Freshdesk Solution Article - Technical Support Step-by-Step Phone Instructions

Safety position: This guide is for phone support coaching of licensed and competent service personnel. Confirm isolation, PPE, correct test equipment and safe access before any live testing. High voltage is present: 415V AC three phase and DC bus voltage can be approximately 560-600V DC. Do not instruct customers or unqualified persons to remove covers or perform electrical tests.

1. Document scope

AreaDetails
Models coveredIndoor: ARTC72LATU / ARTC90LATU
Outdoor: AOTA72LALT / AOTA90LALT
System typeR410A inverter ducted, 415V 50Hz three phase 4W outdoor supply, wired remote controller system.
Primary source materialARTC72/90LATU Service Instruction, ARTC72/90LATU Service Manual, IPM Protection troubleshooting sheet, and Service Agent Training component testing material.
PurposeProvide a phone-support workflow with clickable jump links so Technical Support can quickly move to a component test such as fan motor, thermistor, EEV, pressure sensor, compressor/IPM, or communication.

2. Quick map

Use this section while speaking to the agent. The links jump directly to the test section.

Symptom / error familyMost likely areaJump to
E01 / E13 serial communication issuesIndoor/outdoor signal or wiringCommunication test
E00 wired remote controller errorRemote controller supply or Y1/Y2/Y3 signalRemote signal test
E0A / E06 / E0C / E0E / E15 thermistor errorsThermistor, wiring, connector, PCB return voltageThermistor testing
E16 pressure switch / pressure sensor errorPressure transducer 5V supply, return voltage, diode checkPressure sensor test
E17 IPM protectionConnection, airflow, outdoor fan, compressor, inverter PCBIPM protection flow
E1b outdoor fan errorOutdoor DC fan motor, obstruction, feedback signalFan motor test
E19 inverter voltage protection415V AC input, DC bus, diode bridge, fuses, inverter boardPower checks / Diode bridge
E2F low pressure or no cooling/heatingValves, refrigerant charge, EEV, strainer, airflowNo cooling/heating flow
Drain fault / water issueDrain pump, float switch, drain restrictionDrain and float switch

3. Error code quick reference

The wired remote controller and outdoor 7-segment display should be cross-checked. On the outdoor board, the ERROR lamp flashes rapidly; press ENTER to show the error content, then SELECT to scroll stored errors.

CodeFaultPriority test link
E01Serial error - reverse transferSerial communication
E13Serial error - forward transfer / indoor signal errorSerial communication
E00Wired remote controller errorRemote signal
E02Room temperature thermistor errorThermistors
E04Indoor heat exchanger middle thermistor errorThermistors
E06Outdoor heat exchanger outlet thermistor errorThermistors
E0AOutdoor temperature thermistor errorThermistors
E0COutdoor discharge pipe thermistor errorThermistors
E0EHeat sink thermistor inverter errorThermistors
E0FDischarge temperature errorRefrigeration / airflow
E15Compressor thermistor errorThermistors
E16Pressure switch / pressure sensor errorPressure sensor
E17IPM protectionIPM protection
E1ACompressor location detection errorCompressor
E1bOutdoor fan errorFan motor
E19Inverter voltage protectionPower / Diode bridge
E24Excessive high pressure protection on coolingAirflow / heat exchanger
E2APower supply frequency detection errorPower checks
E2bCompressor temperature errorRefrigeration / compressor temp
E2EInverter communication errorPower / Inverter PCB
E2FLow pressure errorLow pressure flow
E34 / E37Indoor fan motor 1 or 2 lock / revolution errorIndoor fan motor
E38 / E39Indoor fan motor 1 or 2 driving circuit errorIndoor fan drive
E98Pump down errorPump down
E99Indoor unit error conditionCheck wired remote error and indoor PCB/communication

5. Remote signal test

Use this where the wired remote controller is blank, has E00, intermittent control, or no response.

1
Ask the agent to identify if the controller is wired as 2-wire or 3-wire. For 3-wire, test at Y1, Y2 and Y3.
2
Measure Y1 to Y3. Expected: 12V DC, no less than 11.4V DC. If missing, suspect controller board/supply path.
3
Remove Y2 and test between Y3 and the disconnected Y2 cable going to the indoor unit. Expected: fluctuating 7-11V DC pulse.
4
Test between Y3 and Y2 terminal. Expected: fluctuating 7-11V DC pulse.
Phone note: If Y1-Y3 supply is correct but the pulse is absent, determine whether the failure follows the controller, cable, or indoor PCB before quoting parts.

6. Indoor/outdoor serial communication test

Use for E01, E13, intermittent operation, or when either unit is not proving communication.

1
Confirm correct 415V outdoor supply and indoor supply path. Confirm terminals 1, 2, 3 are not crossed and that the signal cable is not loose, open, damaged, or connected to earth.
2
Communication is measured on DC volts between Neutral and Signal. Black lead to Neutral, red lead to Signal.
3
Isolate power, remove signal cable from Terminal 3 at the outdoor unit, re-apply power and test each direction separately.
4
For ARTC indoor signal, expected signal is generally 60-120V DC.
5
For AOTA outdoor signal, expected signal is generally 40-90V DC.
6
If one side is 0-5V DC while the other side produces signal, the side with 0-5V DC is the likely communication fault area. Reconfirm with wiring disconnected before condemning a board.
Do not skip: Reset power after correcting removed connectors or mis-wiring. Confirm no signal wire short to earth.

7. Power and DC bus checks

Use for no operation, E19 inverter voltage protection, inverter communication errors, no DC bus, no fan/compressor output, or repeated PCB failures.

1
Confirm outdoor supply: 415V AC phase-to-phase across L1-L2, L2-L3 and L1-L3. Confirm approximately 240V AC phase-to-neutral/earth.
2
Confirm fuses and hard-wired fuses are intact with power isolated. Do not bypass fuses.
3
Confirm the inverter DC output / DC bus. Three phase bridge rectifier output should be approximately 560-600V DC between + and -.
4
Confirm low-voltage PCB supplies where available: thermistors generally use 5V DC, EEV/fresh air/heater control can use 12V or 13V DC depending on connector, and fan control can use 15V DC.
5
If AC is present but DC bus is absent, test the bridge rectifier, inverter PCB, main relay path, fuses, fan motor, EEV coil, thermistors and pressure transducer before replacing PCB.

Jump to diode bridge test | Jump to IPM test | Jump to fan motor test

8. DC fan motor testing - indoor and outdoor

Use for E1b, E34, E37, E38, E39, non-starting fan, fan hunting, overheat/high pressure faults or IPM protection where airflow is suspect.

1
Confirm the fan blade/wheel rotates freely by hand with power isolated. Check bearings, foreign matter, wheel rub and water damage.
2
Do not disconnect or reconnect fan motor plugs with power applied. Isolate power and wait for DC bus discharge.
3
For standard DC brushless fan motors, use diode test, not resistance. Resistance can be misleading.
TestExpected value
Red lead RED, black lead BLACKO/L
Red lead WHITE, black lead BLACK0.5V to 1.8V, depending on motor generation
Black lead BLACK, red lead RED0.8V to 1.1V
Black lead BLACK, red lead WHITE0.4V to 0.6V
4
On live checks only by competent persons, confirm high-voltage fan supply and control supply at the plug. Typical training values are high voltage DC 330-380V DC, DC ground black, and 15V DC control power white on standard fan motor types.
5
If a fan motor fails diode test, is seized, or has damaged feedback/speed wiring, replace the fan motor before replacing the PCB. A failed fan can damage the board.
Critical: Never unplug the DC fan motor while powered. This can damage the PCB and create a safety risk.

9. Thermistor testing

Use for E02, E04, E06, E0A, E0C, E0E, E15 or any protection fault where sensor value drives control.

1
Power-on test: measure from DC ground to one side of the thermistor plug. Expected supply is generally 5V DC.
2
Measure return voltage from DC ground to the other thermistor wire. Return voltage should be below 5V DC and should align with bulb temperature.
3
Power-off test: unplug the thermistor and measure resistance in kΩ. Confirm bulb temperature and compare against thermistor table or Mobile Technician conversion tool.
4
Inspect physical condition: bulb seated in holder, cable not pinched, connector not corroded, no moisture damage, no short to earth.
Training reference at 20°CResistance / return voltage guide
Room temperatureApprox. 12.53kΩ / 2.21V
Indoor heat exchanger temperatureApprox. 62.90kΩ / 2.21V
Discharge temperatureApprox. 64.50kΩ / 0.83V
Compressor temperatureApprox. 62.55kΩ / 0.86V
Outdoor temperatureApprox. 12.64kΩ / 3.75V
Outdoor heat exchanger / liquid / suction style sensorsApprox. 6.10kΩ family, verify exact thermistor table for this model
Phone note: Do not condemn a PCB until the thermistor has been unplugged and checked against temperature. A thermistor short to earth can damage the main/controller PCB.

10. Pressure switch and pressure transducer testing

Use for E16 pressure switch/sensor error, E24 high pressure, E2F low pressure, discharge temperature issues, or abnormal pressure readings.

1
Power-on: pressure transducers use a 5V DC supply. Red to black should be 5V DC.
2
Return voltage is measured black to white. For discharge pressure, the return voltage is approximately equal to pressure in kPa x 1000 relationship used in training; for example 2.5V DC approx. 2500kPa.
3
Power-off and unplugged: use diode test. Confirm no wire is shorted to earth.
Diode testExpected
Black lead BLACK, red lead WHITE1.0V to 1.1V
Black lead BLACK, red lead RED1.2V to 1.3V
Black lead WHITE, red lead RED1.6V to 1.7V
Black lead WHITE, red lead BLACK0.6V to 0.7V
Black lead RED, red lead BLACK0.5V to 0.6V
Black lead RED, red lead WHITE0.6V to 0.7V
Earth to red/white/blackO/L
4
If pressure reading is not plausible, compare with gauges, refrigerant state, operating mode, valve position and known pressure limits before replacing sensor.

Jump to refrigeration / pressure protection flow

11. Electronic expansion valve (EEV) testing

Use for low pressure, high discharge temperature, poor performance, compressor temperature, EEV noise or suspected metering fault.

1
On power-up, listen/feel for EEV initialisation. The ARTC/AOTA service instruction states EEV initialisation drives 528 pulses toward closing under start-up/interval conditions.
2
Confirm EEV pulse range for these models: 50-480 pulses in cooling/dry and 40-480 pulses in heating. When compressor is stopped, the EEV is set at 480 pulses.
3
Power-off resistance test. Match the actual connector type. Always test each winding to earth for O/L and inspect corrosion under the coil.
EEV typeResistance check
5-wire 12V coilRed to white/orange/yellow/blue = 45-50Ω. Each wire to earth = O/L.
6-wire 12V coilRed to white/orange = 45-50Ω. Brown to yellow/blue = 45-50Ω. Each wire to earth = O/L.
4
If resistance is correct, check whether the coil is clipped firmly to the body and whether the valve body/strainer is restricted. Temperature difference across a strainer can indicate blockage.

Jump to low pressure/no cooling flow

12. Compressor testing

Use for E1A compressor location detection, IPM protection, no start, abnormal noise, trip, or stops soon after starting.

1
Power isolated: confirm compressor harness is tight, correctly connected and not open circuit.
2
Measure winding resistance between U-V, V-W and U-W. All three windings should be equal, normally approximately 1-2Ω around 20-25°C.
3
Insulation test from each winding to earth. Expected: greater than 1MΩ.
4
If resistance/insulation is normal but compressor stops soon after starting, confirm gas and liquid valves open, no refrigerant leak/undercharge, no strainer restriction and no oil/refrigerant circuit blockage before replacing compressor.
5
If the compressor is mechanically noisy, locked, or readings are abnormal, escalate for compressor replacement assessment and capture all readings/photos.

Jump to IPM protection | Jump to ticket evidence

13. IPM protection flow - E17

Use this section for E17 / IPM Protection. The IPM protection sheet identifies the detective actuators as the outdoor inverter PCB and compressor. It also flags connection failure, outdoor fan operation failure, outdoor heat exchanger clogging, compressor failure and inverter PCB failure.

Detection behaviour: when over-current flows in the inverter PCB, the compressor stops. If the same error repeats within 40 seconds after restart and repeats 5 times, the compressor stops permanently.

Important: Do not move straight to inverter PCB. Confirm airflow and fan motor first. A failed fan or blocked coil can drive the IPM protection fault.

14. IPM and diode bridge power-off tests

Use diode mode with power isolated and DC bus discharged. Disconnect control harnesses where required before testing PCB/inverter components.

IPM / TR PCB diode guide

TestExpected
Black lead P, red lead U/V/WApprox. 0.4V each
Black lead U/V/W, red lead NApprox. 0.4V each
Black lead P, red lead N0.7V to 0.9V
Black lead N, red lead PO/L

Three phase bridge rectifier guide

TestExpected
Power on AC inputL1-L2, L2-L3, L1-L3 = 415V AC
Power on phase to earth/neutralApprox. 240V AC
Power on DC output + to -Approx. 560-600V DC
Power off diode: black lead +, red lead AC1/AC2/AC3Approx. 0.4V each
Power off diode: black lead AC1/AC2/AC3, red lead -Approx. 0.4V each
Power off diode: black lead +, red lead -0.7V to 0.9V
Power off diode: black lead -, red lead +O/L
Safety: DC bus can remain charged after isolation. Confirm discharge before touching or unplugging inverter components.

15. No cooling / no heating / pressure protection flow

Use for poor performance, E0F discharge temperature, E2b compressor temperature, E24 high pressure, E2F low pressure or repeat protection stops.

Low pressure focus - E2F

Check valves open, outdoor ambient within range, outdoor fan and heat exchanger, EEV/strainer condition, low pressure sensor characteristics, solenoid valve operation and refrigerant quantity.

High pressure focus - E24

Check outdoor airflow, outdoor coil fouling, fan speed, installation clearances, short cycling/recirculation, overcharge, non-condensables and pressure sensor accuracy.

16. Defrost and heating-specific checks

Use where heating performance is questioned, outdoor fan stops in heating, defrost icon appears, or frosting is reported.

1
Confirm whether the unit is in normal defrost. Outdoor fan OFF and compressor control changes can be normal during defrost.
2
Defrost release is based on outdoor heat exchanger temperature over 10°C or compressor ON time over approximately 15-20 minutes.
3
During defrost flow in the service instruction, EEV and compressor speed are actively controlled. For AOTA72LALT, compressor defrost speed can be 70-95 rps; AOTA90LALT can be 100 rps. EEV values differ by model.
4
If defrost is excessive or incomplete, check outdoor thermistor seating/value, outdoor coil airflow, refrigerant charge, valve position and ambient/site conditions.

17. Drain pump and float switch

Use for water leak, drain fault, float switch activation, or indoor unit stops with drain-related symptoms.

1
Confirm drain pan, pump, hose, trap and fall are clear. Check safety drain path where fitted.
2
Confirm float switch wiring/connector is seated and not bridged incorrectly.
3
Confirm pump supply and operation. If pump runs but water remains, check blockage or incorrect drain installation.
4
Record whether the fault clears after drain pan is emptied and float returns to normal state.

18. Pump down reminder

Use only where pump down is authorised and safe. Follow the service instruction sequence exactly.

1
Confirm liquid and gas stop valves are fully open before beginning.
2
Hold PUMP DOWN button SW102 for over 3 seconds. Compressor and outdoor fan start automatically.
3
When display shows run, close liquid valve immediately.
4
When display changes to the next close prompt, close gas valve immediately.
5
When End displays, compressor and outdoor fan stop automatically after approximately 1 minute, then turn power off.
Error: If E98 pump down error appears, recover refrigerant from the service port rather than continuing pump down attempts.

19. Ticket evidence checklist

Required evidenceDetail to request
Model and serialIndoor and outdoor model/serial photos. Confirm ARTC72/90 with AOTA72/90.
Exact error evidencePhoto of wired remote error and outdoor 7-segment error. Include stored errors if multiple.
Power readingsL1-L2, L2-L3, L1-L3, phase-to-neutral/earth, DC bus + to -, fuse continuity.
Communication readingsIndoor signal value, outdoor signal value, test condition with signal wire disconnected.
Component test photosMeter readings for fan diode test, thermistors, pressure sensor, EEV coil, compressor resistance/insulation, IPM/bridge diode test.
Site and airflowPhotos of outdoor coil, clearances, obstructions, duct/filter/return air condition, indoor coil if accessible.
Refrigeration evidenceValve position, pressure readings, leak evidence, strainer temperature difference, recharge/vacuum details if performed.
DecisionState whether fault is wiring/site/refrigeration/component/PCB and what part is authorised.
Internal note: This article is designed for Freshdesk source view. Internal links are anchor links, so agents can jump directly to tests while on the phone.