ARTG60LHTB - AOTG60LATA Single Phase Duct R410A Units

Freshdesk Solution Article - Technical Support Step-by-Step Phone Instructions
Safety position: This guide is for technical support coaching of licensed and competent service personnel only. Before live testing, confirm the person onsite is authorised, has PPE and suitable test equipment. For power-off tests, isolate supply and wait before touching electrical components. Do not instruct a customer or unqualified person to remove covers or perform electrical tests.

1. Document scope

AreaDetails
Indoor modelARTG60LHTB
Outdoor modelAOTG60LATA
System typeR410A single phase inverter duct system with upper and lower outdoor fan motors.
Core electrical focusOutdoor L-N supply, reverse transfer signal at terminal 1-3, forward transfer signal at terminal 2-3, CN140 remote supply check.
PurposeProvide a Freshdesk-ready call guide with linked flowcharts, component tests, expected readings and ticket evidence requirements.

2. Error code quick reference

CodeManual fault descriptionPhone support action / linked test
E:11Serial communication errorE:11 communication split flow
E:12Wired remote controller communication error3 wire remote controller check
E:39Fan motor drive circuit errorIndoor fan power supply PCB
E:41Indoor room thermistor errorThermistor testing
E:42Indoor heat exchanger thermistor errorThermistor testing
E:51Indoor unit fan motor 1 errorIndoor fan motor 1
E:53Drainage errorDrain / float switch
E:59Indoor unit fan motor 2 errorIndoor fan motor 2
E:5UIndoor unit errorIntake and error confirmation
E:63Inverter errorInverter / filter PCB checks
E:65IPM errorIPM error flow
E:71Discharge thermistor errorOutdoor thermistor testing
E:72Compressor thermistor errorOutdoor thermistor testing
E:73Heat exchanger liquid outlet / middle thermistor errorOutdoor thermistor testing
E:74Outdoor thermistor errorOutdoor thermistor testing
E:77Heat sink thermistor errorInverter PCB / heat sink thermistor
E:84Current sensor errorCurrent sensor / main PCB
E:86Pressure sensor / high pressure switch errorPressure sensor / high pressure switch
E:94Over current errorOver current flow
E:95Compressor control errorCompressor control flow
E:97Outdoor unit fan motor 1 errorOutdoor fan motor 1
E:98Outdoor unit fan motor 2 errorOutdoor fan motor 2
E:994-way valve error4-way valve
E:A1Discharge temperature errorDischarge temperature flow
E:A3Compressor temperature errorCompressor temperature / refrigerant flow
E:A5Low pressure errorLow pressure flow

3. Quick map

Symptom / error familyMost likely areaJump to
No operation / remote blankSingle phase supply, indoor PCB remote supply, Y1/Y2/Y3 wiringRemote check
E:11Indoor/outdoor serial communication: reverse AC90-270 V at 1-3, forward AC30-130 V at 2-3Communication split flow
E:12 / remote commsY1/Y2/Y3 signal and indoor PCB CN140 remote supply3 wire remote flow
E:41/E:42/E:71/E:72/E:73/E:74/E:77Thermistor connector, resistance and PCB 5 V supplyThermistors
E:39/E:51/E:59/E:97/E:98Fan rotation, obstruction, motor short, PCB output voltageIndoor fan / Outdoor fan
E:63/E:65/E:94Inverter / IPM / overcurrent protectionInverter/IPM / E:65 / E:94
E:95Compressor motor control / compressor harness / inverter PCBCompressor flow
E:A1/E:A33-way valve, EEV/strainer, fan/heat exchanger, thermistor, refrigerant chargeDischarge/compressor temp flow
E:A5Low pressure, valve position, fan/heat exchanger, EEV/strainer, pressure sensor, refrigerantLow pressure flow

4. Outdoor display and error history

Outdoor display itemFreshdesk instruction
Outdoor indicator PCBIf ERROR LED is blinking high speed, press ENTER once to display the active error code by LED pattern.
Present value modeUse outdoor buttons to view compressor frequency, upper/lower fan speed, EEV pulse, low/high pressure sensor value, outdoor air temperature, discharge temperature, heat exchanger middle temperature and current.
Error history modePress MODE twice during status display, then ENTER when POWER/MODE blinks twice to review newest error and previous errors.
Ticket evidenceRecord the displayed present values and error history before power reset where possible.

5. GREAT-style linked flowcharts

E:11 communication split flow - ARTG60LHTB / AOTG60LATA

E:11 serial communication error or no indoor / outdoor communication
Reverse transfer / outdoor signal path
Is AC90-270 V signal present at terminal 1-3?
YES
Outdoor reverse signal is present. Check field cable, noise, earthing and indoor receiving side.
Forward transfer / indoor signal path
Is AC30-130 V signal present at terminal 2-3?
YES
Indoor forward signal is present. Check wiring integrity, noise/earth and outdoor receiving side.
NO
Indoor controller PCB becomes suspect only after wiring, supply and external-noise checks are proven.
Useful linked checks
Important split: For ARTG60LHTB / AOTG60LATA, reverse transfer is terminal 1-3 with AC90-270 V. Forward transfer is terminal 2-3 with AC30-130 V. Do not approve boards until supply, wiring, external noise/earthing and loading checks are documented.

3 wire remote controller communication check flow

Wired remote communication error / no operation / remote signal check
Y1-Y3 is 12 VDC
no less than 11.4 VDC
Remote has controller power. Continue to Y2 signal checks.
Y1-Y3 is 0 VDC
Check CN140 terminal 1-3 on the indoor controller PCB. Manual reference is DC13 V supply to remote control.
Y1-Y3 below 11.4 VDC
Check cable length, poor joints, wrong polarity, damaged controller cable or loaded indoor PCB supply.
Remove Y2 from the remote, keep conductor safe, then test between remote terminal Y2 and Y3
Remote Y2-Y3 fluctuates 7-11 / 7-12 VDC pulse
Remote is producing signal. Continue to field cable signal check.
No pulse at remote Y2-Y3
Remote controller likely defective after confirming 12 VDC supply is correct.
Test between disconnected Y2 wire going to indoor unit and Y3 COM
Field Y2-Y3 fluctuates 7-11 / 7-12 VDC pulse
Indoor PCB is returning signal. Reconnect Y2. If communication still fails, inspect terminals, cable shielding/noise and controller condition.
No pulse on field Y2 wire
Check open cable / short to COM / incorrect terminal. If wiring is sound, suspect indoor controller PCB.
Record in ticket: Y1-Y3 supply voltage, remote Y2-Y3 pulse result, disconnected field Y2-to-Y3 pulse result, cable condition and CN140 1-3 voltage.

E:65 IPM error flow - Outdoor unit

IPM abnormal current protection
Check outdoor unit electrical component connections: removed connector, loose terminal, incorrect connection or open cable
Check outdoor fan operation, heat exchanger condition and ambient recirculation
Check outdoor fan motor 1 and fan motor 2
Check compressor winding resistance and compressor terminal connection
If checks do not improve symptom, main PCB becomes suspect
Connector issue found
Correct removed connector, loose terminal or mis-wiring and reset power.
Airflow or fan fault
Correct airflow/coil/fan issue before PCB approval.
Compressor abnormal
Escalate as compressor fault after values are recorded.
All checks pass
Replace main PCB only after connections, fans and compressor are documented.
Important: E:65 on this model requires electrical connections, outdoor fan/heat exchanger, compressor and main PCB sequence. Do not approve the board until fan motor and compressor evidence is documented.

E:94 over current error flow - Outdoor unit

Overcurrent protection after inverter compressor start processing completed, generated consecutively 10 times
Check outdoor fan operation, outdoor heat exchanger, air passages and ambient temperature
Check whether discharged air is being sucked back into the outdoor unit
Check inverter PCB / IPM
If checks do not improve symptom, main PCB becomes suspect
If main PCB does not improve symptom, compressor becomes suspect
Airflow / heat exchanger issue
Clear obstruction, clean coil or correct recirculation before parts are replaced.
IPM abnormal
Replace inverter/transistor PCB after readings are recorded.
Main PCB suspected
Recommend main PCB only after airflow/fan/IPM evidence is documented.
Compressor suspected
Recommend compressor only after previous checks and main PCB sequence are completed.
Important: For E:94, prove outdoor airflow, fan operation, heat exchanger condition, ambient/recirculation and IPM before PCB or compressor recommendation.

E:95 compressor control error flow - Outdoor unit

Compressor rotor position / compressor control error repeated within 40 seconds
Turn unit on and confirm whether abnormal compressor noise is present
Isolate supply and visually inspect compressor harness cable, compressor terminals and main PCB / inverter PCB connections
Check compressor winding resistance U-V, V-W and U-W and record values
Check inverter PCB / IPM
If connection and winding checks are normal but the error remains, main PCB then compressor sequence becomes suspect
Abnormal compressor noise present
Record noise evidence and consider compressor fault after wiring and winding checks.
Harness burnt, loose, open or miswired
Repair or replace affected harness or terminal connection, then reset power and retest.
Compressor winding abnormal
Escalate as compressor fault after values are recorded.
IPM abnormal
Replace inverter/transistor PCB after readings are recorded.
Important: For E:95, physically inspect compressor harness and terminals. Do not replace compressor or PCB without recording compressor winding resistance and harness condition.

E:A1 discharge temperature / E:A3 compressor temperature flow - Outdoor unit

Discharge temperature 115C or compressor temperature 110C protection during operation
Primary check: suspect refrigerant leak / insufficient refrigerant first
Cooling: check 3-way valve gas side is fully open. Heating: check 3-way valve liquid side is fully open
Check EEV operation / coil resistance, capillary / strainer restriction and temperature difference across strainer
Check outdoor fan operation and heat exchanger for foreign matter / blocked fins / recirculation
Check discharge or compressor temperature thermistor value and DC 5 V PCB supply
Check refrigerant amount / leak test
Leak or insufficient refrigerant found
Repair leak, pressure test, evacuate and weigh in charge as required.
3-way valve closed / not fully open
Open valve fully and re-test operation.
EEV / capillary / strainer issue
Confirm coil resistance, start-up noise, operation and temperature difference across restriction.
Thermistor abnormal
Replace thermistor or repair harness only after value is confirmed against temperature.
All checks pass but fault remains
Main PCB/inverter control becomes suspect after refrigerant, valves, EEV, airflow and thermistor are proven.
Important: Treat E:A1/E:A3 as a refrigerant and system-condition fault first. Common causes are valve not opened, EEV/strainer issue, outdoor fan/heat exchanger issue, thermistor fault, insufficient refrigerant or main PCB.

E:A5 low pressure error flow - Outdoor unit

Suction pressure 0.02 MPaG continued for 5 minutes and repeated 5 times within 2 hours
Check 3-way valve is fully open
Check outdoor ambient temperature is not too low
Check outdoor fan operation, obstruction, recirculation and heat exchanger condition
Check EEV operation and strainers for clogging
Check solenoid valve, low pressure sensor characteristics and refrigerant amount
Valve closed / restricted
Open valve fully, correct restriction and retest.
Ambient / airflow issue
Correct operating conditions, airflow, fan operation or blocked coil before replacing parts.
EEV / strainer issue
Check EEV coil, start-up noise, voltage and temperature difference across strainer.
Sensor / solenoid issue
Confirm pressure sensor and solenoid operation before PCB recommendation.
Refrigerant leak / undercharge
Repair leak, pressure test, evacuate and weigh in charge.
Important: Low pressure faults should be proven with valve position, ambient, airflow, EEV/strainer, solenoid, sensor and refrigerant evidence before approving parts.

6. Step-by-step phone support SOPs

SOP 1 - Intake and safety gate

  1. Confirm caller name, company, site address, indoor model/serial and outdoor model/serial.
  2. Confirm exact complaint: error code, operating mode, when it occurs and whether it is repeatable.
  3. Confirm safety: no burning smell, water ingress, damaged wiring, repeated breaker trips or refrigerant odour.
  4. Confirm tools: multimeter with AC/DC volts, resistance and diode test.
  5. Decision point: if caller is not qualified or cannot identify terminals safely, stop at non-invasive checks and arrange authorised attendance.

SOP 2 - E:11 indoor/outdoor serial communication

  1. Reset power and confirm if E:11 returns.
  2. Check external causes such as poor earth, noise or equipment causing harmonic wave near power cable.
  3. Check interconnect and control unit connections for loose connector, open cable or mis-wiring.
  4. Check outdoor supply: expected AC198-264 V at outdoor terminal L-N.
  5. Reverse transfer signal: check outdoor terminal 1-3. Expected swing AC90-270 V.
  6. Forward transfer signal: check outdoor terminal 2-3. Expected swing AC30-130 V.
  7. If reverse transfer signal is abnormal, check outdoor fan motor 1/2, active filter module, inverter PCB/IPM and filter PCB CN110 before main PCB approval.
  8. If forward transfer signal is abnormal, replace controller PCB after wiring, supply and external noise are proven.

SOP 3 - 3 wire remote signal test

  1. At the rear of the wall controller, confirm Y1 = 12 V/red, Y2 = signal/white, Y3 = COM/black.
  2. Measure Y1 to Y3: expected 12 VDC, no less than 11.4 VDC.
  3. Manual PCB supply reference: CN140 terminal 1-3 is the power supply to remote control and should be approximately DC13 V.
  4. Remove Y2 from the remote. Measure between remote terminal Y2 and Y3: expected fluctuating 7-11 / 7-12 VDC pulse.
  5. Measure between the disconnected Y2 wire going to the indoor unit and Y3: expected fluctuating 7-11 / 7-12 VDC pulse.
  6. If no 12 V supply, check indoor PCB remote power supply. If remote has supply but no Y2 pulse, suspect remote controller. If field Y2 has no return pulse, check cable and indoor controller PCB.

SOP 4 - Thermistor testing

  1. Isolate power. Check connector is not loose, removed, miswired or open.
  2. Disconnect thermistor and measure resistance out of circuit. Compare to actual bulb temperature.
  3. Indoor room thermistor rough values: 0C 33.6 kΩ, 5C 25.9 kΩ, 10C 20.2 kΩ, 15C 15.8 kΩ, 20C 12.5 kΩ, 25C 10.0 kΩ, 30C 8.0 kΩ, 35C 6.5 kΩ, 40C 5.3 kΩ, 45C 4.35 kΩ, 50C 3.59 kΩ.
  4. Indoor heat exchanger thermistor rough values: 0C 176 kΩ, 5C 134 kΩ, 10C 103 kΩ, 15C 80.3 kΩ, 20C 62.9 kΩ, 25C 49.7 kΩ, 30C 39.6 kΩ, 35C 31.7 kΩ, 40C 25.6 kΩ, 45C 20.8 kΩ, 50C 17.1 kΩ.
  5. Outdoor thermistor 5 V checks: discharge CN62:1-2, compressor CN62:3-4, heat exchanger outlet CN63:1-2, outdoor temperature CN61:1-3.
  6. With thermistor removed, check PCB supply at thermistor connector: expected DC5.0 V.
  7. Replace thermistor only when resistance is open/short/out of table. Replace PCB only when connector/wiring and thermistor are proven.

SOP 5 - Indoor fan motor testing

  1. Power off. Rotate fan motor 1 and fan motor 2 by hand and check for obstruction, bearing lock, dropped fan or casing contact.
  2. Check ambient temperature around the motor and confirm no external heat source is affecting it.
  3. Check indoor fan motor using Service Parts Information: circuit-test between Vm and GND. If short-circuited below 300 kΩ, replace indoor fan motor and relevant power PCB.
  4. For E:39 fan motor drive circuit, check external voltage drop/noise, connector condition and indoor power supply PCB before board replacement.
  5. Record fan rotation, motor reading, connector condition and PCB decision.

SOP 6 - Outdoor fan motor testing

  1. Power off. Rotate upper and lower fan by hand and check obstruction, bearing lock, fan guard contact or damaged fan.
  2. Check ambient temperature around the motor and confirm no external heat source is affecting it.
  3. Check outdoor fan motor using circuit-test between Vm and GND. If short-circuited below 300 kΩ, replace outdoor fan motor and main PCB where required.
  4. Manual live output reference at main PCB side connector: Red-Black 280-373 VDC and White-Black 15 VDC ±1.5 V.
  5. Fan motor 1 upper is CN800. Fan motor 2 lower is CN802.
  6. On E:11 reverse transfer faults, abnormal outdoor fan motor can load the signal path. Check both fan motors before outdoor PCB approval.

SOP 7 - EEV and strainer testing

  1. Check EEV connector for loose connector or open cable.
  2. Remove connector and check EEV coil resistance. Common service training value: Yellow-Red, Orange-Red, Blue-Red, White-Red = 46 Ω ±4 Ω at 20C.
  3. Remove connector and check PCB drive voltage: expected DC12 V.
  4. Turn on power and listen/feel for EEV start-up operation noise.
  5. EEV control pulse range in the manual is 50-480 pulses in cooling and 40-480 pulses in heating; power-on initialisation drives 528 pulses to the closing direction.
  6. Check opening/closing effect by temperature difference. Closed valve creates inlet/outlet temperature difference; open valve has no temperature difference.
  7. Check strainer. A temperature difference across the strainer suggests internal clogging.

SOP 8 - Compressor testing

  1. Check compressor terminal connection and main PCB / inverter PCB connection for loose or incorrect wiring.
  2. Check winding resistance between U-V, V-W and U-W and record all three values. Treat 0 Ω, infinity or imbalance as abnormal.
  3. If compressor does not start or stops soon, also check gas pipe valve open, refrigerant leak, strainer clogging and harness condition before compressor approval.
  4. If connection and winding resistance do not improve symptom, follow manual sequence for inverter PCB/IPM, main PCB and then compressor.

SOP 9 - Active filter module

  1. Use this for E:11 reverse transfer abnormal signal follow-on, inverter-link faults and active filter checks from the service parts section.
  2. Check external causes first: voltage drop, momentary power failure, defective contact, noise and grounding.
  3. Check connector condition: removed connector, erroneous connection or open cable.
  4. Check active filter module using the service parts method. If abnormal, replace active filter module.
  5. If active filter is normal, continue to inverter PCB / IPM and then main PCB.

SOP 10 - Inverter PCB / IPM

  1. Use this for E:63 inverter error, E:65 IPM error, E:77 heat sink thermistor, E:94 overcurrent and E:95 compressor control error.
  2. Confirm L-N supply is within range before board approval.
  3. Inspect inverter PCB connections and harnesses for loose connectors, corrosion, open cable or burn marks.
  4. For E:77, manual action is inverter PCB replacement because heat sink thermistor is built in.
  5. Check compressor winding and outdoor fan motor loading before recommending inverter PCB or main PCB.
  6. Attach photos and readings to ticket before board approval.

SOP 11 - Pressure sensor / high pressure / low pressure

  1. Check pressure sensor or high pressure switch connector and wiring condition.
  2. High pressure switch reference: contact changes at approximately 4.2 ±0.1 MPa and returns at approximately 3.2 ±0.15 MPa.
  3. For A5, check valve position, ambient, outdoor fan, EEV/strainer, solenoid valve and refrigerant amount before sensor or PCB replacement.
  4. Use outdoor present value mode to record low pressure range and high pressure range values where possible.

SOP 12 - Drain / float switch

  1. Check float switch operation and any blockage by dust.
  2. Remove float switch and check ON/OFF switching operation by meter.
  3. Check CN120 and shorted / pinched wire.
  4. Check drain hose for clogging, traps or poor fall.
  5. If all checks are normal and drainage error remains, controller PCB becomes suspect.

SOP 13 - 4-way valve

  1. Check connector is fitted, not miswired and no open cable.
  2. Check indoor thermistors are fitted in holders and not pinched or reading incorrectly.
  3. Remove CN6 and check solenoid coil resistance. Manual value is approximately 1.7 kΩ.
  4. Check valve position by piping temperature difference. If valve position is not correct after coil and thermistors are proven, valve may be faulty.
  5. If checks pass and error remains, main PCB becomes suspect.

SOP 14 - Current sensor

  1. Reset power and confirm if E:84 returns.
  2. Check external causes: voltage drop, momentary open circuit, noise and grounding.
  3. Check outdoor electrical component connectors, terminal tightness, miswiring and open cables.
  4. If checks do not improve symptom, main PCB becomes suspect.

7. Ticket evidence checklist

Evidence requiredDetails to record
Model and serialIndoor and outdoor model/serial, controller type and exact error display.
Safety and site conditionWho is onsite, licence/competency confirmation, power isolation status, access limitations, water ingress/burning smell/short circuit risk.
Outdoor displayActive error LED pattern, error history, present value readings: compressor frequency, upper/lower fan speed, EEV pulse, pressure values, temperatures and current.
Electrical readingsL-N supply voltage, reverse/forward communication readings, remote Y1/Y2/Y3 readings, fan motor Vm/GND result, PCB 5 V / 12 V / 13 V checks.
Component readingsThermistor kΩ and measured temperature, EEV coil Ω, compressor winding Ω, inverter PCB/IPM observations, active filter result.
Refrigeration evidenceValve positions, operating mode, ambient, fan operation, coil condition, pressures, leak test, strainer temperature difference, weighed charge details.
Approval decisionState what has been proven before recommending motor, thermistor, compressor, active filter, inverter PCB/IPM, main PCB, controller PCB or power PCB.