AIRSTAGE Technical Reference

ARTG54LHTA / AOTG54LATL

Matched ducted system technical specifications
Performance, electrical, refrigerant, airflow, piping, dimensions and operating limits
This article provides the technical specifications for the ARTG54LHTA indoor unit and the corresponding AOTG54LATL outdoor unit. These models are designed to operate as a matched system.

1. Quick answer

Indoor unitARTG54LHTA
Outdoor unitAOTG54LATL
Matched systemYes
Power supplySingle phase, 240 V, 50 Hz
Cooling capacity14.0 kW
Heating capacity16.0 kW
EER / COP3.00 / 3.60 kW/kW
RefrigerantR410A
Maximum piping50 m length / 30 m height

2. Model mapping and electrical specifications

ItemSpecification
Indoor unitARTG54LHTA
Outdoor unitAOTG54LATL
Power phaseSingle phase
Voltage / frequency240 V / 50 Hz
Available voltage range198-264 V

3. Cooling and heating performance

SpecificationCoolingHeating
Rated capacity14.0 kW16.0 kW
Capacity range6.2-15.2 kW6.2-18.0 kW
Rated power consumption4.66 kW4.44 kW
Maximum power consumption5.63 kW5.63 kW
EfficiencyEER 3.00 kW/kWCOP 3.60 kW/kW
Rated operating current19.5 A18.6 A
Maximum operating current23.5 A23.5 A
Moisture removal1.0 L/h-
Direct answer: The EER of the ARTG54LHTA is 3.00 kW/kW.

4. Compressor, refrigerant and piping

Compressor

  • Type: Twin rotary x 1
  • Motor output: 2,100 W
  • Compressor model, weight and motor pole details: Not specified in the provided manual

Refrigerant charge

Total pipe lengthRequired charge
Up to 20 m3,350 g
30 m3,750 g
40 m4,150 g
50 m4,550 g
  • Refrigerant: R410A
  • Pre-charge length: 20 m
  • Additional charge: 40 g per metre over 20 m
  • Maximum pipe length: 50 m
  • Maximum height difference: 30 m
  • Refrigerant oil type: RB
  • Liquid pipe: Ø9.52 mm (3/8 in.)
  • Gas pipe: Ø15.88 mm (5/8 in.)
  • Connection method: Flare
Important: Confirm the actual installed pipe length before calculating additional refrigerant. The factory charge covers a total pipe length of up to 20 m.

5. Fan speed, airflow and noise

ItemSpecification
Indoor fan motor modelNot specified in the provided manual
Outdoor fan motor modelNot specified in the provided manual
Indoor airflowLow 2,450 / Medium 3,000 / High 3,550 m³/h
Outdoor airflowCooling 6,750 / Heating 6,850 m³/h
Outdoor fan speed - coolingUpper 850 rpm / Lower 800 rpm
Outdoor fan speed - heatingUpper 850 rpm / Lower 830 rpm
Indoor sound pressure36 dB(A) low / 45 dB(A) high
Outdoor sound pressure55 dB(A) cooling / 56 dB(A) heating

6. Dimensions and weight

UnitDimensions (H x W x D)Net / shipping weight
ARTG54LHTA indoor425 x 1,250 x 490 mm54 / 61 kg
AOTG54LATL outdoor1,290 x 900 x 330 mm86 / 95 kg

7. Operating range

ConditionRange
Outdoor cooling-5°C to 46°C
Outdoor heating-15°C to 24°C
Indoor cooling18°C to 32°C, 80% RH or less
Indoor heating16°C to 30°C

8. Direct answers to common questions

What is the cooling capacity?
14.0 kW.
What is the heating capacity?
16.0 kW.
What are the EER and COP?
EER is 3.00 kW/kW and COP is 3.60 kW/kW.
What refrigerant is used?
R410A.
Does the system support a 50 m pipe run?
Yes. The maximum total piping length is 50 m.
What additional refrigerant charge is required?
40 g per metre for pipe length over 20 m.
What is the maximum piping height?
30 m.
What is the indoor airflow range?
2,450-3,550 m³/h.
Source: Fujitsu General Design & Technical Manual covering ARTG30LHTA / ARTG36LHTA / ARTG45LHTA / ARTG54LHTA and AOTG30LATL / AOTG36LATL / AOTG45LATL / AOTG54LATL.