ARTG54LHTC - AOTG54LCTL Single Phase Duct R410A Units
Freshdesk Solution Article - Technical Support Step-by-Step Phone Instructions
Safety position: This guide is for technical support coaching of licensed and competent service personnel only. Before live testing, confirm the person onsite is authorised, has PPE and suitable test equipment. For power-off tests, isolate supply and wait before touching electrical components. Do not instruct a customer or unqualified person to remove covers or perform electrical tests.
Document scopeError codesQuick mapOutdoor displayFlowchartsE:11 communication3 wire remote checkE:63 inverterE:65 IPME:94 overcurrentE:95 compressor controlE:A1 discharge tempE:A5 low pressureRemote signal SOPIndoor fanOutdoor fanEEVThermistorsCompressorActive filter / IPMTicket checklist
1. Document scope
| Area | Details |
|---|---|
| Indoor model | ARTG54LHTC |
| Outdoor model | AOTG54LCTL |
| System type | R410A single phase inverter duct system with two indoor fan motors and upper/lower outdoor fans. |
| Core electrical focus | Outdoor L-N supply, reverse transfer signal at terminal 1-3, forward transfer signal at terminal 2-3, CN140 remote supply check. |
| Purpose | Provide a Freshdesk-ready call guide with linked flowcharts, component tests, expected readings and ticket evidence requirements. |
2. Error code quick reference
| Code | Manual fault description | Phone support action / linked test |
|---|---|---|
| E:11 | Serial communication error | E:11 communication split flow |
| E:12 | Wired remote controller communication error | 3 wire remote controller check |
| E:39 | Fan motor drive circuit error | Indoor fan power supply PCB |
| E:41 | Indoor room thermistor error | Room thermistor testing |
| E:42 | Indoor heat exchanger thermistor error | Indoor heat exchanger thermistor |
| E:51 | Indoor unit fan motor 1 error | Indoor fan motor 1 |
| E:53 | Drainage error | Drain / float switch |
| E:59 | Indoor unit fan motor 2 error | Indoor fan motor 2 |
| E:5U | Indoor unit error | Intake and error confirmation |
| E:63 | Inverter error | Inverter / filter PCB flow |
| E:65 | IPM error | IPM error flow |
| E:71 | Discharge thermistor error | Outdoor thermistor testing |
| E:72 | Compressor thermistor error | Outdoor thermistor testing |
| E:73 | Heat exchanger liquid outlet thermistor error | Outdoor thermistor testing |
| E:74 | Outdoor thermistor error | Outdoor thermistor testing |
| E:77 | Heat sink thermistor error | Inverter PCB / heat sink thermistor |
| E:84 | Current sensor error | Current sensor / main PCB |
| E:86 | Pressure sensor / high pressure switch error | Pressure sensor / switch |
| E:94 | Over current error | Over current flow |
| E:95 | Compressor control error | Compressor control flow |
| E:97 | Outdoor unit fan motor 1 error | Outdoor fan motor 1 |
| E:98 | Outdoor unit fan motor 2 error | Outdoor fan motor 2 |
| E:99 | 4-way valve error | 4-way valve |
| E:A1 | Discharge temperature error | Discharge temperature flow |
| E:A3 | Compressor temperature error | Compressor temperature / refrigerant flow |
| E:A5 | Low pressure error | Low pressure flow |
3. Quick map
| Symptom / error family | Most likely area | Jump to |
|---|---|---|
| No operation / remote blank | Single phase supply, indoor PCB remote supply, Y1/Y2/Y3 wiring | Remote check |
| E:11 | Indoor/outdoor serial communication: reverse AC90-270 V at 1-3, forward AC30-130 V at 2-3 | Communication split flow |
| E:12 / remote comms | Y1/Y2/Y3 signal and indoor PCB CN140 remote supply | 3 wire remote flow |
| E:41/E:42/E:71/E:72/E:73/E:74/E:77 | Thermistor connector, resistance and PCB 5 V supply | Thermistors |
| E:39/E:51/E:59/E:97/E:98 | Fan rotation, obstruction, motor short, PCB output voltage | Indoor fan / Outdoor fan |
| E:63/E:65/E:94 | Inverter / IPM / overcurrent protection | E:63 / E:65 / E:94 |
| E:95 | Compressor motor control / compressor harness / transistor PCB | Compressor flow |
| E:A1/E:A3 | 3-way valve, EEV/strainer, fan/heat exchanger, thermistor, refrigerant charge | Discharge/compressor temp flow |
| E:A5 | Low pressure, valve position, fan/heat exchanger, EEV/strainer, pressure sensor, refrigerant | Low pressure flow |
4. Outdoor display and error history
| Outdoor display item | Freshdesk instruction |
|---|---|
| Outdoor indicator PCB | If ERROR LED is blinking high speed, press ENTER once to display the active error code by LED pattern. |
| Display unit controls | SW1 MODE, SW2 SELECT, SW3 ENTER, SW4 EXIT/INITIALIZE, SW5 PUMP DOWN. |
| Present value mode | Use outdoor buttons to view compressor frequency, upper/lower fan speed, EEV pulse, low/high pressure sensor value, outdoor air temperature, discharge temperature, heat exchanger middle temperature and current. |
| Error history mode | Press MODE twice during status display, then ENTER when POWER/MODE blinks twice to review newest error and previous errors. |
| Ticket evidence | Record the displayed present values and error history before power reset where possible. |
5. GREAT-style linked flowcharts
E:11 communication split flow - ARTG54LHTC / AOTG54LCTL
E:11 serial communication error or no indoor / outdoor communication
↓
↓
↓
Reverse transfer / outdoor signal path
Is AC90-270 V signal present at terminal 1-3?
YES
Outdoor reverse signal is present. Check field cable, noise, earthing and indoor receiving side.
Forward transfer / indoor signal path
Is AC30-130 V signal present at terminal 2-3?
YES
Indoor forward signal is present. Check wiring integrity, noise/earth and outdoor receiving side.
NO
Indoor controller PCB becomes suspect only after wiring, supply and external-noise checks are proven.
Useful linked checks
Important split: Reverse transfer is terminal 1-3 with AC90-270 V. Forward transfer is terminal 2-3 with AC30-130 V. Confirm L-N supply, field wiring, external noise/earthing and component loading before board approval.
3 wire remote controller communication check flow
Wired remote communication error / no operation / remote signal check
↓
↓
↓
Y1-Y3 is 12 VDC
no less than 11.4 VDC
no less than 11.4 VDC
Remote has controller power. Continue to Y2 signal checks.
Y1-Y3 is 0 VDC
Check CN140 terminal 1-3 on the indoor controller PCB. Manual reference is DC13 V supply to remote control.
Y1-Y3 below 11.4 VDC
Check cable length, poor joints, wrong polarity, damaged controller cable or loaded indoor PCB supply.
↓
Remove Y2 from the remote, keep conductor safe, then test between remote terminal Y2 and Y3
↓
Remote Y2-Y3 fluctuates 7-11 / 7-12 VDC pulse
Remote is producing signal. Continue to field cable signal check.
No pulse at remote Y2-Y3
Remote controller likely defective after confirming 12 VDC supply is correct.
↓
Test between disconnected Y2 wire going to indoor unit and Y3 COM
↓
Field Y2-Y3 fluctuates 7-11 / 7-12 VDC pulse
Indoor PCB is returning signal. Reconnect Y2. If communication still fails, inspect terminals, cable shielding/noise and controller condition.
No pulse on field Y2 wire
Check open cable / short to COM / incorrect terminal. If wiring is sound, suspect indoor controller PCB.
Record in ticket: Y1-Y3 supply voltage, remote Y2-Y3 pulse result, disconnected field Y2-to-Y3 pulse result, cable condition and CN140 1-3 voltage.
E:63 inverter error flow - Outdoor unit
Inverter PCB error information received from inverter PCB
↓
Reset power and confirm if inverter error returns
↓
Check external causes: temporary voltage drop, temporary open circuit, incorrect grounding, noise or related cables near power line
↓
Check wiring from power supply to filter PCB to inverter PCB
↓
Check connector and cable open condition
↓
If wiring and external causes are proven, replace filter PCB and inverter PCB as manual sequence
↓
External cause found
Correct supply/noise/earthing issue and retest before replacing parts.
Connector/wiring issue
Correct connector or wiring and reset power.
Wiring OK, fault remains
Replace filter PCB and inverter PCB after readings/photos are recorded.
Important: E:63 requires external cause and power-supply-to-filter-to-inverter wiring checks before PCB replacement.
E:65 IPM error flow - Outdoor unit
Abnormal current to IPM in main PCB; compressor protection repeats then permanent stop
↓
Check outdoor unit electrical component connections: removed connector, loose terminal, incorrect connection or open cable
↓
Check outdoor fan operation, heat exchanger obstruction and whether fan rotates by hand
↓
Check outdoor fan motor 1 and fan motor 2
↓
Check compressor with component testing procedure
↓
If checks do not improve symptom, main PCB becomes suspect
↓
Connector issue found
Correct removed connector, loose terminal or mis-wiring and reset power.
Airflow or fan fault
Correct airflow/coil/fan issue before PCB approval.
Compressor abnormal
Escalate as compressor fault after values are recorded.
All checks pass
Replace main PCB only after connections, fans and compressor are documented.
Important: E:65 on this model requires electrical connections, fan/heat exchanger, outdoor fan motor and compressor checks before main PCB approval.
E:94 over current error flow - Outdoor unit
Protection stop by overcurrent after inverter compressor start, generated consecutively 10 times
↓
Check outdoor fan operation, outdoor heat exchanger, air passages and ambient temperature
↓
Check whether discharged air is being sucked back into the outdoor unit
↓
Check transistor PCB / IPM
↓
If checks do not improve symptom, main PCB becomes suspect
↓
If main PCB does not improve symptom, compressor becomes suspect
↓
Airflow / heat exchanger issue
Clear obstruction, clean coil or correct recirculation before parts are replaced.
IPM abnormal
Replace transistor PCB after readings are recorded.
Main PCB suspected
Recommend main PCB only after airflow/fan/IPM evidence is documented.
Compressor suspected
Recommend compressor only after previous checks and main PCB sequence are completed.
Important: For E:94, prove airflow, fan operation, heat exchanger condition, ambient/recirculation and IPM before PCB or compressor recommendation.
E:95 compressor control error flow - Outdoor unit
Compressor rotor location out of phase with actual rotor location, repeated permanent stop
↓
Turn unit on and confirm whether abnormal compressor noise is present
↓
Isolate supply and visually inspect compressor harness cable, compressor terminals and main PCB / transistor PCB connections
↓
Check compressor winding resistance U-V, V-W and U-W and record values
↓
Check transistor PCB / IPM
↓
If connection and winding checks are normal but the error remains, main PCB then compressor sequence becomes suspect
↓
Abnormal compressor noise present
Record noise evidence and consider compressor fault after wiring and winding checks.
Harness burnt, loose, open or miswired
Repair or replace affected harness or terminal connection, then reset power and retest.
Compressor winding abnormal
Escalate as compressor fault after values are recorded.
IPM abnormal
Replace transistor PCB after readings are recorded.
Important: For E:95, physically inspect compressor harness and terminals. Do not replace compressor or PCB without recording compressor winding resistance and harness condition.
E:A1 discharge temperature / E:A3 compressor temperature flow - Outdoor unit
Discharge temperature 115C or compressor temperature 110C protection, generated twice within 24 hours
↓
Primary check: suspect refrigerant leak / insufficient refrigerant first
↓
Cooling: check 3-way valve gas side is fully open. Heating: check 3-way valve liquid side is fully open
↓
Check EEV operation / coil resistance, capillary / strainer restriction and temperature difference across strainer
↓
Check outdoor fan operation and heat exchanger for foreign matter / blocked fins / recirculation
↓
Check discharge or compressor temperature thermistor value and DC 5 V PCB supply
↓
Check refrigerant amount / leak test
↓
Leak or insufficient refrigerant found
Repair leak, pressure test, evacuate and weigh in charge as required.
3-way valve closed / not fully open
Open valve fully and re-test operation.
EEV / capillary / strainer issue
Confirm coil resistance, start-up noise, operation and temperature difference across restriction.
Thermistor abnormal
Replace thermistor or repair harness only after value is confirmed against temperature.
All checks pass but fault remains
Main PCB/inverter control becomes suspect after refrigerant, valves, EEV, airflow and thermistor are proven.
Important: Treat E:A1/E:A3 as a refrigerant and system-condition fault first. Common causes are valve not opened, EEV/strainer issue, outdoor fan/heat exchanger issue, thermistor fault, insufficient refrigerant or PCB control fault.
E:A5 low pressure error flow - Outdoor unit
Suction pressure 0.02 MPaG continued for 5 minutes, repeated 5 times within 2 hours
↓
Check 3-way valve is fully open
↓
Check outdoor ambient temperature is not below operating range
↓
Check outdoor fan operation, obstruction, recirculation and heat exchanger condition
↓
Check indoor and outdoor EEV operation and strainers for clogging
↓
Check solenoid valve SV1, suction pressure sensor characteristics and refrigerant amount
↓
Valve closed / restricted
Open valve fully, correct restriction and retest.
Ambient / airflow issue
Correct operating conditions, airflow, fan operation or blocked coil before replacing parts.
EEV / strainer issue
Check EEV coil, start-up noise, voltage and temperature difference across strainer.
Sensor / solenoid issue
Confirm pressure sensor and SV1 operation before PCB recommendation.
Refrigerant leak / undercharge
Repair leak, pressure test, evacuate and weigh in charge.
Important: Low pressure faults should be proven with valve position, ambient, airflow, EEV/strainer, solenoid, sensor and refrigerant evidence before approving parts.
6. Step-by-step phone support SOPs
SOP 1 - Intake and safety gate
- Confirm caller name, company, site address, indoor model/serial and outdoor model/serial.
- Confirm exact complaint: error code, operating mode, when it occurs and whether it is repeatable.
- Confirm safety: no burning smell, water ingress, damaged wiring, repeated breaker trips or refrigerant odour.
- Confirm tools: multimeter with AC/DC volts, resistance and diode test.
- Decision point: if caller is not qualified or cannot identify terminals safely, stop at non-invasive checks and arrange authorised attendance.
SOP 2 - E:11 indoor/outdoor serial communication
- Reset power and confirm if E:11 returns.
- Check external causes such as poor earth, noise or equipment causing harmonic wave near power cable.
- Check interconnect and control unit connections for loose connector, open cable or mis-wiring.
- Check outdoor supply: expected AC198-264 V at outdoor terminal L-N.
- Reverse transfer signal: check outdoor terminal 1-3. Expected swing AC90-270 V.
- Forward transfer signal: check outdoor terminal 2-3. Expected swing AC30-130 V.
- If reverse transfer signal is abnormal, check outdoor fan motor, active filter module, transistor PCB/IPM and filter PCB CN110 before main PCB approval.
- If forward transfer signal is abnormal, replace controller PCB after wiring, supply and external noise are proven.
SOP 3 - 3 wire remote signal test
- At the rear of the wall controller, confirm Y1 = 12 V/red, Y2 = signal/white, Y3 = COM/black.
- Measure Y1 to Y3: expected 12 VDC, no less than 11.4 VDC.
- Manual PCB supply reference: CN140 terminal 1-3 is the power supply to remote control and should be approximately DC13 V.
- Remove Y2 from the remote. Measure between remote terminal Y2 and Y3: expected fluctuating 7-11 / 7-12 VDC pulse.
- Measure between the disconnected Y2 wire going to the indoor unit and Y3: expected fluctuating 7-11 / 7-12 VDC pulse.
- If no 12 V supply, check indoor PCB remote power supply. If remote has supply but no Y2 pulse, suspect remote controller. If field Y2 has no return pulse, check cable and indoor controller PCB.
SOP 4 - Thermistor testing
- Isolate power. Check connector is not loose, removed, miswired or open.
- Disconnect thermistor and measure resistance out of circuit. Compare to actual bulb temperature.
- Indoor room thermistor rough values: 0C 33.6 kΩ, 5C 25.9 kΩ, 10C 20.2 kΩ, 15C 15.8 kΩ, 20C 12.5 kΩ, 25C 10.0 kΩ, 30C 8.0 kΩ, 35C 6.5 kΩ, 40C 5.3 kΩ, 45C 4.35 kΩ, 50C 3.59 kΩ.
- Indoor heat exchanger thermistor rough values: 0C 176 kΩ, 5C 134 kΩ, 10C 103 kΩ, 15C 80.3 kΩ, 20C 62.9 kΩ, 25C 49.7 kΩ, 30C 39.6 kΩ, 35C 31.7 kΩ, 40C 25.6 kΩ, 45C 20.8 kΩ, 50C 17.1 kΩ.
- Indoor connector references: Room thermistor CN110; H/E thermistor CN114.
- Outdoor connector references: discharge CN62 1-2, compressor CN62 3-4, heat exchanger outlet CN63 1-2, outdoor temperature CN61 1-3. Check each for DC5.0 V after removing thermistor.
- Replace thermistor only when resistance is open/short/out of table. Replace PCB only when connector/wiring and thermistor are proven.
SOP 5 - Indoor fan motor testing
- Power off. Rotate fan motor 1 and fan motor 2 by hand and check for obstruction, bearing lock, dropped fan or casing contact.
- Check ambient temperature around the motor and confirm no external heat source is affecting it.
- Check indoor fan motor using Service Parts Information: if motor is abnormal, replace indoor fan motor.
- Manual logic: if actual indoor fan frequency remains below one third of target frequency for more than 56 seconds, fan motor fault is detected.
- If rotation, ambient and motor checks do not improve symptom, replace power supply PCB as manual sequence.
- Record fan rotation, motor reading, connector condition and PCB decision.
SOP 6 - Outdoor fan motor testing
- Power off. Rotate upper and lower fan by hand and check obstruction, bearing lock, fan guard contact or damaged fan.
- Check ambient temperature around the motor and confirm no external heat source is affecting it.
- Check outdoor fan motor using circuit-test between Vm and GND. If short-circuited below 300 kΩ, replace outdoor fan motor and main PCB where required.
- Manual live output reference at main PCB side connector: Red-Black 280-373 VDC and White-Black 15 VDC ±1.5 V.
- Fan motor 1 is CN800. Fan motor 2 is CN802.
- On E:11 reverse transfer faults, abnormal outdoor fan motor can load the signal path. Check both fan motors before outdoor PCB approval.
SOP 7 - EEV and strainer testing
- Check EEV connector for loose connector or open cable.
- Remove connector and check EEV coil resistance. Common service training value: Yellow-Red, Orange-Red, Blue-Red, White-Red = 46 Ω ±4 Ω at 20C.
- Remove connector and check PCB drive voltage: expected DC12 V.
- Turn on power and listen/feel for EEV start-up operation noise.
- Manual EEV pulse range is 53-480 pulses; power-on initialisation drives 528 pulses to the closing direction.
- Check opening/closing effect by temperature difference. Closed valve creates inlet/outlet temperature difference; open valve has no temperature difference.
- Check strainer. A temperature difference across the strainer suggests internal clogging.
SOP 8 - Compressor testing
- Check compressor terminal connection and main PCB / transistor PCB connection for loose or incorrect wiring.
- Check winding resistance between U-V, V-W and U-W and record all three values. Treat 0 Ω, infinity or imbalance as abnormal.
- If compressor does not start or stops soon, also check gas pipe valve open, refrigerant leak, strainer clogging and harness condition before compressor approval.
- If connection and winding resistance do not improve symptom, follow manual sequence for transistor PCB/IPM, main PCB and then compressor.
SOP 9 - Active filter / transistor PCB / IPM
- Use this for E:11 reverse transfer abnormal, E:63 inverter error, E:65 IPM error, E:77 heat sink thermistor, E:94 overcurrent and E:95 compressor control error.
- Confirm L-N supply is within range before board approval.
- Inspect filter PCB, active filter module, transistor PCB/IPM and main PCB connections for loose connectors, corrosion, open cable or burn marks.
- For E:77, manual action is inverter PCB replacement because heat sink thermistor is built into IPM/inverter section.
- Check compressor winding and outdoor fan motor loading before recommending inverter/transistor/main PCB.
- Attach photos and readings to ticket before board approval.
SOP 10 - Pressure sensor / high pressure / low pressure
- Check pressure sensor or high pressure switch connector and wiring condition.
- Pressure sensor PCB supply reference: Red to Black is DC5 V ±5%; White to Black output follows pressure graph.
- For A5, check valve position, ambient, outdoor fan, indoor/outdoor EEV/strainer, SV1 and refrigerant amount before sensor or PCB replacement.
- Use outdoor present value mode to record low pressure range and high pressure range values where possible.
SOP 11 - Drain / float switch
- Check float switch operation and any blockage by dust.
- Remove float switch and check ON/OFF switching operation by meter.
- Check CN120 and shorted / pinched wire.
- Check drain hose for clogging, traps or poor fall.
- If all checks are normal and drainage error remains, controller PCB becomes suspect.
SOP 12 - 4-way valve
- Check connector is fitted, not miswired and no open cable.
- Check indoor thermistors are fitted in holders and not pinched or reading incorrectly.
- Remove CN6 and check solenoid coil resistance. Manual value is approximately 1.7 kΩ.
- Check valve position by piping temperature difference. If valve position is not correct after coil and thermistors are proven, valve may be faulty.
- If checks pass and error remains, main PCB becomes suspect.
SOP 13 - Current sensor
- Reset power and confirm if E:84 returns.
- Check external causes: voltage drop, momentary open circuit, noise and grounding.
- Check outdoor electrical component connectors, terminal tightness, miswiring and open cables.
- Manual detection logic: current sensor detects 0 A while inverter compressor operates above 56 rps after 1 minute from compressor start, excluding defrost.
- If checks do not improve symptom, main PCB becomes suspect.
7. Ticket evidence checklist
| Evidence required | Details to record |
|---|---|
| Model and serial | Indoor and outdoor model/serial, controller type and exact error display. |
| Safety and site condition | Who is onsite, licence/competency confirmation, power isolation status, access limitations, water ingress/burning smell/short circuit risk. |
| Outdoor display | Active error LED pattern, error history, present value readings: compressor frequency, upper/lower fan speed, EEV pulse, pressure values, temperatures and current. |
| Electrical readings | L-N supply voltage, reverse/forward communication readings, remote Y1/Y2/Y3 readings, fan motor Vm/GND result, PCB 5 V / 12 V / 13 V checks. |
| Component readings | Thermistor kΩ and measured temperature, EEV coil Ω, compressor winding Ω, transistor PCB/IPM observations, active filter/filter PCB result. |
| Refrigeration evidence | Valve positions, operating mode, ambient, fan operation, coil condition, pressures, leak test, strainer temperature difference, weighed charge details. |
| Approval decision | State what has been proven before recommending motor, thermistor, compressor, active filter, transistor PCB/IPM, inverter PCB, main PCB, controller PCB or power supply PCB. |