AIRSTAGE Technical Reference
ARTG24LHTDP & AOTG24LBCA Specifications
Indoor and outdoor unit performance, electrical, piping and dimensional data
Matched ducted system using R410A refrigerant
System match: The ARTG24LHTDP indoor unit is matched with the AOTG24LBCA outdoor unit. Rated capacity is 7.1 kW cooling and 8.0 kW heating.
1. Quick answer
| Indoor unit | ARTG24LHTDP |
| Outdoor unit | AOTG24LBCA |
| Power supply | Single phase, 240 V, 50 Hz |
| Rated capacity | 7.1 kW cooling / 8.0 kW heating |
| Efficiency | EER 3.41 / COP 3.65 |
| Refrigerant | R410A, factory charge 1,800 g |
| Pipe limits | 30 m maximum length / 20 m maximum height |
| Static pressure range | 30 to 200 Pa |
2. Electrical specifications
| Item | Specification |
|---|---|
| Power supply | Single phase |
| Voltage / frequency | 240 V / 50 Hz |
| Available voltage range | 198-264 V |
3. Cooling and heating performance
| Specification | Cooling | Heating |
|---|---|---|
| Rated capacity | 7.1 kW | 8.0 kW |
| Capacity range | 2.9-8.0 kW | 2.2-9.1 kW |
| Power consumption | 2.08 kW | 2.19 kW |
| Maximum power consumption | 4.06 kW | 4.40 kW |
| Efficiency | EER 3.41 kW/kW | COP 3.65 kW/kW |
| Rated operating current | 8.7 A | 9.2 A |
| Maximum operating current | 17.0 A | 18.5 A |
| Power factor | 99.6% | 99.2% |
| Moisture removal | 2.2 L/h | - |
4. Compressor and refrigerant
| Compressor type | Twin rotary x 1 |
| Compressor motor output | 1,100 W |
| Compressor model / weight | Not specified in the source manual |
| Refrigerant | R410A |
| Factory charge / pre-charge length | 1,800 g / 15 m |
| Additional charge | 20 g per metre over 15 m |
| Refrigerant oil | POE (RB68), 600 cm³ |
5. Fan, airflow and sound levels
Indoor static pressure range: 30 to 200 Pa.
| Indoor fan setting | Fan power | Airflow | Sound pressure |
|---|---|---|---|
| Quiet | 15 W | 680 m³/h | 21 dB(A) |
| Low | 25 W | 880 m³/h | 24 dB(A) |
| Medium | 40 W | 1,080 m³/h | 28 dB(A) |
| High | 70 W | 1,360 m³/h | 33 dB(A) |
- Indoor fan: Sirocco fan x 2, motor output 197 W.
- Indoor airflow and sound values are the same for cooling and heating.
- Outdoor fan: Propeller x 1, motor output 49 W.
- Outdoor airflow: 2,460 m³/h cooling and 2,340 m³/h heating.
- Outdoor sound pressure: 55 dB(A) cooling and 56 dB(A) heating.
- Outdoor sound power level: 69 dB(A).
6. Dimensions and weight
| Unit | Net dimensions (H x W x D) | Gross dimensions (H x W x D) | Weight |
|---|---|---|---|
| ARTG24LHTDP indoor | 300 x 1,000 x 700 mm | 400 x 1,238 x 875 mm | 36 kg net / 43 kg gross |
| AOTG24LBCA outdoor | 620 x 790 x 290 mm | 713 x 945 x 395 mm | 41 kg net / 45 kg gross |
7. Pipe connections and limits
| Liquid pipe | Ø 6.35 mm (1/4 in.) |
| Gas pipe | Ø 15.88 mm (5/8 in.) |
| Connection method | Flare |
| Drain hose | Ø 25 mm I.D. / Ø 32 mm O.D. |
| Maximum piping length | 30 m |
| Maximum piping height | 20 m |
8. Operating range
| Condition | Cooling | Heating |
|---|---|---|
| Indoor temperature | 18 to 32°C | 16 to 30°C |
| Outdoor temperature | -10 to 46°C | -15 to 24°C |
| Indoor humidity limit | 80% RH or less | - |
9. Common questions
What is the cooling capacity?
7.1 kW rated, with a capacity range of 2.9 to 8.0 kW.
7.1 kW rated, with a capacity range of 2.9 to 8.0 kW.
What is the heating capacity?
8.0 kW rated, with a capacity range of 2.2 to 9.1 kW.
8.0 kW rated, with a capacity range of 2.2 to 9.1 kW.
What are the EER and COP?
EER is 3.41 kW/kW and COP is 3.65 kW/kW.
EER is 3.41 kW/kW and COP is 3.65 kW/kW.
What refrigerant is used?
R410A. The factory charge is 1,800 g for up to 15 m of pipe.
R410A. The factory charge is 1,800 g for up to 15 m of pipe.
What additional refrigerant charge is required?
Add 20 g per metre for piping over 15 m.
Add 20 g per metre for piping over 15 m.
Can the system support a 30 m pipe run?
Yes. The maximum piping length is 30 m and the maximum height difference is 20 m.
Yes. The maximum piping length is 30 m and the maximum height difference is 20 m.
Technical data should be confirmed against the current product documentation before installation, service or replacement work.