrication, particularly where transitions, flexible connections, plenums, fire dampers or acoustic treatment are required. |
| | Before providing dimensions to a customer or contractor | - Confirm the complete indoor and outdoor model numbers.
- Confirm whether the requested measurement is for the supply-air or return-air opening.
- Confirm the required external static pressure and selected fan setting.
- Do not use cabinet dimensions as duct connection dimensions.
- Where site conditions differ, refer the contractor to the installation manual or General AIRSTAGE technical support.
|
| | GENERAL AIRSTAGE | Ducted Quick Connection Guide 2025 |
|
Did you find it helpful?
Yes
No
Send feedback Sorry we couldn't be helpful. Help us improve this article with your feedback.