Quick Answer
  • Indoor unit model: ARTH30KHTA
  • Outdoor unit model: AOTH30KBTA
  • Matched system: Yes
  • Power supply: Single phase, 220-240 V, 50 Hz
  • Cooling capacity: 8.5 kW
  • Heating capacity: 10.0 kW
  • EER: 3.62 kW/kW
  • COP: 4.26 kW/kW
  • Indoor dimensions (H x W x D): 400 x 1,050 x 500 mm
  • Outdoor dimensions (H x W x D): 788 x 940 x 320 mm
  • Refrigerant type: R32
  • Factory refrigerant charge: 1,900 g
  • Additional refrigerant charge: 40 g per metre over 30 m
  • Maximum piping length: 50 m
  • Maximum piping height: 30 m
  • Static pressure range: 60 to 210 Pa

Model Mapping

ComponentModel
Indoor UnitARTH30KHTA
Outdoor UnitAOTH30KBTA
SystemMatched system

Electrical Specifications

  • Power supply: Single phase
  • Voltage: 220-240 V
  • Frequency: 50 Hz
  • Available voltage range: 198-264 V

Cooling Performance

ItemSpecification
Cooling capacity8.5 kW
Capacity range2.8-10.3 kW
Power consumption2.35 kW
Maximum power consumption3.47 kW
EER3.62 kW/kW
Rated operating current10.4 A
Maximum operating current22.6 A
Sensible capacity8.43 kW
Power factor98.2%
Moisture removal0.1 L/h

Heating Performance

ItemSpecification
Heating capacity10.0 kW
Capacity range2.7-11.3 kW
Power consumption2.35 kW
Maximum power consumption4.12 kW
COP4.26 kW/kW
Rated operating current10.4 A
Maximum operating current22.6 A
Power factor98.2%

Compressor & Refrigerant Details

  • Compressor type: DC twin rotary
  • Motor output: 1,500 W
  • Compressor design: Twin rotary
  • Compressor model: Not specified in the manual
  • Compressor weight: Not specified in the manual
  • Refrigerant type: R32
  • Factory charge: 1,900 g
  • Additional charge rate: 40 g per metre
  • Pre-charge length: 30 m
  • Maximum piping length: 50 m
  • Maximum piping height: 30 m
  • Refrigerant oil type: FW68D
  • Refrigerant oil amount: 600 cm³
Refrigerant charge: The factory charge covers up to 30 m of piping. Add 40 g/m for piping beyond 30 m.

Fan Motor, Airflow & Static Pressure

  • Indoor fan type: Sirocco fan x 2
  • Indoor fan motor output: 197 W
  • Static pressure range: 60 to 210 Pa
  • Indoor airflow - cooling:
    • High: 2,500 m³/h
    • Medium: 2,120 m³/h
    • Low: 1,750 m³/h
  • Indoor airflow - heating:
    • High: 2,500 m³/h
    • Medium: 2,120 m³/h
    • Low: 1,750 m³/h
  • Outdoor fan type: Propeller fan x 1
  • Outdoor fan motor output: 100 W
  • Outdoor airflow:
    • Cooling: 3,750 m³/h
    • Heating: 3,750 m³/h

Noise Levels

Unit / ModeNoise Level
Indoor - High41 dB(A)
Indoor - Medium38 dB(A)
Indoor - Low36 dB(A)
Indoor sound power - Cooling High61 dB(A)
Outdoor - Cooling51 dB(A)
Outdoor - Heating53 dB(A)
Outdoor sound power level69 dB(A)

Dimensions & Weight

ItemSpecification
Indoor dimensions (H x W x D)400 x 1,050 x 500 mm
Indoor gross dimensions460 x 1,230 x 640 mm
Indoor weight39 kg net / 46 kg gross
Outdoor dimensions (H x W x D)788 x 940 x 320 mm
Outdoor gross dimensions966 x 1,027 x 445 mm
Outdoor weight52 kg net / 61 kg gross

Pipe Connection Details

  • Liquid pipe size: Ø9.52 mm (3/8 in.)
  • Gas pipe size: Ø15.88 mm (5/8 in.)
  • Connection method: Flare
  • Indoor drain hose size: Ø25 mm I.D. / Ø32 mm O.D.
  • Outdoor drain hose size: Ø13.0 mm I.D. / Ø16.0 to Ø16.7 mm O.D.

Operating Range

  • Indoor cooling operating range: 18 to 32°C
  • Indoor cooling humidity limit: 80% RH or less
  • Indoor heating operating range: 16 to 30°C
  • Outdoor cooling operating range: -10 to 50°C
  • Outdoor heating operating range: -15 to 24°C

Direct Answers to Common Questions

  • What is the cooling capacity of ARTH30KHTA? 8.5 kW.
  • What is the heating capacity of ARTH30KHTA? 10.0 kW.
  • What is the EER of ARTH30KHTA? 3.62 kW/kW.
  • What is the COP of ARTH30KHTA? 4.26 kW/kW.
  • What refrigerant does this system use? R32.
  • Does this system support a 50 m pipe run? Yes.
  • What is the additional refrigerant charge? 40 g per metre over 30 m.
  • What is the maximum piping height? 30 m.