Applies To

Double skin packaged rooftop package units using the Danfoss MCX controller platform.

Reference variable list:

UNICO_v1.05.00_rev01_FG-000022-ID10.mcxs

This variable list is for the double skin rooftop package unit project reference FG-000022 and shows Modbus-related parameters, status variables, alarms and I/O addresses. 


Purpose

This article provides a practical guide for service, controls and BMS integration teams when using the Modbus variable list for double skin rooftop package units.

It explains:

  • How the variable list is structured
  • Which addresses are commonly required for BMS integration
  • Which values are read-only and which are read/write
  • Key unit status, setpoint, alarm and I/O points
  • Information to collect before escalating a Modbus or BMS issue

Important Notes

The attached Modbus variable list contains factory-level parameters and status variables. Do not change writable parameters unless the adjustment has been approved by Fujitsu General technical support or the equipment supplier.

Incorrect Modbus writes may affect unit operation, safety logic, compressor staging, fan control, defrost operation, setpoints or alarm behaviour.


Variable List Structure

The table is arranged with the following columns:

ColumnMeaning
LABELShort variable code used by the controller
DESCRIPTIONDescription of the parameter, status or alarm
MIN / MAXPermitted operating range
VALUE/TYPEDefault value or enum type
UNITEngineering unit, where applicable
RWRead/write status
ADUModbus address/register reference

The list includes both writable configuration parameters and read-only live values. Writable items are marked RW, while live status, alarms and I/O feedback are generally marked Read


Modbus Communication Settings

The Modbus communication settings are located under General > Serial Settings.

LabelDescriptionDefault / ValueADU
SErSerial address, Modbus107311
bAUSerial baud rate, Modbus192007312
COMSerial format, Modbus8N17313

The external Modbus gateway settings are listed under General > Modbus Gateway.

LabelDescriptionDefault / ValueADU
XC0External communication enableAuto7314
XC1External communication baud rate192007315
XC2External communication settings8N17316

For BMS integration, confirm the controller serial address, baud rate and serial format match the BMS configuration. 


Common Writable Control Points

The following points are commonly used for BMS enable/disable, setpoint and mode control.

LabelDescriptionRangeUnitAccessADU
y01System ON/OFF0–1EnumRW8398
y03System heat/cool0–1EnumRW8400
SC1Cooling temperature setpointSCL–SCH°CRW8261
SH1Heating temperature setpointSHL–SHH°CRW8264
SPrRemote setpoint enable0–1EnumRW7094
Er1Maximum power in demand limit0–100%RW7095

The variable list shows y01 as the System ON/OFF command, y03 as the System heat/cool command, and SC1/SH1 as the cooling and heating temperature setpoints. 


Setpoint Limits

The setpoint limits define the allowable range for cooling and heating setpoints.

LabelDescriptionDefaultUnitADU
SCLMinimum setpoint limit in cooling15.0°C7081
SCHMaximum setpoint limit in cooling30.0°C7082
SHLMinimum setpoint limit in heating15.0°C7084
SHHMaximum setpoint limit in heating40.0°C7085

If the BMS cannot write a setpoint, confirm the requested value is within the configured minimum and maximum limits.


Key Read-Only Unit Status Points

The main unit overview is located under Status var > Chiller Overview.

LabelDescriptionUnit / TypeAccessADU
A01Alarm notificationEnumRead16387
A02On/Off statusEnumRead16388
A03Compressor statusEnumRead16389
A10Remote ON/OFFEnumRead16398
A11Defrost statusEnumRead16399
A12Cool/Heat modeEnumRead16400
A13Control probe°CRead16480
A14Actual setpoint°CRead16481
A15Requested power%Read16484
A16Actual power%Read16485

These are the preferred points for basic BMS monitoring of unit state, operating mode, demand and actual output. 


Compressor Monitoring

The variable list provides individual compressor status, run hours and start counters.

Compressor Status

LabelDescriptionAccessADU
c01Compressor 1 Circuit 1 statusRead16417
c02Compressor 2 Circuit 1 statusRead16418
c03Compressor 3 Circuit 1 statusRead16419
c07Compressor 1 Circuit 2 statusRead16423
c08Compressor 2 Circuit 2 statusRead16424

The attached rooftop package unit configuration includes compressor variables for up to six compressors per circuit; however, not every compressor variable will apply to every unit size or configuration. 

Compressor Run Hours

LabelDescriptionUnitAccessADU
c0aCompressor 1 Circuit 1 hourshRead16801
c0bCompressor 2 Circuit 1 hourshRead16803
c0cCompressor 3 Circuit 1 hourshRead16805

Run hours are useful for service planning, compressor rotation checks and fault investigation.


Rooftop Status Variables

The rooftop-specific status points are listed under Status var > Rooftop.

LabelDescriptionUnit / TypeAccessADU
RS00Supply damper on/offEnumRead17001
RS01Supply fan on/offEnumRead17002
RS02Supply fan speed%Read17003
RS03External damper on/offEnumRead17004
RS04External damper position%Read17005
RS05Return fan on/offEnumRead17006
RS06Return fan speed%Read17007
R023Free cooling demand%Read17024
R024Free heating demand%Read17025
R026Air quality demand%Read17027

For rooftop package units, these are useful BMS points for confirming fan demand, damper status and economiser/free-cooling activity. 


Supply Fan Parameters

Supply fan setup parameters are located under Supply Fan > Setup.

LabelDescriptionDefaultUnitAccessADU
SF0Regulation typeFIXEnumRW7317
SF1Minimum speed10.0%RW7318
SF2Maximum speed75.0%RW7319
SF3Time at maximum speed at startup0sRW7320
SF6Enable supply damperTIMEEnumRW7323
SF7Fan delay after damper60sRW7324
SF8Fan delay at OFF60secRW7325

The variable list confirms SF2 Maximum speed is set to 75% by default, matching the fan speed note shown in the wiring information. 


External Damper / Economiser Parameters

External damper control is listed under External Damper > Configuration and related free-cooling/free-heating sections.

LabelDescriptionDefaultUnitADU
dE0Enable FreeCoolHeatingNOEnum7346
dE1Minimum opening20.0%7347
dE2Maximum opening100.0%7528
sC0Summer free-cooling enableYESEnum7350
wH0Winter free-heating enableYESEnum7355
wC0Winter free-cooling enableYESEnum7365

These points may only be relevant where the unit is fitted with the applicable damper, economiser or air quality options.


Alarm Monitoring

Alarms are shown in the ALARMS section. The alarm list includes the label, description, reset type, whether the alarm is active when the unit is off, and the associated Modbus ADU and bit reference.

Common Alarm Registers

Alarm TypeExamplesADU
General / phase / high pressure / low pressure alarmsA01, A02, AH1, AL120481–20482
Compressor protection alarmsAC1, C01, C02, C0320482–20483
Fan protection alarmsA60, A61, AF1, AF220483–20484
Probe and sensor alarmsP05, P14, P21, P23, P2420485–20486
Network and communication alarmsN01, N02, N03–N1020488–20489
Rooftop-specific alarmsSFA, RFA, SFL, FIR, SFW20491–20492

The alarm table indicates that alarms are mapped as individual bits within ADU registers, such as 20481 .08, 20482 .11, and similar. This means the BMS may need to read the register and decode the relevant bit, depending on the integration platform. 


Common Rooftop-Specific Alarms

LabelDescriptionResetADU / Bit
SFASupply fan alarmManual20491 .06
RFAReturn fan alarmManual20491 .07
SFSSupply fan safety switchAuto20492 .12
FIRFire/smoke alarmManual20492 .13
SFWSupply flow320492 .14
SFLSupply filterAuto20492 .15
FR1Frost alarm Circuit 1Auto20492 .00
FR2Frost alarm Circuit 2Auto20492 .01

These are key points for service diagnostics where the complaint relates to airflow, filter pressure, fire trip, fan failure or frost protection.


I/O Configuration

The last pages of the variable list show physical I/O mappings.

Analogue Inputs

InputDescriptionSignal TypeUnitADU
AI1Return temperatureNTC-10K°C21804
AI2Outdoor temperatureNTC-10K°C21768
AI3Suction pressure Circuit 14–20 mAbarg21775
AI5Discharge pressure Circuit 14–20 mAbarg21766
AI12Variable setpoint0–10 V21769
AI16Supply temperatureNTC-10K°C21803

Digital Inputs

InputDescriptionContact TypeADU
DI1Remote ON/OFFN.C.21309
DI3High pressure switch Circuit 1N.C.21299
DI7Protection Compressor 1 Circuit 1N.C.21253
DI8Protection Compressor 2 Circuit 1N.C.21254
DI11Protection Compressor 3 Circuit 1N.C.21255
DI15Supply filterN.C.21335
DI17Phases/voltage statusN.C.21311
DI18Remote cooling/heatingN.C.21314
DI19Protection fansN.C.21287
DI20Demand limitN.O.21315
DI21Supply fan alarmN.C.21326
DI22Unit second setpointN.O.21310

Analogue Outputs

OutputDescriptionSignalADU
AO1Sink/source side regulation value 10–10 V22018
AO3Supply fan0–10 V22026

Digital Outputs

OutputDescriptionContact TypeADU
DO2Compressor 1 Circuit 1N.O.21506
DO3Compressor 2 Circuit 1N.O.21507
DO4Supply damperN.O.21571
DO6Compressor 3 Circuit 1N.O.21508
DO10Four-way valve Circuit 1N.C.21536
DO12Supply fanN.O.21568
DO13Sink/source side regulation enable 1N.O.21532
DO14General alarmN.O.21534
DO20Operating statusN.O.21567

These I/O points are useful when cross-checking controller status against field wiring and the electrical schematic. 


BMS Integration Recommendations

When integrating to BMS:

  1. Confirm the fitted communication option from the model code and wiring diagram.
  2. Confirm whether the site is using Modbus RTU or another protocol gateway.
  3. Confirm Modbus address, baud rate and parity settings.
  4. Agree which points are monitoring-only and which points are writable.
  5. Avoid writing to factory parameters unless approved.
  6. Use status variables for monitoring rather than physical I/O where possible.
  7. For alarms, confirm whether the BMS can decode individual bits within alarm registers.
  8. Validate all values on site against the controller display before handover.

Recommended Minimum BMS Point List

For most projects, the following minimum point list is recommended:

PurposeRecommended Variables
Unit enable/statusy01, A02, A10
Modey03, A12
SetpointSC1, SH1, A14
Control temperatureA13
Demand/outputA15, A16
Alarm statusA01 plus alarm bit registers
Compressor statusA03, c01, c02, c03
Fan statusRS01, RS02
Damper statusRS00, RS03, RS04
Filter/fan alarmsSFA, SFS, SFL
Communication settingsSEr, bAU, COM

Troubleshooting

IssueChecks
BMS cannot communicateConfirm Modbus address, baud rate, parity, wiring polarity, shield and termination
Values are incorrectConfirm register type, scaling, signed/unsigned format and whether the BMS is offsetting register numbers
BMS cannot write ON/OFFConfirm write access, controller mode, remote enable configuration and whether local controls are overriding BMS
Setpoint write rejectedConfirm setpoint is within SCL/SCH or SHL/SHH limits
Alarm not matching displayConfirm BMS is decoding the correct ADU and bit position
Fan command present but fan not runningCheck RS01/RS02, supply fan alarm, supply flow alarm and physical fan enable/output
Unit enabled but compressors not startingCheck requested power, compressor status, active alarms, safety chain and anti-short-cycle timers

Escalation Information to Collect

When escalating a Modbus or BMS issue, provide:

  • Full model number
  • Serial number
  • Variable list file name and revision
  • Controller software version, if available
  • BMS protocol and hardware details
  • Modbus address, baud rate and parity
  • Register map used by the BMS contractor
  • Screenshot/export of BMS point configuration
  • Photos of communication wiring and controller terminals
  • Active alarm list from the controller display
  • Values read from key points such as A02, A12, A13, A14, A15, A16 and A01