AIRSTAGE Technical Reference

ARTG54LHTB / AOTG54LATT

Matched ducted system technical specifications
Performance, electrical, refrigerant, piping, airflow, noise and dimensional data
This article summarises the technical specifications for the ARTG54LHTB indoor unit and corresponding AOTG54LATT outdoor unit. These models operate as a matched system.

1. Quick answer

Indoor unitARTG54LHTB
Outdoor unitAOTG54LATT
Matched systemYes
Power supply3N ~ 415 V, 50 Hz
Cooling / heating capacity14.0 kW / 16.0 kW
EER / COP3.25 / 3.66 kW/kW
RefrigerantR410A
Factory charge3,450 g for up to 30 m piping
Additional charge50 g per metre over 30 m
Maximum pipe length / height75 m / 30 m

2. Model mapping and electrical specifications

ItemSpecification
Indoor unitARTG54LHTB
Outdoor unitAOTG54LATT
Power supply3N ~ 415 V, 50 Hz
Available voltage range3N ~ 342-457 V

3. Cooling and heating performance

SpecificationCoolingHeating
Rated capacity14.0 kW16.0 kW
Capacity range6.2-16.0 kW6.2-18.0 kW
Rated power consumption4.31 kW4.37 kW
Maximum power consumption7.08 kW7.08 kW
EfficiencyEER 3.25 kW/kWCOP 3.66 kW/kW
Rated operating current6.2 A6.3 A
Maximum operating current12.0 A12.0 A
Moisture removal1.5 L/h-
Direct answer: The EER of the ARTG54LHTB is 3.25 kW/kW.

4. Compressor, refrigerant and piping

Compressor

  • Type: DC twin rotary, one compressor
  • Motor output: 3,750 W
  • Compressor model and weight: Not specified in the provided manual

Refrigerant charge

ItemSpecification
RefrigerantR410A
Factory charge3,450 g for total pipe length up to 30 m
Charge at 40 m3,950 g
Charge at 50 m4,450 g
Charge at 60 m4,950 g
Charge at 70 m5,450 g
Additional charge rate50 g per metre over 30 m
Maximum pipe length / height75 m / 30 m
Refrigerant oilPOE

Connection pipe details

  • Liquid pipe: Ø9.52 mm (3/8 in.)
  • Gas pipe: Ø15.88 mm (5/8 in.)
  • Connection method: Flare

5. Fan speed, airflow and noise

ItemSpecification
Indoor fan motor modelNot specified in the provided manual
Outdoor fan motor modelNot specified in the provided manual
Outdoor fan speedCooling: upper fan 900 rpm / lower fan 800 rpm. Heating: upper fan 870 rpm / lower fan 840 rpm
Indoor airflowLow 2,450; medium 3,000; high 3,550 m³/h
Outdoor airflow6,900 m³/h in cooling and heating
Indoor sound pressure36 dB(A) low / 45 dB(A) high
Outdoor sound pressure55 dB(A) cooling / 56 dB(A) heating

6. Dimensions and weight

UnitDimensions (H × W × D)Weight
ARTG54LHTB indoor425 × 1,250 × 490 mm54 kg net / 61 kg shipping
AOTG54LATT outdoor1,290 × 900 × 330 mm104 kg net / 114 kg shipping

7. Operating range

  • Outdoor cooling: -15°C to 46°C
  • Outdoor heating: -15°C to 24°C
  • Indoor cooling: 18°C to 32°C, 80% RH or less
  • Indoor heating: 16°C to 30°C

8. Direct answers to common questions

What is the cooling capacity?
14.0 kW.
What is the heating capacity?
16.0 kW.
What are the EER and COP?
EER 3.25 kW/kW and COP 3.66 kW/kW.
Does the system support a 75 m pipe run?
Yes. The maximum pipe length is 75 m, with a maximum height difference of 30 m.
What additional refrigerant charge is required?
50 g per metre for pipe length over 30 m.
What is the indoor airflow range?
2,450-3,550 m³/h.
Source: Fujitsu General Design & Technical Manual covering ARTG36LHTB / ARTG45LHTB / ARTG54LHTB / ARTG60LHTA and AOTG36LATT / AOTG45LATT / AOTG54LATT / AOTG60LATT.