1. Quick answer

Indoor unitARTG45LHTA
Outdoor unitAOTG45LATL
Matched systemYes
Power supplySingle phase, 240 V, 50 Hz
Cooling / heating capacity12.5 kW / 14.0 kW
EER / COP3.10 / 3.68 kW/kW
RefrigerantR410A
Factory charge3,350 g for up to 20 m total piping
Additional charge40 g per metre over 20 m
Maximum piping length / height50 m / 30 m

2. Model mapping and electrical specifications

SpecificationValue
Indoor unitARTG45LHTA
Outdoor unitAOTG45LATL
Power supplySingle phase, 240 V, 50 Hz
Available voltage range198-264 V

3. Cooling and heating performance

SpecificationCoolingHeating
Rated capacity12.5 kW14.0 kW
Capacity range5.7-14.0 kW6.0-16.0 kW
Rated power consumption4.03 kW3.80 kW
Maximum power consumption5.38 kW5.38 kW
EfficiencyEER 3.10 kW/kWCOP 3.68 kW/kW
Rated operating current16.9 A16.0 A
Maximum operating current22.5 A22.5 A
Moisture removal1.0 L/hNot applicable
Direct answer: The EER of the ARTG45LHTA matched system is 3.10 kW/kW.

4. Compressor, refrigerant and piping

Compressor

  • Type: Twin rotary x 1
  • Motor output: 2,100 W
  • Compressor model, weight and motor pole details: Not specified in the provided manual

Refrigerant charge

Total pipe lengthRequired refrigerant charge
Up to 20 m3,350 g factory charge
30 m3,750 g
40 m4,150 g
50 m4,550 g
  • Refrigerant: R410A
  • Additional charge rate: 40 g per metre over 20 m
  • Maximum piping length: 50 m
  • Maximum piping height: 30 m
  • Pre-charge length: 20 m
  • Refrigerant oil type: RB
  • Liquid pipe: 9.52 mm (3/8 in.)
  • Gas pipe: 15.88 mm (5/8 in.)
  • Connection method: Flare
Important: Refrigerant charging and piping work must be completed by appropriately qualified personnel in accordance with the installation instructions and applicable regulations.

5. Fan speed, airflow and noise

ItemValue
Indoor airflow - Low2,250 m³/h
Indoor airflow - Medium2,750 m³/h
Indoor airflow - High3,250 m³/h
Outdoor airflow - Cooling6,750 m³/h
Outdoor airflow - Heating6,200 m³/h
Outdoor fan speed - CoolingUpper 850 rpm / Lower 800 rpm
Outdoor fan speed - HeatingUpper 780 rpm / Lower 750 rpm
Indoor sound pressure36 dB(A) low / 45 dB(A) high
Outdoor sound pressure55 dB(A) cooling / 55 dB(A) heating

Indoor and outdoor fan motor model numbers, and indoor fan rpm values, are not specified in the provided manual.

6. Dimensions and weight

UnitDimensions (H x W x D)Weight
ARTG45LHTA indoor425 x 1,250 x 490 mm54 kg net / 61 kg shipping
AOTG45LATL outdoor1,290 x 900 x 330 mm86 kg net / 95 kg shipping

7. Operating range

ConditionOperating range
Outdoor cooling-5°C to 46°C
Outdoor heating-15°C to 24°C
Indoor cooling18°C to 32°C, 80% RH or less
Indoor heating16°C to 30°C

8. Direct answers to common questions

What is the cooling capacity?
12.5 kW.

What is the heating capacity?
14.0 kW.

What is the EER?
3.10 kW/kW.

What is the COP?
3.68 kW/kW.

What refrigerant does the system use?
R410A.

Can the system support a 50 m pipe run?
Yes. The maximum total piping length is 50 m.

What is the additional refrigerant charge?
40 g per metre for piping over the 20 m pre-charge length.

What is the maximum piping height?
30 m.

What is the indoor airflow range?
2,250-3,250 m³/h.

What are the indoor and outdoor noise levels?
Indoor: 36 dB(A) low and 45 dB(A) high. Outdoor: 55 dB(A) in cooling and heating.