AIRSTAGE Technical Reference

ARTG45LHTDP / AOTG45LBTB

Matched ducted system technical specifications
Performance, electrical, refrigerant, piping, airflow, static pressure, noise and dimensional data
This article summarises the technical specifications for the ARTG45LHTDP indoor unit and corresponding AOTG45LBTB outdoor unit. These models operate as a matched system.

1. Quick answer

Indoor unitARTG45LHTDP
Outdoor unitAOTG45LBTB
Matched systemYes
Power supplySingle phase, 240 V, 50 Hz
Cooling / heating capacity11.5 kW / 14.0 kW
EER / COP3.45 / 3.80 kW/kW
RefrigerantR410A
Factory charge3,350 g for up to 20 m piping
Additional charge40 g per metre over 20 m
Maximum pipe length / height50 m / 30 m
Static pressure range30-200 Pa

2. Model mapping and electrical specifications

ItemSpecification
Indoor unitARTG45LHTDP
Outdoor unitAOTG45LBTB
Power supplySingle phase
Voltage240 V
Frequency50 Hz
Available voltage range198-264 V

3. Cooling and heating performance

SpecificationCoolingHeating
Rated capacity11.5 kW14.0 kW
Capacity range2.8-14.0 kW4.2-15.5 kW
Rated power consumption3.33 kW3.68 kW
Maximum power consumption5.00 kW5.02 kW
EfficiencyEER 3.45 kW/kWCOP 3.80 kW/kW
Rated operating current14.0 A15.4 A
Maximum operating current21.0 A21.0 A
Power factor99.1%99.6%
Moisture removal2.6 L/h-
Direct answer: The EER of the ARTG45LHTDP is 3.45 kW/kW.

4. Compressor, refrigerant and piping

ItemSpecification
Compressor typeTwin rotary × 1
Compressor motor output2,100 W
Compressor modelNot specified in the manual
RefrigerantR410A
Factory charge3,350 g
Pre-charge length20 m
Additional charge rate40 g per metre over 20 m
Maximum pipe length / height50 m / 30 m
Refrigerant oilPOE (RB68), 800 cm³

Connection details

  • Liquid pipe: Ø9.52 mm (3/8 in.)
  • Gas pipe: Ø15.88 mm (5/8 in.)
  • Connection method: Flare
  • Drain hose: Ø25 mm I.D. / Ø32 mm O.D.

5. Fan, airflow, static pressure and noise

ItemSpecification
Indoor fanSirocco fan × 3, 375 W motor output
Static pressure range30-200 Pa
Indoor fan powerQuiet 70 W; low 90 W; medium 135 W; high 225 W
Indoor airflowQuiet 1,430; low 1,650; medium 2,040; high 2,550 m³/h in cooling and heating
Outdoor fanPropeller × 2, 100 W × 2 motor output
Outdoor airflow6,650 m³/h cooling / 6,200 m³/h heating
Indoor sound pressureQuiet 29; low 31; medium 35; high 40 dB(A) in cooling and heating
Outdoor sound pressure55 dB(A) cooling / 55 dB(A) heating
Outdoor sound power69 dB(A)

6. Dimensions and weight

UnitNet dimensions (H × W × D)Gross dimensionsWeight
ARTG45LHTDP indoor300 × 1,400 × 700 mm400 × 1,638 × 875 mm46 kg net / 55 kg gross
AOTG45LBTB outdoor1,290 × 900 × 330 mm1,460 × 1,050 × 445 mm86 kg net / 95 kg gross

7. Operating range

  • Outdoor cooling: -15°C to 46°C
  • Outdoor heating: -15°C to 24°C
  • Indoor cooling: 18°C to 32°C, 80% RH or less
  • Indoor heating: 16°C to 30°C

8. Direct answers to common questions

What is the cooling capacity?
11.5 kW.
What is the heating capacity?
14.0 kW.
What are the EER and COP?
EER 3.45 kW/kW and COP 3.80 kW/kW.
Does the system support a 50 m pipe run?
Yes. The maximum pipe length is 50 m, with a maximum height difference of 30 m.
What additional refrigerant charge is required?
40 g per metre for pipe length over 20 m.
What is the indoor airflow range?
1,430-2,550 m³/h.
What is the static pressure range?
30-200 Pa.