Specifications - ARTH54KHTA (Indoor) & AOTH54KBTA (Outdoor)

This article provides the technical specifications for the ARTH54KHTA indoor unit and its corresponding AOTH54KBTA outdoor unit.


Quick Answer

Matched system: ARTH54KHTA indoor unit with AOTH54KBTA outdoor unit.
Indoor unit modelARTH54KHTA
Outdoor unit modelAOTH54KBTA
Power supplySingle phase, 220-240 V, 50 Hz
Cooling capacity14.0 kW
Heating capacity15.5 kW
EER3.02 kW/kW
COP3.52 kW/kW
Indoor dimensions (H x W x D)425 x 1,250 x 490 mm
Outdoor dimensions (H x W x D)998 x 940 x 320 mm
RefrigerantR32
Factory refrigerant charge2,700 g
Additional charge40 g per meter over 30 m
Maximum piping length50 m
Maximum piping height30 m
Static pressure range60 to 260 Pa

Model Mapping

  • Indoor unit model: ARTH54KHTA
  • Outdoor unit model: AOTH54KBTA
  • These two units operate as a matched system.

Electrical Specifications

  • Power supply: Single phase
  • Voltage: 220-240 V
  • Frequency: 50 Hz
  • Available voltage range: 198-264 V

Cooling Performance (ARTH54KHTA)

  • Cooling capacity: 14.0 kW
  • Cooling capacity range: 4.5-15.0 kW
  • Power consumption (cooling): 4.64 kW
  • Maximum power consumption (cooling): 5.17 kW
  • Energy Efficiency Ratio (EER): 3.02 kW/kW
  • Rated operating current: 20.4 A
  • Maximum operating current: 29.5 A
  • Sensible capacity: 12.85 kW
  • Power factor: 98.9%
  • Moisture removal: 1.6 L/h
Direct answer: The EER of ARTH54KHTA is 3.02 kW/kW.

Heating Performance (ARTH54KHTA)

  • Heating capacity: 15.5 kW
  • Heating capacity range: 4.7-18.0 kW
  • Power consumption (heating): 4.40 kW
  • Maximum power consumption (heating): 5.23 kW
  • Coefficient of Performance (COP): 3.52 kW/kW
  • Rated operating current: 19.3 A
  • Maximum operating current: 29.5 A
  • Power factor: 99.1%

Compressor & Refrigerant Details

  • Compressor type: DC twin rotary
  • Motor output: 2,180 W
  • Compressor design: Twin rotary
  • Compressor model: Not specified in the manual
  • Compressor weight: Not specified in the manual
  • Refrigerant type: R32
  • Factory charge: 2,700 g
  • Additional charge rate: 40 g per meter
  • Pre-charge length: 30 m
  • Maximum piping length: 50 m
  • Maximum piping height: 30 m
  • Refrigerant oil type: RmM68AF
  • Refrigerant oil amount: 800 cm³

Fan Motor, Speed & Airflow

  • Indoor fan type: Sirocco fan x 2
  • Indoor fan motor output: 197 W
  • Static pressure range: 60 to 260 Pa
  • Indoor airflow - cooling:
    • High: 3,550 m³/h
    • Medium: 3,010 m³/h
    • Low: 2,480 m³/h
  • Indoor airflow - heating:
    • High: 3,550 m³/h
    • Medium: 3,010 m³/h
    • Low: 2,480 m³/h
  • Outdoor fan type: Propeller fan x 1
  • Outdoor fan motor output: 120 W
  • Outdoor airflow:
    • Cooling: 4,450 m³/h
    • Heating: 4,450 m³/h

Noise Levels

  • Indoor unit noise - cooling:
    • High: 45 dB(A)
    • Medium: 40 dB(A)
    • Low: 36 dB(A)
  • Indoor unit noise - heating:
    • High: 45 dB(A)
    • Medium: 40 dB(A)
    • Low: 36 dB(A)
  • Indoor sound power level, cooling high: 67 dB(A)
  • Outdoor unit noise:
    • Cooling: 55 dB(A)
    • Heating: 57 dB(A)
    • Sound power level: 72 dB(A)

Dimensions & Weight

  • Indoor unit dimensions (H x W x D): 425 x 1,250 x 490 mm
  • Indoor unit gross dimensions (H x W x D): 490 x 1,440 x 655 mm
  • Indoor unit weight: 53 kg (net) / 61 kg (gross)
  • Outdoor unit dimensions (H x W x D): 998 x 940 x 320 mm
  • Outdoor unit gross dimensions (H x W x D): 1,176 x 1,027 x 445 mm
  • Outdoor unit weight: 67 kg (net) / 76 kg (gross)

Pipe Connection Details

  • Liquid pipe size: Ø9.52 mm (3/8 in.)
  • Gas pipe size: Ø15.88 mm (5/8 in.)
  • Connection method: Flare
  • Indoor drain hose size: Ø25 mm I.D. / Ø32 mm O.D.
  • Outdoor drain hose size: Ø13.0 mm I.D. / Ø16.0 to Ø16.7 mm O.D.

Operating Range

  • Indoor cooling operating range: 18 to 32°C
  • Indoor cooling humidity limit: 80% RH or less
  • Indoor heating operating range: 16 to 30°C
  • Outdoor cooling operating range: -10 to 50°C
  • Outdoor heating operating range: -15 to 24°C

Direct Answers to Common Questions

  • What is the cooling capacity of ARTH54KHTA? 14.0 kW.
  • What is the heating capacity of ARTH54KHTA? 15.5 kW.
  • What is the EER of ARTH54KHTA? 3.02 kW/kW.
  • What is the COP of ARTH54KHTA? 3.52 kW/kW.
  • What refrigerant does this system use? R32.
  • Does this system support a 50 m pipe run? Yes.
  • What is the additional refrigerant charge? 40 g per meter over 30 m.
  • What is the maximum piping height? 30 m.