AIRSTAGE Technical Reference

ARTG45LHTB / AOTG45LATT

Matched ducted system technical specifications
Capacities, electrical data, refrigerant charge, piping limits, airflow, sound levels and dimensions
This article provides the technical specifications for the ARTG45LHTB indoor unit and its matched AOTG45LATT outdoor unit.

1. Quick answer

Indoor unitARTG45LHTB
Outdoor unitAOTG45LATT
Matched systemYes
Power supply3N ~ 415 V, 50 Hz
Cooling capacity12.5 kW
Heating capacity14.0 kW
EER / COP3.27 / 3.81 kW/kW
RefrigerantR410A
Factory charge3,450 g for up to 30 m piping
Additional charge50 g per metre over 30 m
Maximum pipe length / height75 m / 30 m

2. Model mapping and electrical specifications

Matched combination: ARTG45LHTB indoor unit with AOTG45LATT outdoor unit.
Electrical itemSpecification
PhaseThree phase and neutral
Voltage415 V
Frequency50 Hz
Available voltage range342-457 V

3. Cooling and heating performance

SpecificationCoolingHeating
Rated capacity12.5 kW14.0 kW
Capacity range5.7-14.0 kW6.0-16.2 kW
Rated power consumption3.82 kW3.67 kW
Maximum power consumption6.37 kW6.37 kW
EfficiencyEER 3.27 kW/kWCOP 3.81 kW/kW
Rated operating current5.5 A5.3 A
Maximum operating current11.0 A11.0 A
Moisture removal1.0 L/h-

4. Compressor, refrigerant and piping

Compressor

  • Type: Twin rotary x 1
  • Motor type: DC twin rotary compressor
  • Motor output: 3,750 W
  • Compressor model, weight and motor pole details: Not specified in the provided manual

Refrigerant charge

Total pipe lengthRequired refrigerant charge
Up to 30 m3,450 g factory charge
40 m4,950 g
50 m5,450 g
60 m5,950 g
70 m6,450 g
Additional charge: Add 50 g of R410A per metre when the total pipe length exceeds the 30 m pre-charge length.
  • Maximum piping length: 75 m
  • Maximum piping height: 30 m
  • Liquid pipe: Ø9.52 mm (3/8 in.)
  • Gas pipe: Ø15.88 mm (5/8 in.)
  • Connection method: Flare
  • Refrigerant oil type: POE

5. Fan speed, airflow and sound levels

ItemSpecification
Indoor fan motor modelNot specified in the provided manual
Outdoor fan motor modelNot specified in the provided manual
Outdoor fan speed - coolingUpper 850 rpm / Lower 800 rpm
Outdoor fan speed - heatingUpper 780 rpm / Lower 750 rpm
Indoor airflowLow 2,250 / Medium 2,750 / High 3,250 m³/h
Outdoor airflowCooling 6,750 / Heating 6,200 m³/h
Indoor sound pressureLow 35 / High 43 dB(A)
Outdoor sound pressureCooling 54 / Heating 54 dB(A)

6. Dimensions and weight

UnitDimensions (H x W x D)Weight
ARTG45LHTB indoor425 x 1,250 x 490 mm54 kg net / 61 kg shipping
AOTG45LATT outdoor1,290 x 900 x 330 mm104 kg net / 114 kg shipping

7. Operating range

  • Outdoor cooling range: -15°C to 46°C
  • Outdoor heating range: -15°C to 24°C
  • Indoor cooling range: 18°C to 32°C, 80% RH or less
  • Indoor heating range: 16°C to 30°C

8. Direct answers to common questions

What is the cooling capacity?
12.5 kW.
What is the heating capacity?
14.0 kW.
What are the EER and COP?
EER is 3.27 kW/kW and COP is 3.81 kW/kW.
What refrigerant does the system use?
R410A.
Can the system support a 75 m pipe run?
Yes. The maximum piping length is 75 m.
What is the additional refrigerant charge?
50 g per metre over 30 m.
What is the maximum piping height?
30 m.
What is the indoor airflow range?
2,250-3,250 m³/h.
Source: Fujitsu General Design & Technical Manual covering ARTG36LHTB / ARTG45LHTB / ARTG54LHTB / ARTG60LHTA and AOTG36LATT / AOTG45LATT / AOTG54LATT / AOTG60LATT.