General Assist Technical Reference

TWH.581.TTJ - Compressor Sweating

Low-load operation, evaporator refrigerant level and diagnostic checks
Applies to TWH.581.TTJ low-load chiller units, including 600 kW applications
Issue / symptom: Visible condensation or sweating on the compressor body or suction area during operation, particularly after extended running or during low thermal load conditions.
Key check: Before changing refrigerant charge or control settings, confirm the chiller is operating within its intended working range. Excessive compressor sweating may indicate liquid refrigerant return or an evaporator refrigerant level that is too high.

1. Background

Some compressor sweating can occur depending on the chiller operating conditions. However, excessive sweating may indicate that the compressor is drawing in liquid refrigerant or that the evaporator refrigerant level is too high.

Factory advice is to first confirm that the chiller is operating within its intended working range before making any refrigerant or control adjustments.

2. Checks Required

Before adjusting refrigerant charge or controls, verify the following:

CheckRequirement
Chilled water flowConfirm flow rate is within specification.
Water temperaturesConfirm entering and leaving water temperatures are within the expected operating range.
Thermal loadConfirm the unit is operating under a suitable site load.
Compressor operationConfirm stable operation and check for excessive start/stop cycling.
Refrigerant chargeConfirm the correct charge, especially for units supplied NI / without refrigerant.
Evaporator sight glassConfirm refrigerant level is within the acceptable range.

3. Important Refrigerant Level Guideline

Maximum level: The refrigerant level in the evaporator must not exceed 50% of the sight glass indicator.

If the level is above 50%, refrigerant may need to be removed. Use the reference image below as a guide; the red line indicates the approximate maximum acceptable level.

Evaporator sight glass refrigerant level reference

4. Likely Causes

  • Evaporator refrigerant level is too high.
  • The unit is overcharged with refrigerant.
  • The unit is operating under low thermal load.
  • Compressors are starting and stopping frequently.
  • The chiller is not reaching steady-state operating conditions.
  • Evaporator refrigerant level control becomes unstable under low-load operation.

5. Notes on Low Thermal Load Operation

TT units are not ideal for very low thermal load operation.

When the thermal load is low, the compressors may frequently start and stop. This can prevent the unit from reaching steady-state conditions and may result in sub-optimal evaporator refrigerant level control.

Where this occurs, compressor response should be stabilised according to the actual site load. Factory support may be able to optimise some control algorithm parameters during site attendance.

6. Recommended Action

  1. Confirm operating conditions. Check water flow, entering/leaving water temperatures, site load and whether one or both compressors are sweating.
  2. Check refrigerant charge. Confirm the correct refrigerant quantity was charged during commissioning, particularly for NI / uncharged units.
  3. Inspect the evaporator sight glass. Confirm the level does not exceed 50% of the sight glass.
  4. Remove refrigerant if required. If the level is above 50%, recover refrigerant until the level is within the acceptable range. This must be performed by appropriately qualified personnel.
  5. Monitor compressor operation. Check for frequent cycling and confirm whether the chiller can reach stable operating conditions.
  6. Escalate if the issue remains. If sweating continues after confirming operating range and refrigerant level, escalate to factory / GI technical support. Control parameter optimisation may be required under low-load conditions.
Important: Do not remove refrigerant solely because a compressor is sweating. Confirm operating conditions, site load, refrigerant charge and evaporator level first.
General Assist Technical Reference