AIRSTAGE Technical Reference

ARTG36LHTA / AOTG36LATL

Matched system technical specifications
Indoor unit ARTG36LHTA with outdoor unit AOTG36LATL
This article provides the key electrical, performance, refrigerant, airflow, noise, dimensional and piping specifications for the ARTG36LHTA indoor unit and its matched AOTG36LATL outdoor unit.

1. Quick answer

Indoor unitARTG36LHTA
Outdoor unitAOTG36LATL
Matched systemYes
Power supplySingle phase, 240 V, 50 Hz
Cooling / heating capacity10.5 kW / 12.1 kW
EER / COP3.30 / 3.67 kW/kW
RefrigerantR410A
Factory charge3,350 g for up to 20 m total piping
Additional charge40 g per metre over 20 m
Maximum piping50 m length / 30 m height

2. Model mapping and electrical specifications

System match: ARTG36LHTA and AOTG36LATL are designed to operate together as a matched system.
Electrical itemSpecification
PhaseSingle phase
Voltage240 V
Frequency50 Hz
Available voltage range198-264 V

3. Cooling and heating performance

SpecificationCoolingHeating
Rated capacity10.5 kW12.1 kW
Capacity range5.0-11.4 kW5.1-14.0 kW
Rated power consumption3.18 kW3.30 kW
Maximum power consumption4.67 kW4.80 kW
EfficiencyEER 3.30 kW/kWCOP 3.67 kW/kW
Rated operating current13.4 A13.9 A
Maximum operating current19.6 A20.1 A

Moisture removal in cooling: 1.5 L/h.

4. Compressor and refrigerant details

Compressor

  • Type: Twin rotary x 1
  • Motor output: 2,100 W
  • Compressor model, compressor weight and motor pole details: Not specified in the provided manual

Refrigerant charge

Total pipe lengthRequired charge
Up to 20 m3,350 g
30 m3,750 g
40 m4,150 g
50 m4,550 g
  • Refrigerant: R410A
  • Additional charge rate: 40 g per metre over 20 m
  • Pre-charge length: 20 m
  • Maximum piping length: 50 m
  • Maximum piping height: 30 m
  • Refrigerant oil type: RB

5. Fan speed, airflow and noise

Manual limitation: Indoor and outdoor fan motor model numbers are not specified in the provided manual. Indoor fan speed is also not stated in rpm.
ItemSpecification
Outdoor fan speed - coolingUpper fan 780 rpm / lower fan 750 rpm
Outdoor fan speed - heatingUpper fan 780 rpm / lower fan 750 rpm
Indoor airflowLow 1,750 / medium 2,100 / high 2,500 m³/h
Outdoor airflow6,200 m³/h in cooling and heating
Indoor sound pressure35 dB(A) low / 43 dB(A) high
Outdoor sound pressure52 dB(A) cooling / 54 dB(A) heating

6. Dimensions, weight and pipe connections

UnitDimensions (H x W x D)Weight
ARTG36LHTA indoor400 x 1,050 x 500 mm39 kg net / 46 kg shipping
AOTG36LATL outdoor1,290 x 900 x 330 mm86 kg net / 95 kg shipping
  • Liquid pipe: Ø9.52 mm (3/8 in.)
  • Gas pipe: Ø15.88 mm (5/8 in.)
  • Connection method: Flare

7. Operating range

Mode / locationOperating range
Outdoor - cooling-5°C to 46°C
Outdoor - heating-15°C to 24°C
Indoor - cooling18°C to 32°C, 80% RH or less
Indoor - heating16°C to 30°C

8. Direct answers to common questions

What is the cooling capacity?
10.5 kW.

What is the heating capacity?
12.1 kW.

What are the EER and COP?
EER is 3.30 kW/kW and COP is 3.67 kW/kW.

What refrigerant does the system use?
R410A.

Does the system support a 50 m pipe run?
Yes. The maximum total piping length is 50 m.

What is the additional refrigerant charge?
40 g per metre over 20 m.

What is the maximum piping height?
30 m.

What is the indoor airflow range?
1,750-2,500 m³/h.

What are the sound pressure levels?
Indoor: 35 dB(A) low and 43 dB(A) high. Outdoor: 52 dB(A) cooling and 54 dB(A) heating.

Source: Fujitsu General Design & Technical Manual covering ARTG30LHTA / ARTG36LHTA / ARTG45LHTA / ARTG54LHTA and AOTG30LATL / AOTG36LATL / AOTG45LATL / AOTG54LATL.