AIRSTAGE Technical Reference

ARTG45LHTA / AOTG45LBTC

Matched ducted system specifications
Capacity, electrical, refrigerant, airflow, noise, dimensions and piping data
Matched system: Indoor unit ARTG45LHTA is matched with outdoor unit AOTG45LBTC.

Quick Answer

Indoor unitARTG45LHTA
Outdoor unitAOTG45LBTC
Power supplySingle phase, 240 V, 50 Hz
Cooling / heating capacity11.5 kW / 14.0 kW
EER / COP3.11 / 3.65 kW/kW
RefrigerantR410A, factory charge 2,900 g
Additional charge40 g per metre over 20 m
Maximum pipe length / height50 m / 30 m
External static pressureRated 60 Pa; selectable high settings 100, 150 or 200 Pa; operating range 60-260 Pa

Model Mapping

  • Indoor unit: ARTG45LHTA
  • Outdoor unit: AOTG45LBTC
  • These units operate as a matched system.

Electrical Specifications

ItemSpecification
SupplySingle phase, 240 V, 50 Hz
Available voltage range198-264 V
Maximum operating current23.5 A
Recommended circuit breaker32 A
Power cable4.0 mm²
Connection cable1.5 mm²
Limited wiring length51 m

Cooling and Heating Performance

ItemCoolingHeating
Rated capacity11.5 kW14.0 kW
Capacity range5.7-13.5 kW6.0-15.5 kW
Power consumption3.70 kW3.84 kW
Maximum power consumption5.62 kW5.62 kW
EfficiencyEER 3.11 kW/kWCOP 3.65 kW/kW
Rated current15.5 A16.1 A
Maximum current23.5 A23.5 A
Direct answer: The EER of ARTG45LHTA is 3.11 kW/kW.

Compressor and Refrigerant Details

  • Compressor: Twin rotary x 1
  • Compressor motor output: 2,100 W
  • Compressor model and weight: Not specified in the manual
  • Refrigerant: R410A
  • Factory charge: 2,900 g
  • Pre-charge length: 20 m
  • Additional charge: 40 g per metre over 20 m
  • Maximum pipe length: 50 m
  • Maximum height difference: 30 m
  • Refrigerant oil: POE (RB68), 800 cm³

Fan, Airflow and Static Pressure

  • Indoor fan: Sirocco fan x 2; motor output 197 x 2 W
  • Indoor airflow, cooling and heating: High 3,250 m³/h; Medium 2,750 m³/h; Low 2,200 m³/h
  • External static pressure: Rated 60 Pa; high settings 100, 150 or 200 Pa; operating range 60-260 Pa
  • Outdoor fan: Propeller x 1; motor output 111 W
  • Outdoor airflow: 4,200 m³/h cooling; 4,650 m³/h heating

Noise Levels

LocationNoise level
Indoor - cooling and heatingHigh 43 dB(A); Medium 39 dB(A); Low 35 dB(A)
Outdoor58 dB(A) cooling; 58 dB(A) heating; sound power 72 dB(A)

Dimensions and Weight

UnitNet dimensions (H x W x D)Gross dimensionsWeight
Indoor425 x 1,250 x 490 mm490 x 1,440 x 655 mm54 kg net / 61 kg gross
Outdoor914 x 970 x 370 mm1,078 x 1,064 x 479 mm75 kg net / 84 kg gross

Pipe Connections

  • Liquid pipe: Ø 9.52 mm (3/8 in.)
  • Gas pipe: Ø 15.88 mm (5/8 in.)
  • Connection: Flare
  • Drain hose: Ø 23.4 mm I.D. / Ø 25.4 mm O.D.

Operating Range

  • Indoor cooling: 18 to 32°C; 80% RH or less
  • Indoor heating: 16 to 30°C
  • Outdoor cooling: -15 to 46°C
  • Outdoor heating: -15 to 24°C

Common Questions

What is the cooling capacity?11.5 kW
What is the heating capacity?14.0 kW
What is the EER?3.11 kW/kW
What is the COP?3.65 kW/kW
What refrigerant is used?R410A
Can the system support a 50 m pipe run?Yes
What is the additional refrigerant charge?40 g per metre over 20 m
What is the maximum piping height?30 m
Specifications should be confirmed against the applicable product documentation before installation or service work.