Specifications - ARTH54KHTA (Indoor) & AOTH54KBTA (Outdoor)
This article provides the technical specifications for the ARTH54KHTA indoor unit and its corresponding AOTH54KBTA outdoor unit.
Quick Answer
Matched system: ARTH54KHTA indoor unit with AOTH54KBTA outdoor unit.
| Indoor unit model | ARTH54KHTA |
| Outdoor unit model | AOTH54KBTA |
| Power supply | Single phase, 220-240 V, 50 Hz |
| Cooling capacity | 14.0 kW |
| Heating capacity | 15.5 kW |
| EER | 3.02 kW/kW |
| COP | 3.52 kW/kW |
| Indoor dimensions (H x W x D) | 425 x 1,250 x 490 mm |
| Outdoor dimensions (H x W x D) | 998 x 940 x 320 mm |
| Refrigerant | R32 |
| Factory refrigerant charge | 2,700 g |
| Additional charge | 40 g per meter over 30 m |
| Maximum piping length | 50 m |
| Maximum piping height | 30 m |
| Static pressure range | 60 to 260 Pa |
Model Mapping
- Indoor unit model: ARTH54KHTA
- Outdoor unit model: AOTH54KBTA
- These two units operate as a matched system.
Electrical Specifications
- Power supply: Single phase
- Voltage: 220-240 V
- Frequency: 50 Hz
- Available voltage range: 198-264 V
Cooling Performance (ARTH54KHTA)
- Cooling capacity: 14.0 kW
- Cooling capacity range: 4.5-15.0 kW
- Power consumption (cooling): 4.64 kW
- Maximum power consumption (cooling): 5.17 kW
- Energy Efficiency Ratio (EER): 3.02 kW/kW
- Rated operating current: 20.4 A
- Maximum operating current: 29.5 A
- Sensible capacity: 12.85 kW
- Power factor: 98.9%
- Moisture removal: 1.6 L/h
Direct answer: The EER of ARTH54KHTA is 3.02 kW/kW.
Heating Performance (ARTH54KHTA)
- Heating capacity: 15.5 kW
- Heating capacity range: 4.7-18.0 kW
- Power consumption (heating): 4.40 kW
- Maximum power consumption (heating): 5.23 kW
- Coefficient of Performance (COP): 3.52 kW/kW
- Rated operating current: 19.3 A
- Maximum operating current: 29.5 A
- Power factor: 99.1%
Compressor & Refrigerant Details
- Compressor type: DC twin rotary
- Motor output: 2,180 W
- Compressor design: Twin rotary
- Compressor model: Not specified in the manual
- Compressor weight: Not specified in the manual
- Refrigerant type: R32
- Factory charge: 2,700 g
- Additional charge rate: 40 g per meter
- Pre-charge length: 30 m
- Maximum piping length: 50 m
- Maximum piping height: 30 m
- Refrigerant oil type: RmM68AF
- Refrigerant oil amount: 800 cm³
Fan Motor, Speed & Airflow
- Indoor fan type: Sirocco fan x 2
- Indoor fan motor output: 197 W
- Static pressure range: 60 to 260 Pa
- Indoor airflow - cooling:
- High: 3,550 m³/h
- Medium: 3,010 m³/h
- Low: 2,480 m³/h
- Indoor airflow - heating:
- High: 3,550 m³/h
- Medium: 3,010 m³/h
- Low: 2,480 m³/h
- Outdoor fan type: Propeller fan x 1
- Outdoor fan motor output: 120 W
- Outdoor airflow:
- Cooling: 4,450 m³/h
- Heating: 4,450 m³/h
Noise Levels
- Indoor unit noise - cooling:
- High: 45 dB(A)
- Medium: 40 dB(A)
- Low: 36 dB(A)
- Indoor unit noise - heating:
- High: 45 dB(A)
- Medium: 40 dB(A)
- Low: 36 dB(A)
- Indoor sound power level, cooling high: 67 dB(A)
- Outdoor unit noise:
- Cooling: 55 dB(A)
- Heating: 57 dB(A)
- Sound power level: 72 dB(A)
Dimensions & Weight
- Indoor unit dimensions (H x W x D): 425 x 1,250 x 490 mm
- Indoor unit gross dimensions (H x W x D): 490 x 1,440 x 655 mm
- Indoor unit weight: 53 kg (net) / 61 kg (gross)
- Outdoor unit dimensions (H x W x D): 998 x 940 x 320 mm
- Outdoor unit gross dimensions (H x W x D): 1,176 x 1,027 x 445 mm
- Outdoor unit weight: 67 kg (net) / 76 kg (gross)
Pipe Connection Details
- Liquid pipe size: Ø9.52 mm (3/8 in.)
- Gas pipe size: Ø15.88 mm (5/8 in.)
- Connection method: Flare
- Indoor drain hose size: Ø25 mm I.D. / Ø32 mm O.D.
- Outdoor drain hose size: Ø13.0 mm I.D. / Ø16.0 to Ø16.7 mm O.D.
Operating Range
- Indoor cooling operating range: 18 to 32°C
- Indoor cooling humidity limit: 80% RH or less
- Indoor heating operating range: 16 to 30°C
- Outdoor cooling operating range: -10 to 50°C
- Outdoor heating operating range: -15 to 24°C
Direct Answers to Common Questions
- What is the cooling capacity of ARTH54KHTA? 14.0 kW.
- What is the heating capacity of ARTH54KHTA? 15.5 kW.
- What is the EER of ARTH54KHTA? 3.02 kW/kW.
- What is the COP of ARTH54KHTA? 3.52 kW/kW.
- What refrigerant does this system use? R32.
- Does this system support a 50 m pipe run? Yes.
- What is the additional refrigerant charge? 40 g per meter over 30 m.
- What is the maximum piping height? 30 m.