AIRSTAGE Technical Reference
ARTG36LHTDP / AOTG36LBTA
Matched ducted system technical specifications
Capacities, electrical data, refrigerant charge, static pressure, airflow, sound levels and dimensions
This article provides the technical specifications for the ARTG36LHTDP indoor unit and its matched AOTG36LBTA outdoor unit.
Model clarification: The referenced manual lists ARTG36LHTDP. It does not list ARTG36LHTDO.
1. Quick answer
| Indoor unit | ARTG36LHTDP |
| Outdoor unit | AOTG36LBTA |
| Matched system | Yes |
| Power supply | Single phase, 240 V, 50 Hz |
| Cooling capacity | 10.0 kW |
| Heating capacity | 11.2 kW |
| EER / COP | 3.22 / 3.65 kW/kW |
| Refrigerant | R410A |
| Factory charge | 2,100 g for up to 20 m piping |
| Additional charge | 40 g per metre over 20 m |
| Maximum pipe length / height | 50 m / 30 m |
| Static pressure range | 30 to 200 Pa |
2. Model mapping and electrical specifications
Matched combination: ARTG36LHTDP indoor unit with AOTG36LBTA outdoor unit.
| Electrical item | Specification |
|---|---|
| Phase | Single phase |
| Voltage | 240 V |
| Frequency | 50 Hz |
| Available voltage range | 198-264 V |
3. Cooling and heating performance
| Specification | Cooling | Heating |
|---|---|---|
| Rated capacity | 10.0 kW | 11.2 kW |
| Capacity range | 3.8-11.2 kW | 4.0-14.0 kW |
| Rated power consumption | 3.11 kW | 3.07 kW |
| Maximum power consumption | 4.78 kW | 4.76 kW |
| Efficiency | EER 3.22 kW/kW | COP 3.65 kW/kW |
| Rated operating current | 13.0 A | 12.9 A |
| Maximum operating current | 20.0 A | 20.0 A |
| Power factor | 99.7% | 99.2% |
| Moisture removal | 2.4 L/h | - |
4. Compressor, refrigerant and piping
| Item | Specification |
|---|---|
| Compressor type | Twin rotary x 1 |
| Compressor motor output | 2,100 W |
| Compressor model | Not specified in the manual |
| Refrigerant type | R410A |
| Factory charge | 2,100 g |
| Pre-charge length | 20 m |
| Refrigerant oil | POE (RB68), 800 cm³ |
Additional charge: Add 40 g of R410A per metre when the total pipe length exceeds the 20 m pre-charge length.
- Maximum piping length: 50 m
- Maximum piping height: 30 m
- Liquid pipe: Ø9.52 mm (3/8 in.)
- Gas pipe: Ø15.88 mm (5/8 in.)
- Connection method: Flare
- Drain hose: Ø25 mm I.D. / Ø32 mm O.D.
5. Fan, airflow and sound levels
Indoor fan and airflow
| Speed | Fan power | Cooling airflow | Heating airflow | Cooling sound | Heating sound |
|---|---|---|---|---|---|
| Quiet | 45 W | 1,070 m³/h | 1,070 m³/h | 26 dB(A) | 26 dB(A) |
| Low | 60 W | 1,330 m³/h | 1,330 m³/h | 28 dB(A) | 28 dB(A) |
| Medium | 90 W | 1,640 m³/h | 1,640 m³/h | 31 dB(A) | 31 dB(A) |
| High | 150 W | 2,050 m³/h | 1,850 m³/h | 36 dB(A) | 33 dB(A) |
- Indoor fan type: Sirocco fan x 3
- Indoor fan motor output: 375 W
- Static pressure range: 30 to 200 Pa
- Outdoor fan type: Propeller x 1
- Outdoor fan motor output: 100 W
- Outdoor airflow: 3,800 m³/h cooling / 3,800 m³/h heating
- Outdoor sound pressure: 54 dB(A) cooling / 55 dB(A) heating
- Outdoor sound power level: 70 dB(A)
6. Dimensions and weight
| Unit | Net dimensions (H x W x D) | Gross dimensions (H x W x D) | Weight |
|---|---|---|---|
| ARTG36LHTDP indoor | 300 x 1,400 x 700 mm | 400 x 1,638 x 875 mm | 46 kg net / 55 kg gross |
| AOTG36LBTA outdoor | 830 x 900 x 330 mm | 1,000 x 1,050 x 445 mm | 61 kg net / 69 kg gross |
7. Operating range
- Outdoor cooling range: -15°C to 46°C
- Outdoor heating range: -15°C to 24°C
- Indoor cooling range: 18°C to 32°C, 80% RH or less
- Indoor heating range: 16°C to 30°C