Specifications - ARTG30LHTA (Indoor) & AOTG30LBTC (Outdoor)

This article provides the technical specifications for the ARTG30LHTA indoor unit and its corresponding AOTG30LBTC outdoor unit.

Quick Answer
  • Indoor unit model: ARTG30LHTA
  • Outdoor unit model: AOTG30LBTC
  • Matched system: Yes
  • Power supply: Single phase, 240 V, 50 Hz
  • Cooling capacity: 8.5 kW
  • Heating capacity: 10.0 kW
  • EER: 3.26 kW/kW
  • COP: 3.70 kW/kW
  • Indoor dimensions (H x W x D): 400 x 1,050 x 500 mm
  • Outdoor dimensions (H x W x D): 830 x 900 x 330 mm
  • Refrigerant type: R410A
  • Factory charge: 2,100 g
  • Additional charge rate: 40 g per metre over 20 m
  • Maximum piping length: 50 m
  • Maximum piping height: 30 m
  • External static pressure: Rated 60 Pa / High 100 Pa / Operation range 60 to 210 Pa

Model Mapping

ComponentModel
Indoor UnitARTG30LHTA
Outdoor UnitAOTG30LBTC
SystemMatched system

Electrical Specifications

  • Power supply: Single phase
  • Voltage: 240 V
  • Frequency: 50 Hz
  • Available voltage range: 198-264 V
  • Maximum operating current: 17.1 A
  • Recommended circuit breaker current: 25 A
  • Power cable size: 4.0 mm²
  • Connection cable cross-sectional area: 1.5 mm²
  • Limited wiring length: 51 m

Cooling Performance

ItemSpecification
Cooling capacity8.5 kW
Capacity range4.7-10.0 kW
Power consumption2.61 kW
Maximum power consumption4.06 kW
EER3.26 kW/kW
Rated operating current11.0 A
Maximum operating current17.1 A
Moisture removal0.9 L/h

Heating Performance

ItemSpecification
Heating capacity10.0 kW
Capacity range5.0-11.5 kW
Power consumption2.70 kW
Maximum power consumption4.06 kW
COP3.70 kW/kW
Rated operating current11.3 A
Maximum operating current17.1 A

Compressor & Refrigerant Details

  • Compressor type: Twin rotary x 1
  • Compressor motor output: 2,100 W
  • Compressor model: Not specified in the manual
  • Compressor weight: Not specified in the manual
  • Refrigerant type: R410A
  • Factory charge: 2,100 g
  • Additional charge rate: 40 g per metre
  • Pre-charge length: 20 m
  • Maximum piping length: 50 m
  • Maximum piping height: 30 m
  • Refrigerant oil type: POE (RB68)
  • Refrigerant oil amount: 800 cm³
Refrigerant charge: The factory charge covers up to 20 m of piping. Add 40 g/m for piping beyond 20 m.

Fan Motor, Airflow & Static Pressure

  • Indoor fan type: Sirocco fan x 2
  • Indoor fan motor output: 197 W
  • External static pressure: Rated 60 Pa / High 100 Pa / Operation range 60 to 210 Pa
  • Indoor airflow - cooling:
    • High: 2,500 m³/h
    • Medium: 2,100 m³/h
    • Low: 1,700 m³/h
  • Indoor airflow - heating:
    • High: 2,500 m³/h
    • Medium: 2,100 m³/h
    • Low: 1,700 m³/h
  • Outdoor fan type: Propeller x 1
  • Outdoor fan motor output: 100 W
  • Outdoor airflow:
    • Cooling: 3,600 m³/h
    • Heating: 3,600 m³/h

Noise Levels

Unit / ModeNoise Level
Indoor - High41 dB(A)
Indoor - Medium38 dB(A)
Indoor - Low36 dB(A)
Outdoor - Cooling53 dB(A)
Outdoor - Heating55 dB(A)
Outdoor sound power level69 dB(A)

Dimensions & Weight

ItemSpecification
Indoor dimensions (H x W x D)400 x 1,050 x 500 mm
Indoor gross dimensions460 x 1,230 x 640 mm
Indoor weight39 kg net / 46 kg gross
Outdoor dimensions (H x W x D)830 x 900 x 330 mm
Outdoor gross dimensions1,000 x 1,050 x 445 mm
Outdoor weight61 kg net / 69 kg gross

Pipe Connection Details

  • Liquid pipe size: Ø 9.52 mm (3/8 in.)
  • Gas pipe size: Ø 15.88 mm (5/8 in.)
  • Connection method: Flare
  • Drain hose size: Ø 23.4 mm I.D. / Ø 25.4 mm O.D.

Operating Range

  • Indoor cooling operating range: 18 to 32°C
  • Indoor cooling humidity limit: 80% RH or less
  • Indoor heating operating range: 16 to 30°C
  • Outdoor cooling operating range: -15 to 46°C
  • Outdoor heating operating range: -15 to 24°C

Direct Answers to Common Questions

  • What is the cooling capacity of ARTG30LHTA? 8.5 kW.
  • What is the heating capacity of ARTG30LHTA? 10.0 kW.
  • What is the EER of ARTG30LHTA? 3.26 kW/kW.
  • What is the COP of ARTG30LHTA? 3.70 kW/kW.
  • What refrigerant does this system use? R410A.
  • Does this system support a 50 m pipe run? Yes.
  • What is the additional refrigerant charge? 40 g per metre over 20 m.
  • What is the maximum piping height? 30 m.