AIRSTAGE Technical Reference

ARTG30LHTA / AOTG30LATL

Matched ducted system technical specifications
Capacities, electrical data, refrigerant charge, piping limits, airflow, sound levels and dimensions
This article provides the technical specifications for the ARTG30LHTA indoor unit and its matched AOTG30LATL outdoor unit.

1. Quick answer

Indoor unitARTG30LHTA
Outdoor unitAOTG30LATL
Matched systemYes
Power supplySingle phase, 240 V, 50 Hz
Cooling capacity9.0 kW
Heating capacity11.2 kW
EER / COP3.33 / 3.80 kW/kW
RefrigerantR410A
Factory charge3,350 g for up to 20 m piping
Additional charge40 g per metre over 20 m
Maximum pipe length / height50 m / 30 m

2. Model mapping and electrical specifications

Matched combination: ARTG30LHTA indoor unit with AOTG30LATL outdoor unit.
Electrical itemSpecification
PhaseSingle phase
Voltage240 V
Frequency50 Hz
Available voltage range198-264 V

3. Cooling and heating performance

SpecificationCoolingHeating
Rated capacity9.0 kW11.2 kW
Capacity range4.7-10.0 kW5.0-12.1 kW
Rated power consumption2.70 kW2.95 kW
Maximum power consumption4.30 kW4.30 kW
EfficiencyEER 3.33 kW/kWCOP 3.80 kW/kW
Rated operating current11.4 A12.4 A
Maximum operating current18.1 A18.1 A
Moisture removal1.0 L/h-

4. Compressor, refrigerant and piping

Compressor

  • Type: Twin rotary x 1
  • Motor output: 2,100 W
  • Compressor model, weight and motor pole details: Not specified in the provided manual

Refrigerant charge

Total pipe lengthRequired refrigerant charge
Up to 20 m3,350 g factory charge
30 m3,750 g
40 m4,150 g
50 m4,550 g
Additional charge: Add 40 g of R410A per metre when the total pipe length exceeds the 20 m pre-charge length.
  • Maximum piping length: 50 m
  • Maximum piping height: 30 m
  • Liquid pipe: Ø9.52 mm (3/8 in.)
  • Gas pipe: Ø15.88 mm (5/8 in.)
  • Connection method: Flare
  • Refrigerant oil type: RB

5. Fan speed, airflow and sound levels

ItemSpecification
Indoor fan motor modelNot specified in the provided manual
Outdoor fan motor modelNot specified in the provided manual
Outdoor fan speed - coolingUpper 750 rpm / Lower 700 rpm
Outdoor fan speed - heatingUpper 720 rpm / Lower 700 rpm
Indoor airflowLow 1,750 / Medium 2,100 / High 2,500 m³/h
Outdoor airflowCooling 5,950 / Heating 5,800 m³/h
Indoor sound pressureLow 36 / High 41 dB(A)
Outdoor sound pressureCooling 52 / Heating 53 dB(A)

6. Dimensions and weight

UnitDimensions (H x W x D)Weight
ARTG30LHTA indoor400 x 1,050 x 500 mm39 kg net / 46 kg shipping
AOTG30LATL outdoor1,290 x 900 x 330 mm86 kg net / 95 kg shipping

7. Operating range

  • Outdoor cooling range: -5°C to 46°C
  • Outdoor heating range: -15°C to 24°C
  • Indoor cooling range: 18°C to 32°C, 80% RH or less
  • Indoor heating range: 16°C to 30°C

8. Direct answers to common questions

What is the cooling capacity?
9.0 kW.
What is the heating capacity?
11.2 kW.
What are the EER and COP?
EER is 3.33 kW/kW and COP is 3.80 kW/kW.
What refrigerant does the system use?
R410A.
Can the system support a 50 m pipe run?
Yes. The maximum piping length is 50 m.
What is the additional refrigerant charge?
40 g per metre over 20 m.
What is the maximum piping height?
30 m.
What is the indoor airflow range?
1,750-2,500 m³/h.
Source: Fujitsu General Design & Technical Manual covering ARTG30LHTA / ARTG36LHTA / ARTG45LHTA / ARTG54LHTA and AOTG30LATL / AOTG36LATL / AOTG45LATL / AOTG54LATL.