AIRSTAGE Technical Reference
ARTG54LHTDP / AOTG54LBTB
Matched ducted system technical specifications
Capacities, electrical data, refrigerant charge, static pressure, airflow, sound levels and dimensions
This article provides the technical specifications for the ARTG54LHTDP indoor unit and its matched AOTG54LBTB outdoor unit.
1. Quick answer
| Indoor unit | ARTG54LHTDP |
| Outdoor unit | AOTG54LBTB |
| Matched system | Yes |
| Power supply | Single phase, 240 V, 50 Hz |
| Cooling capacity | 13.0 kW |
| Heating capacity | 16.0 kW |
| EER / COP | 3.32 / 3.60 kW/kW |
| Refrigerant | R410A |
| Factory charge | 3,450 g for up to 30 m piping |
| Additional charge | 50 g per metre over 30 m |
| Maximum pipe length / height | 75 m / 30 m |
| Static pressure range | 30 to 200 Pa |
2. Model mapping and electrical specifications
Matched combination: ARTG54LHTDP indoor unit with AOTG54LBTB outdoor unit.
| Electrical item | Specification |
|---|---|
| Phase | Single phase |
| Voltage | 240 V |
| Frequency | 50 Hz |
| Available voltage range | 198-264 V |
3. Cooling and heating performance
| Specification | Cooling | Heating |
|---|---|---|
| Rated capacity | 13.0 kW | 16.0 kW |
| Capacity range | 6.2-15.2 kW | 6.2-18.0 kW |
| Rated power consumption | 3.92 kW | 4.45 kW |
| Maximum power consumption | 5.58 kW | 5.59 kW |
| Efficiency | EER 3.32 kW/kW | COP 3.60 kW/kW |
| Rated operating current | 16.5 A | 18.7 A |
| Maximum operating current | 23.5 A | 23.5 A |
| Power factor | 99.0% | 99.2% |
| Moisture removal | 3.7 L/h | - |
4. Compressor, refrigerant and piping
| Item | Specification |
|---|---|
| Compressor type | Twin rotary x 1 |
| Compressor motor output | 3,750 W |
| Compressor model | Not specified in the manual |
| Refrigerant type | R410A |
| Factory charge | 3,450 g |
| Pre-charge length | 30 m |
| Refrigerant oil | POE (VG74), 1,550 cm³ |
Additional charge: Add 50 g of R410A per metre when the total pipe length exceeds the 30 m pre-charge length.
- Maximum piping length: 75 m
- Maximum piping height: 30 m
- Liquid pipe: Ø9.52 mm (3/8 in.)
- Gas pipe: Ø15.88 mm (5/8 in.)
- Connection method: Flare
- Drain hose: Ø25 mm I.D. / Ø32 mm O.D.
5. Fan, airflow and sound levels
Indoor fan and airflow
| Speed | Fan power | Cooling airflow | Heating airflow | Sound pressure |
|---|---|---|---|---|
| Quiet | 70 W | 1,430 m³/h | 1,430 m³/h | 29 dB(A) |
| Low | 90 W | 1,650 m³/h | 1,650 m³/h | 31 dB(A) |
| Medium | 135 W | 2,040 m³/h | 2,040 m³/h | 35 dB(A) |
| High | 225 W | 2,550 m³/h | 2,550 m³/h | 40 dB(A) |
- Indoor fan type: Sirocco fan x 3
- Indoor fan motor output: 375 W
- Static pressure range: 30 to 200 Pa
- Outdoor fan type: Propeller x 2
- Outdoor fan motor output: 100 W x 2
- Outdoor airflow: 6,850 m³/h cooling / 6,750 m³/h heating
- Outdoor sound pressure: 55 dB(A) cooling / 57 dB(A) heating
- Outdoor sound power level: 70 dB(A)
6. Dimensions and weight
| Unit | Net dimensions (H x W x D) | Gross dimensions (H x W x D) | Weight |
|---|---|---|---|
| ARTG54LHTDP indoor | 300 x 1,400 x 700 mm | 400 x 1,638 x 875 mm | 46 kg net / 55 kg gross |
| AOTG54LBTB outdoor | 1,290 x 900 x 330 mm | 1,460 x 1,050 x 445 mm | 93 kg net / 102 kg gross |
7. Operating range
- Outdoor cooling range: -15°C to 46°C
- Outdoor heating range: -15°C to 24°C
- Indoor cooling range: 18°C to 32°C, 80% RH or less
- Indoor heating range: 16°C to 30°C