General Assist Technical Reference
ARTG12LLLB & AOTG12LBCA / AOTG12LBCB
Matched ducted system technical specifications
Indoor unit: ARTG12LLLB | Outdoor units: AOTG12LBCA or AOTG12LBCB | Refrigerant: R410A
This article provides the principal performance, electrical, dimensional, airflow, noise and refrigerant specifications for the ARTG12LLLB indoor unit and its matched AOTG12LBCA or AOTG12LBCB outdoor unit.
1. Quick answer
| Indoor unit model | ARTG12LLLB |
| Outdoor unit model | AOTG12LBCA or AOTG12LBCB |
| Matched system | Yes |
| Power supply | Single phase, 240 V, 50 Hz |
| Cooling capacity | 3.50 kW |
| Heating capacity | 4.50 kW |
| EER / COP | 3.72 / 3.78 kW/kW |
| Refrigerant | R410A |
| Maximum pipe length / height | 20 m / 15 m |
2. Electrical and performance specifications
Electrical supply
| Item | Specification |
|---|---|
| Supply | 240 V, single phase, 50 Hz |
| Available voltage range | 198–264 V |
| Maximum operating current | 10.9 A |
| Starting current | 5.3 A |
| Manual circuit-breaker reference | AOTG12LBCA: 15 A; AOTG12LBCB: 16 A — confirm all wiring and protection against current local requirements |
| Manual power-cable reference | AOTG12LBCA: 3.5 mm²; AOTG12LBCB: 2.5 mm². Connection cable: 1.5 mm². Apply current local wiring rules. |
3. Compressor, refrigerant and piping
| Item | Specification |
|---|---|
| Compressor | DC twin rotary × 1 |
| Compressor motor output | 850 W |
| Refrigerant | R410A |
| Factory charge | 1,200 g for pipe length up to 15 m |
| Additional charge | 20 g per metre over 15 m |
| Maximum pipe length | 20 m |
| Maximum height difference | 15 m |
| Liquid / gas pipe | Ø6.35 mm (1/4 in.) / Ø9.52 mm (3/8 in.), flare connection |
| Refrigerant oil | FREOL α68SZ, 350 cm³ |
Refrigerant charging: The factory charge covers up to 15 m total pipe length. Add 20 g per metre beyond 15 m, equivalent to 100 g at the maximum 20 m pipe length.
4. Fan, airflow and sound levels
| Fan setting | Indoor airflow | Equivalent |
|---|---|---|
| Quiet | 480 m³/h | 133 L/s / 283 CFM |
| Low | 550 m³/h | 153 L/s / 324 CFM |
| Medium | 600 m³/h | 167 L/s / 353 CFM |
| High | 650 m³/h | 181 L/s / 383 CFM |
| Sound / outdoor airflow | Cooling | Heating |
|---|---|---|
| Indoor sound pressure | 26 dB(A) quiet / 29 dB(A) high | 24 dB(A) quiet / 29 dB(A) high |
| Outdoor sound pressure | 49 dB(A) | 49 dB(A) |
| Outdoor airflow | 2,050 m³/h | 1,840 m³/h |
Specified sound-pressure levels are laboratory values measured in an anechoic chamber. Actual installed sound levels may be higher due to the surrounding environment, ductwork and mounting conditions.
5. Dimensions and weights
| Unit | Net dimensions (H × W × D) | Shipping dimensions | Weight |
|---|---|---|---|
| ARTG12LLLB indoor | 198 × 700 × 620 mm | 274 × 945 × 772 mm | 18 kg net / 22 kg gross |
| AOTG12LBCA / AOTG12LBCB outdoor | 620 × 790 × 290 mm | 713 × 945 × 395 mm | 39 kg net / 42 kg gross |
6. Operating range
| Condition | Range |
|---|---|
| Outdoor cooling | -10°C to 46°C |
| Outdoor heating | -15°C to 24°C |
| Indoor cooling | 18°C to 32°C, 80% RH or less |
| Indoor heating | 16°C to 30°C |
7. Direct answers to common questions
Source: Fujitsu General Design & Technical Manual DR_AR007EF_05, dated 29 May 2020. Specifications and designs may change without notice. Confirm current installation instructions and local electrical requirements before installation or service work.