ARTG Three Phase Duct - AOTG36/45/54/60LATT R410A Units
ARTG Three Phase Duct - AOTG36/45/54/60LATT R410A Units
Freshdesk Solution Article - Technical Support Step-by-Step Phone Instructions
Safety position: This guide is for technical support coaching of licensed and competent service personnel only. Before live testing, confirm the person onsite is authorised, has PPE and suitable test equipment. For power-off tests, isolate supply and wait before touching electrical components. Do not instruct a customer or unqualified person to remove covers or perform electrical tests.
Document scopeError codesQuick mapOutdoor displayFlowchartsE:11 communication3 wire remote checkE:64 PFCE:65 trip terminal LE:94 trip detectionE:95 compressor controlE:A1 discharge tempE:A5 low pressureRemote signal SOPIndoor fanOutdoor fanEEVThermistorsCompressorInverter/PFC/IPMTicket checklist
1. Document scope
| Area | Details |
|---|---|
| Three phase outdoor models | AO*G36LATT, AO*G45LATT, AO*G54LATT, AOTG60LATT |
| ARTG duct indoor models in this manual | ARTG36LHTB, ARTG45LHTB, ARTG54LHTB, ARTG60LHTA plus related AU/AR/AB indoor combinations listed in the service instruction. |
| System type | R410A three phase inverter duct / high static duct, single or simultaneous operation multi type. |
| Core electrical focus | Three phase supply and communication checks: AC198-264 V at outdoor terminal 1-2, L1-N, L2-N, L3-N; serial signal AC70-130 V at outdoor terminal 2-3. |
| Purpose | Provide a Freshdesk-ready call guide with linked flowcharts, component tests, expected readings and ticket evidence requirements. |
2. Error code quick reference
| Code | Manual fault description | Phone support action / linked test |
|---|---|---|
| E:11 | Serial communication error | E:11 communication split flow |
| E:12 | Wired remote controller communication error | 3 wire remote controller check |
| E:21 | Unit number or refrigerant circuit address setting error | Address / refrigerant circuit check |
| E:22 | Indoor unit capacity error | Indoor capacity combination check |
| E:24 | Connection unit number error | Connection number check |
| E:27 | Primary / secondary unit setup error | Primary-secondary setup check |
| E:32 | Indoor unit PCB model information error | Indoor controller PCB / EEPROM |
| E:35 | Manual auto switch error | Manual auto switch |
| E:41 | Room temp sensor error | Indoor thermistor testing |
| E:42 | Indoor heat exchanger middle temp sensor error | Indoor thermistor testing |
| E:51 | Indoor unit fan motor error | Indoor fan motor |
| E:53 | Drain pump error | Drain / float switch |
| E:5U | Indoor unit error | Intake and error confirmation |
| E:62 | Outdoor unit main PCB model information / communication error | Outdoor PCB evidence |
| E:63 | Inverter error | Inverter / filter PCB checks |
| E:64 | PFC circuit error | PFC circuit flow |
| E:65 | Trip terminal L error / IPM error | Trip terminal L flow |
| E:71 | Discharge temp sensor error | Outdoor thermistor testing |
| E:72 | Compressor temp sensor error | Outdoor thermistor testing |
| E:73 | Heat exchanger liquid temp sensor error | Outdoor thermistor testing |
| E:74 | Outdoor temp sensor error | Outdoor thermistor testing |
| E:77 | Heat sink / PFC heat sink temp sensor error | Inverter/PFC heat sink |
| E:84 | Current sensor error | Current sensor / main PCB |
| E:86 | High pressure switch / pressure sensor error | Pressure sensor / switch |
| E:94 | Trip detection | Trip detection flow |
| E:95 | Compressor motor control / loss of synchronisation | Compressor control flow |
| E:97 | Outdoor unit fan motor 1 error | Outdoor fan motor 1 |
| E:98 | Outdoor unit fan motor 2 error | Outdoor fan motor 2 |
| E:99 | 4-way valve error | 4-way valve |
| E:A1 | Discharge temp. error | Discharge temperature flow |
| E:A3 | Compressor temp. error | Compressor temperature / refrigerant flow |
| E:A5 | Low pressure error | Low pressure flow |
3. Quick map
| Symptom / error family | Most likely area | Jump to |
|---|---|---|
| No operation / remote blank | Remote supply, controller PCB CN6/CN140/CN14, Y1/Y2/Y3 wiring | Remote check |
| E:11 | Indoor/outdoor serial communication: AC70-130 V at outdoor terminal 2-3 after three phase supply checks | Communication split flow |
| E:12 / remote comms | Y1/Y2/Y3 signal and indoor PCB remote supply connector by indoor model | 3 wire remote flow |
| E:41/E:42/E:71/E:72/E:73/E:74/E:77 | Thermistor connector, resistance and PCB 5 V supply | Thermistors |
| E:51/E:97/E:98 | Fan rotation, obstruction, motor short, PCB output voltage | Indoor fan / Outdoor fan |
| E:63/E:64/E:65/E:94 | Inverter / PFC / trip terminal / overcurrent protection | Inverter/PFC/IPM |
| E:95 | Compressor motor control / compressor harness / inverter board sequence | Compressor flow |
| E:A1/E:A3 | 3-way valve, EEV/strainer, fan/heat exchanger, thermistor, refrigerant charge | Discharge/compressor temp flow |
| E:A5 | Low pressure, valve position, fan/heat exchanger, EEV/strainer, pressure sensor, refrigerant | Low pressure flow |
4. Outdoor display and error history
| Outdoor display item | Freshdesk instruction |
|---|---|
| Outdoor indicator PCB | ERROR LED blinking high speed indicates active abnormal operation. Press ENTER once to display active error code by LED pattern. |
| Display unit controls | SW1 DIP selects COOL/HEAT during test operation. SW2 MODE, SW3 SELECT, SW4 ENTER/TEST RUN, SW5 EXIT/INITIALIZE, SW6 PUMP DOWN. |
| Present value mode | Use outdoor buttons to view compressor frequency, upper/lower fan speed, EEV pulse, low/high pressure sensor value, outdoor air temperature, discharge temperature, heat exchanger middle temperature and current. |
| Error history mode | Press MODE twice during status display, then ENTER when POWER/MODE blinks twice to review newest error and previous errors. |
| Ticket evidence | Record active error, history, present value readings and DIP switch positions before clearing error history. |
5. GREAT-style linked flowcharts
E:11 communication split flow - Three phase ARTG / AOTG LATT
E:11 serial communication error or no indoor / outdoor communication
↓
↓
↓
Reverse transfer / outdoor signal path
Is AC70-130 V signal present at terminal 2-3?
YES
Outdoor reverse signal is present. Check field cable, noise, earthing and indoor receiving side.
NO
↓
If outdoor fan motor is abnormal, replace outdoor fan motor and main PCB. If fan motors are normal, main PCB becomes suspect.
Forward transfer / indoor signal path
Is AC70-130 V signal present at terminal 2-3?
YES
Indoor forward signal is present. Check wiring integrity, noise/earth and outdoor receiving side.
NO
Replace indoor controller PCB and power PCB only after wiring, supply and external-noise checks are proven.
Useful linked checks
Important split: In the three phase LATT service instruction, reverse and forward communication are both checked for AC70-130 V at outdoor terminal 2-3, after confirming AC198-264 V at 1-2, L1-N, L2-N and L3-N. Do not approve boards until supply, wiring, external noise/earthing and fan loading checks are documented.
3 wire remote controller communication check flow
Wired remote communication error / no operation / remote signal check
↓
↓
↓
Y1-Y3 is 12 VDC
no less than 11.4 VDC
no less than 11.4 VDC
Remote has controller power. Continue to Y2 signal checks.
Y1-Y3 is 0 VDC
Check controller PCB supply connector: AR*G45/54LHTA CN6 1-3; ARTG45/54LHTB and ARTG60LHTA CN140 1-3; other models CN14 1-3.
Y1-Y3 below 11.4 VDC
Check cable length, poor joints, wrong polarity, damaged controller cable or loaded indoor PCB supply.
↓
Remove Y2 from the remote, keep conductor safe, then test between remote terminal Y2 and Y3
↓
Remote Y2-Y3 fluctuates 7-11 / 7-12 VDC pulse
Remote is producing signal. Continue to field cable signal check.
No pulse at remote Y2-Y3
Remote controller likely defective after confirming 12 VDC supply is correct.
↓
Test between disconnected Y2 wire going to indoor unit and Y3 COM
↓
Field Y2-Y3 fluctuates 7-11 / 7-12 VDC pulse
Indoor PCB is returning signal. Reconnect Y2. If communication still fails, inspect terminals, cable shielding/noise and controller condition.
No pulse on field Y2 wire
Check open cable / short to COM / incorrect terminal. If wiring is sound, suspect indoor controller PCB.
Record in ticket: Y1-Y3 supply voltage, remote Y2-Y3 pulse result, disconnected field Y2-to-Y3 pulse result, cable condition and CN6/CN140/CN14 1-3 voltage.
E:64 PFC circuit error flow - Outdoor unit
PFC circuit / PFC communication / PFC AD detection / PFC hardware abnormal
↓
Confirm three phase supply and neutral: 1-2, L1-N, L2-N and L3-N should be AC198-264 V
↓
Check external causes: temporary voltage drop, temporary open circuit, incorrect grounding, noise or cables near power line
↓
Check wiring from power supply to filter PCB / PFC / inverter PCB
↓
Check connector condition: removed connector, loose terminal, erroneous connection or open cable
↓
If checks do not improve the symptom, follow PFC / filter PCB / inverter PCB replacement sequence
↓
Supply/noise issue found
Correct supply, phase/neutral, earthing or noise issue and retest.
Connector/wiring issue
Correct connector or wiring and reset power.
PFC/filter abnormal
Replace PFC/filter PCB after results and photos are recorded.
Fault remains
Escalate inverter/main PCB sequence with evidence.
Important: E:64 on the three phase series is supply/PFC sensitive. Record all phase-to-neutral readings, grounding/noise checks and connector condition before PCB approval.
E:65 trip terminal L / IPM error flow - Outdoor unit
Trip terminal L error / abnormal current to IPM
↓
Confirm error history and whether the fault occurs on compressor start or after running
↓
Check three phase supply, neutral and external causes: voltage drop, poor earth, noise or momentary power issue
↓
Check outdoor unit electrical components: removed connector, loose terminal, incorrect connection or open cable
↓
Check outdoor fan operation, heat exchanger condition and ambient recirculation
↓
Check compressor winding resistance and compressor terminal connection
↓
Check inverter PCB / IPM and PFC section before main PCB decision
↓
Supply/noise issue found
Correct supply, earthing or external noise issue and retest before replacing parts.
Connector issue found
Correct removed connector, loose terminal or mis-wiring and reset power.
Fan/airflow issue
Correct airflow/coil/fan issue before PCB approval.
Compressor/IPM abnormal
Escalate compressor or inverter/PFC board after readings are recorded.
Important: E:65 should not be treated as a board-only fault until electrical connections, supply quality, outdoor fan/heat exchanger, compressor and inverter/PFC checks are documented.
E:94 trip detection / over current flow - Outdoor unit
Protection stop by overcurrent generation after inverter compressor start, generated consecutively
↓
Check outdoor fan operation, outdoor heat exchanger, air passages and ambient temperature
↓
Check whether discharged air is being sucked back into the outdoor unit
↓
Check inverter PCB / IPM
↓
If airflow and IPM checks do not improve symptom, main PCB becomes suspect
↓
If main PCB does not improve symptom, compressor becomes suspect
↓
Airflow / heat exchanger issue
Clear obstruction, clean coil or correct recirculation before parts are replaced.
IPM abnormal
Replace inverter/transistor PCB after readings are recorded.
Main PCB suspected
Recommend main PCB only after airflow/fan/IPM evidence is documented.
Compressor suspected
Recommend compressor only after previous checks and main PCB sequence are completed.
Important: For E:94, prove outdoor airflow, fan operation, heat exchanger condition, ambient/recirculation and IPM before PCB or compressor recommendation.
E:95 compressor motor control flow - Outdoor unit
Compressor motor control / rotor position detection / loss of synchronisation
↓
Turn unit on and confirm whether abnormal compressor noise is present
↓
Isolate supply and visually inspect compressor harness cable, compressor terminals and inverter/main PCB connections
↓
Check compressor winding resistance U-V, V-W and U-W and record all values
↓
Check inverter PCB / IPM
↓
If connection and winding checks are normal but the error remains, main PCB then compressor sequence becomes suspect
↓
Abnormal compressor noise present
Record noise evidence and consider compressor fault after wiring and winding checks.
Harness burnt, loose, open or miswired
Repair or replace affected harness or terminal connection, then reset power and retest.
Compressor winding abnormal
Escalate as compressor fault after values are recorded.
IPM abnormal
Replace inverter/transistor PCB after readings are recorded.
Important: For E:95, physically inspect compressor harness and terminals. Do not replace compressor or PCB without recording compressor winding resistance, harness condition and inverter/IPM readings.
E:A1 discharge temperature / E:A3 compressor temperature flow - Outdoor unit
Discharge temperature over 115C or compressor temperature over 110C protection
↓
Primary check: suspect refrigerant leak / insufficient refrigerant first
↓
Cooling: check 3-way valve gas side is fully open. Heating: check 3-way valve liquid side is fully open
↓
Check EEV operation / coil resistance, capillary / strainer restriction and temperature difference across strainer
↓
Check outdoor fan operation and heat exchanger for foreign matter / blocked fins / recirculation
↓
Check discharge or compressor temperature thermistor value and DC 5 V PCB supply
↓
Check refrigerant amount / leak test
↓
Leak or insufficient refrigerant found
Repair leak, pressure test, evacuate and weigh in charge as required.
3-way valve closed / not fully open
Open valve fully and re-test operation.
EEV / capillary / strainer issue
Confirm coil resistance, start-up noise, operation and temperature difference across restriction.
Thermistor abnormal
Replace thermistor or repair harness only after value is confirmed against temperature.
All checks pass but fault remains
Main PCB/inverter control becomes suspect after refrigerant, valves, EEV, airflow and thermistor are proven.
Important: Treat E:A1/E:A3 as a refrigerant and system-condition fault first. Common causes are valve not opened, EEV/strainer issue, outdoor fan/heat exchanger issue, thermistor fault, insufficient refrigerant or PCB control fault.
E:A5 low pressure error flow - Outdoor unit
Low pressure protection: pressure sensor value 0.02 MPaG or lower continued for 5 minutes
↓
Check 3-way valve is fully open
↓
Check outdoor ambient temperature is not too low
↓
Check outdoor fan operation, obstruction, recirculation and heat exchanger condition
↓
Check EEV operation and strainers for clogging
↓
Check solenoid valve, low pressure sensor characteristics and refrigerant amount
↓
Valve closed / restricted
Open valve fully, correct restriction and retest.
Ambient / airflow issue
Correct operating conditions, airflow, fan operation or blocked coil before replacing parts.
EEV / strainer issue
Check EEV coil, start-up noise, voltage and temperature difference across strainer.
Sensor / solenoid issue
Confirm pressure sensor and solenoid operation before PCB recommendation.
Refrigerant leak / undercharge
Repair leak, pressure test, evacuate and weigh in charge.
Important: Low pressure faults should be proven with valve position, ambient, airflow, EEV/strainer, solenoid, sensor and refrigerant evidence before approving parts.
6. Step-by-step phone support SOPs
SOP 1 - Intake and safety gate
- Confirm caller name, company, site address, indoor model/serial and outdoor model/serial.
- Confirm exact complaint: error code, operating mode, when it occurs and whether it is repeatable.
- Confirm whether the installation is single indoor or simultaneous multi and confirm all indoor unit addresses/capacities.
- Confirm safety: no burning smell, water ingress, damaged wiring, repeated breaker trips or refrigerant odour.
- Confirm tools: multimeter with AC/DC volts, resistance and diode test.
- Decision point: if caller is not qualified or cannot identify terminals safely, stop at non-invasive checks and arrange authorised attendance.
SOP 2 - E:11 indoor/outdoor serial communication - three phase
- Reset power and confirm if E:11 returns.
- Check external causes such as poor earth, noise or equipment causing harmonic wave near power cable.
- Check interconnect and control unit connections for loose connector, open cable or mis-wiring.
- Check outdoor supply: expected AC198-264 V at outdoor terminal 1-2, L1-N, L2-N and L3-N.
- Reverse transfer signal: check outdoor terminal 2-3. Expected swing AC70-130 V.
- Forward transfer signal: check outdoor terminal 2-3. Expected swing AC70-130 V.
- If reverse transfer signal is abnormal, check outdoor fan motor 1/2 before outdoor main PCB approval.
- If forward transfer signal is abnormal, replace indoor controller PCB and power PCB after wiring, supply and external noise are proven.
SOP 3 - 3 wire remote signal test
- At the rear of the wall controller, confirm Y1 = 12 V/red, Y2 = signal/white, Y3 = COM/black.
- Measure Y1 to Y3: expected 12 VDC, no less than 11.4 VDC.
- Manual PCB supply reference: AR*G45/54LHTA CN6 1-3; ARTG45/54LHTB and ARTG60LHTA CN140 1-3; other models CN14 1-3. Manual service instruction calls for DC12 V at this connector.
- Remove Y2 from the remote. Measure between remote terminal Y2 and Y3: expected fluctuating 7-11 / 7-12 VDC pulse.
- Measure between the disconnected Y2 wire going to the indoor unit and Y3: expected fluctuating 7-11 / 7-12 VDC pulse.
- If no 12 V supply, check indoor PCB remote power supply. If remote has supply but no Y2 pulse, suspect remote controller. If field Y2 has no return pulse, check cable and indoor controller PCB.
SOP 4 - Thermistor testing
- Isolate power. Check connector is not loose, removed, miswired or open.
- Disconnect thermistor and measure resistance out of circuit. Compare to actual bulb temperature.
- Indoor room thermistor rough values from the service instruction: -10C 58.2 kΩ, -5C 44.0 kΩ, 0C 33.6 kΩ, 5C 25.9 kΩ, 10C 20.2 kΩ, 15C 15.8 kΩ, 20C 12.5 kΩ, 25C 10.0 kΩ, 30C 8.0 kΩ, 35C 6.5 kΩ, 40C 5.3 kΩ, 45C 4.3 kΩ.
- ARTG45/54LHTB and ARTG60LHTA indoor thermistor connectors: H/E middle thermistor CN114, room temp thermistor CN110.
- Outdoor thermistor faults require connector/cable check, thermistor resistance check, then PCB DC5.0 V check.
- Replace thermistor only when resistance is open/short/out of table. Replace PCB only when connector/wiring and thermistor are proven.
SOP 5 - Indoor fan motor testing
- Power off. Rotate fan by hand and check for obstruction, bearing lock, dropped fan or casing contact.
- Check ambient temperature around the motor and confirm no external heat source is affecting it.
- Check indoor fan motor using Service Parts Information and component training values; if motor is abnormal, replace fan motor.
- For fan motor errors, if fan rotation, ambient and motor checks do not improve the symptom, replace the relevant power PCB/controller PCB as per model sequence.
- Record fan rotation, motor reading, connector condition and PCB decision.
SOP 6 - Outdoor fan motor testing
- Power off. Rotate upper and lower outdoor fan by hand and check obstruction, bearing lock, fan guard contact or damaged fan.
- Check ambient temperature around the motor and confirm no external heat source is affecting it.
- Check outdoor fan motor using circuit-test between Vm and GND. If short-circuited below 300 kΩ, replace outdoor fan motor and main PCB where required.
- Outdoor fan speed reference: upper/lower fan speeds are displayed in outdoor present value mode from 0-900 rpm.
- On E:11 reverse transfer faults, abnormal outdoor fan motor can load the signal path. Check both fan motors before outdoor PCB approval.
SOP 7 - EEV and strainer testing
- Check EEV connector for loose connector or open cable.
- Remove connector and check EEV coil resistance. Common service training value: Yellow-Red, Orange-Red, Blue-Red, White-Red = 46 Ω ±4 Ω at 20C.
- Remove connector and check PCB drive voltage: expected DC12 V.
- Turn on power and listen/feel for EEV start-up operation noise.
- Manual EEV pulse range is 50-480 pulses in cooling/dry and 40-480 pulses in heating. At compressor stop, EEV is set to 480 pulses. Initialization drives 528 pulses to closing direction.
- Check opening/closing effect by temperature difference. Closed valve creates inlet/outlet temperature difference; open valve has no temperature difference.
- Check strainer. A temperature difference across the strainer suggests internal clogging.
SOP 8 - Compressor testing
- Check compressor terminal connection and inverter/main PCB connection for loose or incorrect wiring.
- Check winding resistance between U-V, V-W and U-W and record all three values. Treat 0 Ω, infinity or imbalance as abnormal.
- If compressor does not start or stops soon, also check gas pipe valve open, refrigerant leak, strainer clogging and harness condition before compressor approval.
- If connection and winding resistance do not improve symptom, follow manual sequence for inverter/IPM, main PCB and then compressor.
SOP 9 - Inverter / PFC / IPM
- Use this for E:63 inverter error, E:64 PFC circuit error, E:65 trip terminal L, E:77 heat sink thermistor, E:94 trip detection and E:95 compressor control error.
- Confirm three phase supply readings are within range before board approval.
- Inspect filter PCB, inverter PCB, PFC connectors and harnesses for loose connectors, corrosion, open cable or burn marks.
- Check compressor winding and outdoor fan motor loading before recommending inverter/PFC/main PCB.
- Attach photos and readings to ticket before board approval.
SOP 10 - Pressure sensor / high pressure / low pressure
- Check pressure sensor or high pressure switch connector and wiring condition.
- Use outdoor present value mode to record low pressure range and high pressure range values where possible.
- For A5, check valve position, outdoor ambient, outdoor fan, EEV/strainer, solenoid valve and refrigerant amount before sensor or PCB replacement.
- Low pressure protection logic includes pressure sensor value 0.02 MPaG or less continuing for 5 minutes.
SOP 11 - Drain / float switch
- Check float switch operation and any blockage by dust.
- Remove float switch and check ON/OFF switching operation by meter.
- Check connector and shorted / pinched wire.
- Check drain hose for clogging, traps or poor fall.
- If all checks are normal and drainage error remains, controller PCB becomes suspect.
SOP 12 - Address / model combination / primary-secondary setup
- Check unit number or refrigerant circuit address settings; addresses must be consecutive within the same refrigerant circuit.
- Check total connected indoor capacity matches outdoor capacity within 3 minutes after power on.
- Check indoor unit number connection; 4 or more indoor units in the same refrigerant system triggers connection number error.
- Check primary/secondary setup. There must be one master unit in the same refrigerant system; avoid two masters and avoid address 0 set as slave.
- Correct DIP switch or wiring, reset power and retest before PCB approval.
SOP 13 - EEPROM / indoor PCB model information
- Reset power and confirm if E:32 returns.
- Check all indoor electrical connectors for loose connector or incorrect wiring.
- Check PCB for shortage, corrosion or water damage.
- Check external cause such as poor earth or harmonic noise near the power cable.
- If checks do not improve symptom, replace controller PCB.
SOP 14 - Outdoor PCB model information / communication
- Reset power and confirm if E:62 returns.
- Check temporary voltage drop, momentary open circuit and grounding.
- Check there are no related control cables routed near the power line causing noise.
- If checks do not improve symptom, replace outdoor main PCB.
SOP 15 - Manual auto switch
- Check whether the manual auto switch is stuck or being held on for 60 seconds or more.
- Check ON/OFF switching operation by meter.
- If manual auto switch is disabled, replace it.
- If switch testing does not improve symptom, replace controller PCB and indicator PCB as per manual.
SOP 16 - 4-way valve
- Check connector is fitted, not miswired and no open cable.
- Check relevant indoor thermistors are fitted in holders and not pinched or reading incorrectly.
- Check solenoid coil / valve operation where accessible.
- Check valve position by piping temperature difference. If valve position is not correct after coil and thermistors are proven, valve may be faulty.
- If checks pass and error remains, board control becomes suspect.
SOP 17 - Current sensor
- Reset power and confirm if E:84 returns.
- Check external causes: voltage drop, momentary open circuit, noise and grounding.
- Check outdoor electrical component connectors, terminal tightness, miswiring and open cables.
- If checks do not improve symptom, main PCB / current sensor board sequence becomes suspect.
7. Ticket evidence checklist
| Evidence required | Details to record |
|---|---|
| Model and serial | Indoor and outdoor model/serial, controller type, single/simultaneous multi arrangement and exact error display. |
| Safety and site condition | Who is onsite, licence/competency confirmation, power isolation status, access limitations, water ingress/burning smell/short circuit risk. |
| Outdoor display | Active error LED pattern, error history, present value readings: compressor frequency, upper/lower fan speed, EEV pulse, pressure values, temperatures and current. |
| Electrical readings | Three phase/neutral supply readings, reverse/forward communication readings, remote Y1/Y2/Y3 readings, fan motor Vm/GND result, PCB 5 V / 12 V checks. |
| Component readings | Thermistor kΩ and measured temperature, EEV coil Ω, compressor winding Ω, inverter/PFC/IPM observations, fan motor results. |
| Refrigeration evidence | Valve positions, operating mode, ambient, fan operation, coil condition, pressures, leak test, strainer temperature difference, weighed charge details. |
| Approval decision | State what has been proven before recommending motor, thermistor, compressor, PFC/filter PCB, inverter PCB/IPM, main PCB, controller PCB or power PCB. |