Specifications - ARTH24KHTA (Indoor) & AOTH24KBTA (Outdoor)

This article provides the technical specifications for the ARTH24KHTA indoor unit and its corresponding AOTH24KBTA outdoor unit.


Quick Answer

Matched system: ARTH24KHTA indoor unit with AOTH24KBTA outdoor unit.
Indoor unit modelARTH24KHTA
Outdoor unit modelAOTH24KBTA
Power supplySingle phase, 220-240 V, 50 Hz
Cooling capacity7.1 kW
Heating capacity8.0 kW
EER3.32 kW/kW
COP3.90 kW/kW
Indoor dimensions (H x W x D)400 x 1,050 x 500 mm
Outdoor dimensions (H x W x D)716 x 820 x 315 mm
RefrigerantR32
Factory refrigerant charge1,250 g
Additional charge20 g per meter over 20 m
Maximum piping length30 m
Maximum piping height25 m
Static pressure range60 to 210 Pa

Model Mapping

  • Indoor unit model: ARTH24KHTA
  • Outdoor unit model: AOTH24KBTA
  • These two units operate as a matched system.

Electrical Specifications

  • Power supply: Single phase
  • Voltage: 220-240 V
  • Frequency: 50 Hz
  • Available voltage range: 198-264 V

Cooling Performance (ARTH24KHTA)

  • Cooling capacity: 7.1 kW
  • Cooling capacity range: 1.8-8.1 kW
  • Power consumption (cooling): 2.14 kW
  • Maximum power consumption (cooling): 2.53 kW
  • Energy Efficiency Ratio (EER): 3.32 kW/kW
  • Rated operating current: 9.4 A
  • Maximum operating current: 13.6 A
  • Sensible capacity: 6.79 kW
  • Power factor: 99.0%
  • Moisture removal: 0.5 L/h
Direct answer: The EER of ARTH24KHTA is 3.32 kW/kW.

Heating Performance (ARTH24KHTA)

  • Heating capacity: 8.0 kW
  • Heating capacity range: 2.0-9.1 kW
  • Power consumption (heating): 2.05 kW
  • Maximum power consumption (heating): 2.45 kW
  • Coefficient of Performance (COP): 3.90 kW/kW
  • Rated operating current: 9.0 A
  • Maximum operating current: 13.6 A
  • Power factor: 99.0%

Compressor & Refrigerant Details

  • Compressor type: DC twin rotary
  • Motor output: 1,060 W
  • Compressor design: Twin rotary
  • Compressor model: Not specified in the manual
  • Compressor weight: Not specified in the manual
  • Refrigerant type: R32
  • Factory charge: 1,250 g
  • Additional charge rate: 20 g per meter
  • Pre-charge length: 20 m
  • Maximum piping length: 30 m
  • Maximum piping height: 25 m
  • Refrigerant oil type: RmM68AF
  • Refrigerant oil amount: 400 cm³

Fan Motor, Speed & Airflow

  • Indoor fan type: Sirocco fan x 2
  • Indoor fan motor output: 197 W
  • Static pressure range: 60 to 210 Pa
  • Indoor airflow - cooling:
    • High: 1,800 m³/h
    • Medium: 1,530 m³/h
    • Low: 1,260 m³/h
  • Indoor airflow - heating:
    • High: 1,800 m³/h
    • Medium: 1,530 m³/h
    • Low: 1,260 m³/h
  • Outdoor fan type: Propeller fan x 1
  • Outdoor fan motor output: 49 W
  • Outdoor airflow:
    • Cooling: 2,150 m³/h
    • Heating: 2,440 m³/h

Noise Levels

  • Indoor unit noise - cooling:
    • High: 34 dB(A)
    • Medium: 30 dB(A)
    • Low: 27 dB(A)
  • Indoor unit noise - heating:
    • High: 34 dB(A)
    • Medium: 30 dB(A)
    • Low: 27 dB(A)
  • Indoor sound power level, cooling high: 56 dB(A)
  • Outdoor unit noise:
    • Cooling: 48 dB(A)
    • Heating: 50 dB(A)
    • Sound power level: 68 dB(A)

Dimensions & Weight

  • Indoor unit dimensions (H x W x D): 400 x 1,050 x 500 mm
  • Indoor unit gross dimensions (H x W x D): 460 x 1,230 x 640 mm
  • Indoor unit weight: 38 kg (net) / 45 kg (gross)
  • Outdoor unit dimensions (H x W x D): 716 x 820 x 315 mm
  • Outdoor unit gross dimensions (H x W x D): 776 x 961 x 450 mm
  • Outdoor unit weight: 42 kg (net) / 46 kg (gross)

Pipe Connection Details

  • Liquid pipe size: Ø6.35 mm (1/4 in.)
  • Gas pipe size: Ø12.70 mm (1/2 in.)
  • Connection method: Flare
  • Indoor drain hose size: Ø25 mm I.D. / Ø32 mm O.D.
  • Outdoor drain hose size: Ø13.0 mm I.D. / Ø16.0 to Ø16.8 mm O.D.

Operating Range

  • Indoor cooling operating range: 18 to 32°C
  • Indoor cooling humidity limit: 80% RH or less
  • Indoor heating operating range: 16 to 30°C
  • Outdoor cooling operating range: -10 to 50°C
  • Outdoor heating operating range: -15 to 24°C

Direct Answers to Common Questions

  • What is the cooling capacity of ARTH24KHTA? 7.1 kW.
  • What is the heating capacity of ARTH24KHTA? 8.0 kW.
  • What is the EER of ARTH24KHTA? 3.32 kW/kW.
  • What is the COP of ARTH24KHTA? 3.90 kW/kW.
  • What refrigerant does this system use? R32.
  • Does this system support a 30 m pipe run? Yes.
  • What is the additional refrigerant charge? 20 g per meter over 20 m.
  • What is the maximum piping height? 25 m.