VRF Indoor Unit Controller Compatibility

Purpose: Use this reference to confirm which wired, simple, wireless and external controllers can be connected to the listed VRF indoor unit models.

Important: A Conditional result means an additional receiver/interface may be required or a controller type may be restricted. Always read the Notes column before installation.

Compatibility Key

YesController can be connected as listed.
ConditionalAdditional hardware or model-specific restrictions apply. Refer to Notes.
NoController is not compatible.

Controller Families

  • Touch Panel Wired Remote: UTY-RNRYZ2 / UTY-RNRYZ1 / UTY-RNRY
  • Wired Remote: UTY-RNKYT
  • Simple Remote: UTY-RSRY / UTY-RHRY / UTY-RSKYT / UTY-RHKYT
  • Wireless Remote: UTY-LNHY
  • External Switch Controller: UTY-TERX / UTY-TEKX

Indoor Unit Compatibility Matrix

Indoor Unit TypeIndoor Model CodesTouch Panel Wired
UTY-RNRYZ2 / Z1 / RNRY
Wired Remote
UTY-RNKYT
Simple Remote
UTY-RSRY / RHRY / RSKYT / RHKYT
Wireless Remote
UTY-LNHY
External Switch
UTY-TERX / TEKX
Notes
Compact CassetteAUXB07GALH, AUXB09GALH, AUXB12GALH, AUXB14GALH, AUXB18GALH, AUXB24GALHYesYesYesYesYesFully compatible across all listed controller types.
CassetteAUXD18GALH, AUXD24GALH, AUXA18GALH, AUXA24GALH, AUXA30GALH, AUXA34GALH, AUXA36GALH, AUXA45GALH, AUXA54GALHYesYesYesConditionalYesWireless requires IR Receiver Unit UTY-LRHYB1.
Circular Flow CassetteAUXM018GLAH, AUXM024GLAH, AUXM030GLAH, AUXK018GLAH, AUXK024GLAH, AUXK030GLAH, AUXK034GLAH, AUXK036GLAH, AUXK045GLAH, AUXK054GLAHYesNoConditionalConditionalConditionalPolar 3-wire controllers cannot be connected. Wireless requires UTY-LBHXD.
Low Static Pressure Duct / Concealed FloorARXB07GALH, ARXB09GALH, ARXB12GALH, ARXB14GALH, ARXB18GALHYesYesYesConditionalYesWireless requires UTB-TWC.
Mini DuctARXK07GCLH, ARXK07GALH, ARXK09GCLH, ARXK09GALH, ARXK12GCLH, ARXK12GALH, ARXK14GCLH, ARXK14GALH, ARXK18GCLH, ARXK18GALH, ARXK24GCLH, ARXK24GALHYesYesYesConditionalYesWireless requires UTB-TWC.
Slim Duct / Slim Concealed FloorARXD07GALH, ARXD09GALH, ARXD12GALH, ARXD14GALH, ARXD18GALH, ARXD24GALHYesYesYesConditionalYesWireless requires UTB-TWC.
Low Static Pressure DuctARXB24GALH, ARXB30GALH, ARXB36GALH, ARXB45GALHYesYesYesConditionalYesWireless requires UTB-TWC.
Medium Static Pressure DuctARXA24GALH, ARXA30GALH, ARXA36GALH, ARXA45GALH, ARXA24GBLH, ARXA30GBLH, ARXA36GBLH, ARXA45GBLHYesYesYesConditionalYesWireless requires UTB-TWC.
High Static Pressure DuctARXC36GATH, ARXC45GATH, ARXC60GATH, ARXC72GATH, ARXC90GATH, ARXC96GATH, ARXC36GBTHYesYesYesConditionalYesWireless requires UTB-TWC.
Compact FloorAGYA007GCAH, AGYA009GCAH, AGYA012GCAH, AGYA014GCAHYesNoConditionalYesConditionalPolar 3-wire controllers cannot be connected.
Compact Floor (EEV external)AGYE007GCAH, AGYE009GCAH, AGYE012GCAH, AGYE014GCAHYesNoConditionalYesConditionalSame controller logic as Compact Floor.
Floor / CeilingABYA12GATH, ABYA14GATH, ABYA18GATH, ABYA24GATHYesYesYesYesYesFully compatible across all listed controller types.
CeilingABYA30GATH, ABYA36GATH, ABYA45GATH, ABYA54GATHYesYesYesYesYesFully compatible across all listed controller types.
Wall MountedASYA007GTAH, ASYA009GTAH, ASYA07GACH, ASYA09GACH, ASYA12GACH, ASYA14GACH, ASYA18GACH, ASYA24GACH, ASYA30GACH, ASYA18GBCH, ASYA24GBCHYesConditionalConditionalYesConditionalWired remote is not connectable with indoor unit AS*****GTAH.
Wall Mounted (EEV external)ASYE007GTAH, ASYE009GTAH, ASYE07GACH, ASYE09GACH, ASYE12GACH, ASYE14GACHYesConditionalConditionalYesConditionalSame wall-mounted controller restrictions apply.

Key Compatibility Notes

  • UTB-TWC: Required for wireless control on the listed ducted indoor units.
  • UTY-LRHYB1: Required for wireless control on the listed Cassette models.
  • UTY-LBHXD: Required for wireless control on Circular Flow Cassette models.
  • Polar 3-wire controllers: Cannot be connected to Circular Flow Cassette or Compact Floor models where specifically noted.
  • AS*****GTAH wall-mounted units: Wired remote restrictions apply; check the exact model before selecting the controller.

Technician tip: Confirm the complete indoor model number before ordering or connecting a controller. Similar-looking indoor units can use different controller interfaces.