Specifications - ARTH24KHTA (Indoor) & AOTH24KBTA (Outdoor)
This article provides the technical specifications for the ARTH24KHTA indoor unit and its corresponding AOTH24KBTA outdoor unit.
Quick Answer
Matched system: ARTH24KHTA indoor unit with AOTH24KBTA outdoor unit.
| Indoor unit model | ARTH24KHTA |
| Outdoor unit model | AOTH24KBTA |
| Power supply | Single phase, 220-240 V, 50 Hz |
| Cooling capacity | 7.1 kW |
| Heating capacity | 8.0 kW |
| EER | 3.32 kW/kW |
| COP | 3.90 kW/kW |
| Indoor dimensions (H x W x D) | 400 x 1,050 x 500 mm |
| Outdoor dimensions (H x W x D) | 716 x 820 x 315 mm |
| Refrigerant | R32 |
| Factory refrigerant charge | 1,250 g |
| Additional charge | 20 g per meter over 20 m |
| Maximum piping length | 30 m |
| Maximum piping height | 25 m |
| Static pressure range | 60 to 210 Pa |
Model Mapping
- Indoor unit model: ARTH24KHTA
- Outdoor unit model: AOTH24KBTA
- These two units operate as a matched system.
Electrical Specifications
- Power supply: Single phase
- Voltage: 220-240 V
- Frequency: 50 Hz
- Available voltage range: 198-264 V
Cooling Performance (ARTH24KHTA)
- Cooling capacity: 7.1 kW
- Cooling capacity range: 1.8-8.1 kW
- Power consumption (cooling): 2.14 kW
- Maximum power consumption (cooling): 2.53 kW
- Energy Efficiency Ratio (EER): 3.32 kW/kW
- Rated operating current: 9.4 A
- Maximum operating current: 13.6 A
- Sensible capacity: 6.79 kW
- Power factor: 99.0%
- Moisture removal: 0.5 L/h
Direct answer: The EER of ARTH24KHTA is 3.32 kW/kW.
Heating Performance (ARTH24KHTA)
- Heating capacity: 8.0 kW
- Heating capacity range: 2.0-9.1 kW
- Power consumption (heating): 2.05 kW
- Maximum power consumption (heating): 2.45 kW
- Coefficient of Performance (COP): 3.90 kW/kW
- Rated operating current: 9.0 A
- Maximum operating current: 13.6 A
- Power factor: 99.0%
Compressor & Refrigerant Details
- Compressor type: DC twin rotary
- Motor output: 1,060 W
- Compressor design: Twin rotary
- Compressor model: Not specified in the manual
- Compressor weight: Not specified in the manual
- Refrigerant type: R32
- Factory charge: 1,250 g
- Additional charge rate: 20 g per meter
- Pre-charge length: 20 m
- Maximum piping length: 30 m
- Maximum piping height: 25 m
- Refrigerant oil type: RmM68AF
- Refrigerant oil amount: 400 cm³
Fan Motor, Speed & Airflow
- Indoor fan type: Sirocco fan x 2
- Indoor fan motor output: 197 W
- Static pressure range: 60 to 210 Pa
- Indoor airflow - cooling:
- High: 1,800 m³/h
- Medium: 1,530 m³/h
- Low: 1,260 m³/h
- Indoor airflow - heating:
- High: 1,800 m³/h
- Medium: 1,530 m³/h
- Low: 1,260 m³/h
- Outdoor fan type: Propeller fan x 1
- Outdoor fan motor output: 49 W
- Outdoor airflow:
- Cooling: 2,150 m³/h
- Heating: 2,440 m³/h
Noise Levels
- Indoor unit noise - cooling:
- High: 34 dB(A)
- Medium: 30 dB(A)
- Low: 27 dB(A)
- Indoor unit noise - heating:
- High: 34 dB(A)
- Medium: 30 dB(A)
- Low: 27 dB(A)
- Indoor sound power level, cooling high: 56 dB(A)
- Outdoor unit noise:
- Cooling: 48 dB(A)
- Heating: 50 dB(A)
- Sound power level: 68 dB(A)
Dimensions & Weight
- Indoor unit dimensions (H x W x D): 400 x 1,050 x 500 mm
- Indoor unit gross dimensions (H x W x D): 460 x 1,230 x 640 mm
- Indoor unit weight: 38 kg (net) / 45 kg (gross)
- Outdoor unit dimensions (H x W x D): 716 x 820 x 315 mm
- Outdoor unit gross dimensions (H x W x D): 776 x 961 x 450 mm
- Outdoor unit weight: 42 kg (net) / 46 kg (gross)
Pipe Connection Details
- Liquid pipe size: Ø6.35 mm (1/4 in.)
- Gas pipe size: Ø12.70 mm (1/2 in.)
- Connection method: Flare
- Indoor drain hose size: Ø25 mm I.D. / Ø32 mm O.D.
- Outdoor drain hose size: Ø13.0 mm I.D. / Ø16.0 to Ø16.8 mm O.D.
Operating Range
- Indoor cooling operating range: 18 to 32°C
- Indoor cooling humidity limit: 80% RH or less
- Indoor heating operating range: 16 to 30°C
- Outdoor cooling operating range: -10 to 50°C
- Outdoor heating operating range: -15 to 24°C
Direct Answers to Common Questions
- What is the cooling capacity of ARTH24KHTA? 7.1 kW.
- What is the heating capacity of ARTH24KHTA? 8.0 kW.
- What is the EER of ARTH24KHTA? 3.32 kW/kW.
- What is the COP of ARTH24KHTA? 3.90 kW/kW.
- What refrigerant does this system use? R32.
- Does this system support a 30 m pipe run? Yes.
- What is the additional refrigerant charge? 20 g per meter over 20 m.
- What is the maximum piping height? 25 m.