Freshdesk Solution Article - Technical Support Step-by-Step Phone Instructions
1. Document scope
| Area | Details |
|---|---|
| Models covered | Indoor: ARTC72LATU / ARTC90LATU Outdoor: AOTA72LALT / AOTA90LALT |
| System type | R410A inverter ducted, 415V 50Hz three phase 4W outdoor supply, wired remote controller system. |
| Primary source material | ARTC72/90LATU Service Instruction, ARTC72/90LATU Service Manual, IPM Protection troubleshooting sheet, and Service Agent Training component testing material. |
| Purpose | Provide a phone-support workflow with clickable jump links so Technical Support can quickly move to a component test such as fan motor, thermistor, EEV, pressure sensor, compressor/IPM, or communication. |
2. Quick map
Use this section while speaking to the agent. The links jump directly to the test section.
| Symptom / error family | Most likely area | Jump to |
|---|---|---|
| E01 / E13 serial communication issues | Indoor/outdoor signal or wiring | Communication test |
| E00 wired remote controller error | Remote controller supply or Y1/Y2/Y3 signal | Remote signal test |
| E0A / E06 / E0C / E0E / E15 thermistor errors | Thermistor, wiring, connector, PCB return voltage | Thermistor testing |
| E16 pressure switch / pressure sensor error | Pressure transducer 5V supply, return voltage, diode check | Pressure sensor test |
| E17 IPM protection | Connection, airflow, outdoor fan, compressor, inverter PCB | IPM protection flow |
| E1b outdoor fan error | Outdoor DC fan motor, obstruction, feedback signal | Fan motor test |
| E19 inverter voltage protection | 415V AC input, DC bus, diode bridge, fuses, inverter board | Power checks / Diode bridge |
| E2F low pressure or no cooling/heating | Valves, refrigerant charge, EEV, strainer, airflow | No cooling/heating flow |
| Drain fault / water issue | Drain pump, float switch, drain restriction | Drain and float switch |
3. Error code quick reference
The wired remote controller and outdoor 7-segment display should be cross-checked. On the outdoor board, the ERROR lamp flashes rapidly; press ENTER to show the error content, then SELECT to scroll stored errors.
| Code | Fault | Priority test link |
|---|---|---|
| E01 | Serial error - reverse transfer | Serial communication |
| E13 | Serial error - forward transfer / indoor signal error | Serial communication |
| E00 | Wired remote controller error | Remote signal |
| E02 | Room temperature thermistor error | Thermistors |
| E04 | Indoor heat exchanger middle thermistor error | Thermistors |
| E06 | Outdoor heat exchanger outlet thermistor error | Thermistors |
| E0A | Outdoor temperature thermistor error | Thermistors |
| E0C | Outdoor discharge pipe thermistor error | Thermistors |
| E0E | Heat sink thermistor inverter error | Thermistors |
| E0F | Discharge temperature error | Refrigeration / airflow |
| E15 | Compressor thermistor error | Thermistors |
| E16 | Pressure switch / pressure sensor error | Pressure sensor |
| E17 | IPM protection | IPM protection |
| E1A | Compressor location detection error | Compressor |
| E1b | Outdoor fan error | Fan motor |
| E19 | Inverter voltage protection | Power / Diode bridge |
| E24 | Excessive high pressure protection on cooling | Airflow / heat exchanger |
| E2A | Power supply frequency detection error | Power checks |
| E2b | Compressor temperature error | Refrigeration / compressor temp |
| E2E | Inverter communication error | Power / Inverter PCB |
| E2F | Low pressure error | Low pressure flow |
| E34 / E37 | Indoor fan motor 1 or 2 lock / revolution error | Indoor fan motor |
| E38 / E39 | Indoor fan motor 1 or 2 driving circuit error | Indoor fan drive |
| E98 | Pump down error | Pump down |
| E99 | Indoor unit error condition | Check wired remote error and indoor PCB/communication |
4. Phone triage flow
5. Remote signal test
Use this where the wired remote controller is blank, has E00, intermittent control, or no response.
6. Indoor/outdoor serial communication test
Use for E01, E13, intermittent operation, or when either unit is not proving communication.
7. Power and DC bus checks
Use for no operation, E19 inverter voltage protection, inverter communication errors, no DC bus, no fan/compressor output, or repeated PCB failures.
Jump to diode bridge test | Jump to IPM test | Jump to fan motor test
8. DC fan motor testing - indoor and outdoor
Use for E1b, E34, E37, E38, E39, non-starting fan, fan hunting, overheat/high pressure faults or IPM protection where airflow is suspect.
| Test | Expected value |
|---|---|
| Red lead RED, black lead BLACK | O/L |
| Red lead WHITE, black lead BLACK | 0.5V to 1.8V, depending on motor generation |
| Black lead BLACK, red lead RED | 0.8V to 1.1V |
| Black lead BLACK, red lead WHITE | 0.4V to 0.6V |
9. Thermistor testing
Use for E02, E04, E06, E0A, E0C, E0E, E15 or any protection fault where sensor value drives control.
| Training reference at 20°C | Resistance / return voltage guide |
|---|---|
| Room temperature | Approx. 12.53kΩ / 2.21V |
| Indoor heat exchanger temperature | Approx. 62.90kΩ / 2.21V |
| Discharge temperature | Approx. 64.50kΩ / 0.83V |
| Compressor temperature | Approx. 62.55kΩ / 0.86V |
| Outdoor temperature | Approx. 12.64kΩ / 3.75V |
| Outdoor heat exchanger / liquid / suction style sensors | Approx. 6.10kΩ family, verify exact thermistor table for this model |
10. Pressure switch and pressure transducer testing
Use for E16 pressure switch/sensor error, E24 high pressure, E2F low pressure, discharge temperature issues, or abnormal pressure readings.
| Diode test | Expected |
|---|---|
| Black lead BLACK, red lead WHITE | 1.0V to 1.1V |
| Black lead BLACK, red lead RED | 1.2V to 1.3V |
| Black lead WHITE, red lead RED | 1.6V to 1.7V |
| Black lead WHITE, red lead BLACK | 0.6V to 0.7V |
| Black lead RED, red lead BLACK | 0.5V to 0.6V |
| Black lead RED, red lead WHITE | 0.6V to 0.7V |
| Earth to red/white/black | O/L |
11. Electronic expansion valve (EEV) testing
Use for low pressure, high discharge temperature, poor performance, compressor temperature, EEV noise or suspected metering fault.
| EEV type | Resistance check |
|---|---|
| 5-wire 12V coil | Red to white/orange/yellow/blue = 45-50Ω. Each wire to earth = O/L. |
| 6-wire 12V coil | Red to white/orange = 45-50Ω. Brown to yellow/blue = 45-50Ω. Each wire to earth = O/L. |
12. Compressor testing
Use for E1A compressor location detection, IPM protection, no start, abnormal noise, trip, or stops soon after starting.
13. IPM protection flow - E17
Use this section for E17 / IPM Protection. The IPM protection sheet identifies the detective actuators as the outdoor inverter PCB and compressor. It also flags connection failure, outdoor fan operation failure, outdoor heat exchanger clogging, compressor failure and inverter PCB failure.
Detection behaviour: when over-current flows in the inverter PCB, the compressor stops. If the same error repeats within 40 seconds after restart and repeats 5 times, the compressor stops permanently.
14. IPM and diode bridge power-off tests
Use diode mode with power isolated and DC bus discharged. Disconnect control harnesses where required before testing PCB/inverter components.
IPM / TR PCB diode guide
| Test | Expected |
|---|---|
| Black lead P, red lead U/V/W | Approx. 0.4V each |
| Black lead U/V/W, red lead N | Approx. 0.4V each |
| Black lead P, red lead N | 0.7V to 0.9V |
| Black lead N, red lead P | O/L |
Three phase bridge rectifier guide
| Test | Expected |
|---|---|
| Power on AC input | L1-L2, L2-L3, L1-L3 = 415V AC |
| Power on phase to earth/neutral | Approx. 240V AC |
| Power on DC output + to - | Approx. 560-600V DC |
| Power off diode: black lead +, red lead AC1/AC2/AC3 | Approx. 0.4V each |
| Power off diode: black lead AC1/AC2/AC3, red lead - | Approx. 0.4V each |
| Power off diode: black lead +, red lead - | 0.7V to 0.9V |
| Power off diode: black lead -, red lead + | O/L |
15. No cooling / no heating / pressure protection flow
Use for poor performance, E0F discharge temperature, E2b compressor temperature, E24 high pressure, E2F low pressure or repeat protection stops.
Low pressure focus - E2F
Check valves open, outdoor ambient within range, outdoor fan and heat exchanger, EEV/strainer condition, low pressure sensor characteristics, solenoid valve operation and refrigerant quantity.
High pressure focus - E24
Check outdoor airflow, outdoor coil fouling, fan speed, installation clearances, short cycling/recirculation, overcharge, non-condensables and pressure sensor accuracy.
16. Defrost and heating-specific checks
Use where heating performance is questioned, outdoor fan stops in heating, defrost icon appears, or frosting is reported.
17. Drain pump and float switch
Use for water leak, drain fault, float switch activation, or indoor unit stops with drain-related symptoms.
18. Pump down reminder
Use only where pump down is authorised and safe. Follow the service instruction sequence exactly.
19. Ticket evidence checklist
| Required evidence | Detail to request |
|---|---|
| Model and serial | Indoor and outdoor model/serial photos. Confirm ARTC72/90 with AOTA72/90. |
| Exact error evidence | Photo of wired remote error and outdoor 7-segment error. Include stored errors if multiple. |
| Power readings | L1-L2, L2-L3, L1-L3, phase-to-neutral/earth, DC bus + to -, fuse continuity. |
| Communication readings | Indoor signal value, outdoor signal value, test condition with signal wire disconnected. |
| Component test photos | Meter readings for fan diode test, thermistors, pressure sensor, EEV coil, compressor resistance/insulation, IPM/bridge diode test. |
| Site and airflow | Photos of outdoor coil, clearances, obstructions, duct/filter/return air condition, indoor coil if accessible. |
| Refrigeration evidence | Valve position, pressure readings, leak evidence, strainer temperature difference, recharge/vacuum details if performed. |
| Decision | State whether fault is wiring/site/refrigeration/component/PCB and what part is authorised. |