AIRSTAGE Technical Reference
ARTG60LHTB / AOTG60LATA
Matched ducted system technical specifications
Capacities, electrical data, refrigerant charge, airflow, sound levels, piping and dimensions
This article provides the technical specifications for the ARTG60LHTB indoor unit and its matched AOTG60LATA outdoor unit.
1. Quick answer
| Indoor unit | ARTG60LHTB |
| Outdoor unit | AOTG60LATA |
| Matched system | Yes |
| Power supply | Single phase, 240 V, 50 Hz |
| Cooling capacity | 15.8 kW |
| Heating capacity | 18.0 kW |
| EER / COP | 3.21 / 3.60 kW/kW |
| Refrigerant | R410A |
| Factory charge | 3,450 g for up to 30 m piping |
| Additional charge | 50 g per metre over 30 m |
| Maximum pipe length / height | 75 m / 30 m |
2. Model mapping and electrical specifications
Matched combination: ARTG60LHTB indoor unit with AOTG60LATA outdoor unit.
| Electrical item | Specification |
|---|---|
| Phase | Single phase |
| Voltage | 240 V |
| Frequency | 50 Hz |
| Available voltage range | 198-264 V |
3. Cooling and heating performance
| Specification | Cooling | Heating |
|---|---|---|
| Rated capacity | 15.8 kW | 18.0 kW |
| Capacity range | 6.2-16.3 kW | 6.2-18.5 kW |
| Rated power consumption | 4.92 kW | 4.98 kW |
| Maximum power consumption | 5.94 kW | 5.94 kW |
| Efficiency | EER 3.21 kW/kW | COP 3.60 kW/kW |
| Rated operating current | 20.7 A | 21.0 A |
| Maximum operating current | 26.0 A | 26.0 A |
| Moisture removal | 1.0 L/h | - |
Efficiency reference: The EER is 3.21 kW/kW and the COP is 3.60 kW/kW.
4. Compressor, refrigerant and piping
| Item | Specification |
|---|---|
| Compressor type | Twin rotary x 1 |
| Motor type | DC twin rotary compressor |
| Compressor motor output | 3,750 W |
| Compressor model | Not specified in the provided manual |
| Compressor weight | Not specified in the provided manual |
| Refrigerant type | R410A |
| Factory charge | 3,450 g for total pipe length up to 30 m |
| Pre-charge length | 30 m |
| Refrigerant oil type | POE |
Additional charge: Add 50 g of R410A per metre when the total pipe length exceeds the 30 m pre-charge length.
Refrigerant charge by pipe length
| Total pipe length | Total refrigerant charge |
|---|---|
| Up to 30 m | 3,450 g |
| 40 m | 3,950 g |
| 50 m | 4,450 g |
| 60 m | 4,950 g |
| 70 m | 5,450 g |
- Maximum piping length: 75 m
- Maximum piping height: 30 m
- Liquid pipe: Ø9.52 mm (3/8 in.)
- Gas pipe: Ø15.88 mm (5/8 in.)
- Connection method: Flare
5. Fan, airflow and sound levels
Indoor airflow and noise
| Fan setting | Airflow | Sound pressure |
|---|---|---|
| Low | 2,700 m³/h | 36 dB(A) |
| Medium | 3,600 m³/h | 43 dB(A) |
| High | 4,100 m³/h | 46 dB(A) |
Fan motor and outdoor performance
| Item | Cooling | Heating |
|---|---|---|
| Outdoor fan speed | Upper 900 rpm / Lower 800 rpm | Upper 900 rpm / Lower 900 rpm |
| Outdoor airflow | 6,900 m³/h | 7,300 m³/h |
| Outdoor sound pressure | 57 dB(A) | 59 dB(A) |
- Indoor fan motor model: Not specified in the provided manual
- Outdoor fan motor model: Not specified in the provided manual
- Indoor fan speed in rpm: Not specified for low, medium or high
6. Dimensions and weight
| Unit | Dimensions (H x W x D) | Weight |
|---|---|---|
| ARTG60LHTB indoor | 450 x 1,587 x 700 mm | 94 kg net / 109 kg shipping |
| AOTG60LATA outdoor | 1,290 x 900 x 330 mm | 93 kg net / 101 kg shipping |
7. Operating range
- Outdoor cooling range: -15°C to 46°C
- Outdoor heating range: -15°C to 24°C
- Indoor cooling range: 18°C to 32°C, 80% RH or less
- Indoor heating range: 16°C to 30°C
8. Direct answers to common questions
Source: Fujitsu General Design & Technical Manual for ARTG60LHTB and AOTG60LATA.