Outdoor Communication Error
Freshdesk Solution: Diagnostic flowchart and component test guide for outdoor communication error where likely causes include the main controller PCB, IPM / TR PCB, ACTPM / active filter module, DC fan motor and EEV coil.
Quick fault logic
Step 1 - Confirm communication before condemning power components
3-wire remote signal test
- At the wall controller, check Y1 to Y3 = 12V DC. If 12V DC is not present, the training guide notes the controller board could be faulty.
- Remove Y2 and test between Y3 and the disconnected cable to indoor: look for a fluctuating 7-11V DC pulse.
- Also test between controller terminals Y2 and Y3 for a fluctuating 7-12V DC signal.
Indoor to outdoor serial signal test
- Test between terminal 2 (neutral) and terminal 3 (signal) from both indoor and outdoor ends.
- If one end shows signal and the other does not, suspect damaged or disconnected signal cable between indoor and outdoor.
- If the communication circuit is missing with wiring confirmed, move the diagnosis toward the main controller PCB / signal chip.
| Signal reference | Expected value | Use |
|---|---|---|
| Remote Y1 to Y3 | 12V DC, not less than 11.4V | Confirms controller power to remote circuit |
| Remote Y2 to Y3 | 7-11V DC pulse | Confirms remote data signal |
| AST & ART/C indoor signal | 60-120V | Indoor communication reference |
| ASTA & ASTB indoor signal | 40-90V | Indoor communication reference |
| ASTG indoor signal | Approx. 200V static | Indoor communication reference |
| ARTG & 3 phase indoor signal | Approx. 295V static | Indoor communication reference |
| ARTH indoor signal | 50-250V | Indoor communication reference |
| AOTA outdoor signal | 60-120V | Outdoor communication reference |
| AOTG / AOTH outdoor signal | 3-110V | Outdoor communication reference |
Step 2 - How to check each suspect component
Main controller PCB
- Visually inspect for burn marks, damaged tracks, loose plugs, failed relay area or blown replaceable DC fuse 3.15A.
- Confirm the PCB has correct input supply and communication output present before disconnecting major components.
- Check the outdoor fan motor plug supply references on the board: red to black = 330-370V DC and white to black = 15V DC.
- Check the EEV output is a 12V DC circuit and the pressure sensor / thermistor circuits are 5V DC.
- If wiring and all connected components test correctly, but the signal remains missing or unstable, replace the main controller PCB.
IPM / TR PCB
Test method: power OFF, disconnect all control harnesses, multimeter on diode.
| Black lead | Red lead | Expected value |
|---|---|---|
| P | U | 0.4V |
| P | V | 0.4V |
| P | W | 0.4V |
| U | N | 0.4V |
| V | N | 0.4V |
| W | N | 0.4V |
| P | N | 0.7-0.9V |
| N | P | O/L |
A failed IPM can upset the outdoor controller and present as a communication-related shutdown. Any short, open or major deviation from the diode pattern is grounds to replace the IPM / TR PCB.
ACTPM / Active filter module
Test method: power OFF, disconnect all control harnesses, multimeter on auto-range resistance.
| Black lead | Red lead | Expected value |
|---|---|---|
| - | + | 360kΩ |
| - | L1 | 360kΩ |
| - | L2 | Over 1MΩ |
| - | N | 0Ω |
| + | P | 720kΩ to 900kΩ |
| N | P | 360kΩ to 540kΩ |
- Inspect the ACTPM for physical damage.
- The training guide states an ACTPM short will trip the power supply circuit breaker.
- If values are out of range or the breaker trip history points here, replace the ACTPM.
DC fan motor
Important: do not disconnect the DC fan motor when power is applied.
- Check mechanically whether the fan shaft is partially or fully seized.
- Test with power OFF using diode mode.
- Motor wiring reference: red = high voltage DC 330-380V, black = DC ground, white = 15V DC control, yellow = speed signal, blue/brown = feedback signal.
| Red lead | Black lead | Expected value |
|---|---|---|
| RED | BLACK | O/L |
| WHITE | BLACK | 0.5V to 1.8V |
| BLACK | RED | 0.8V to 1.1V |
| BLACK | WHITE | 0.4V to 0.6V |
If the motor is shorted, electrically abnormal or mechanically seized, replace the fan motor and inspect the board socket and harness for heat damage.
EEV coil
5-wire EEV coil
Test method: power OFF, resistance test.
- Test from red to white / orange / yellow / blue.
- Each should be 45Ω to 50Ω.
- Each wire to earth should read O/L.
6-wire EEV coil
Test method: power OFF, resistance test.
- Test red to white and red to orange = 45Ω to 50Ω.
- Test brown to yellow and brown to blue = 45Ω to 50Ω.
- All wires to earth should read O/L.
Physical checks for both EEV types
- Check for corrosion underneath where the EEV coil sits on the EEV body.
- Ensure the coil is clipped down and secured firmly to the EEV body.
- A shorted EEV coil or moisture-damaged coil can load the 12V DC output and create control issues that may appear as communication faults.
Step 3 - Decision guide
| Observed result | Likely direction | Action |
|---|---|---|
| No remote or indoor/outdoor signal voltage | Main controller PCB, signal chip, wiring fault | Repair wiring, confirm supply, replace controller PCB if signal cannot be restored |
| Signal present but fault remains | Connected outdoor component may be loading controller | Power off and isolate DC fan motor, EEV coil, IPM and ACTPM one by one |
| ACTPM out of range or breaker trip history | ACTPM failure | Replace ACTPM and inspect related harnesses |
| IPM diode readings incorrect | IPM / TR PCB failure | Replace IPM / TR PCB |
| DC fan motor electrically abnormal or seized | Fan motor failure | Replace motor and inspect board plug/socket |
| EEV coil resistance incorrect or short to earth | EEV coil failure | Replace EEV coil and confirm secure seating on valve body |
| All components test correctly | Main controller PCB remains primary suspect | Replace controller PCB and retest communication |
Final verification
- Reconnect all harnesses correctly.
- Restore power.
- Confirm indoor to outdoor communication signal is present.
- Clear the fault and perform a test run.
- Verify fan operation, EEV response, stable communication and normal system operation.