General Assist Technical Reference
AOTA72LALT / AOTA90LALT - Intermittent Error 13
Communication fault diagnosis and field troubleshooting
Use this workflow where Error 13 occurs intermittently and basic continuity or insulation-resistance checks do not identify a permanent fault.
Applies to: AOTA72LALT and AOTA90LALT
Safety: Isolate power before handling wiring or PCB connections. Follow site lock-out/tag-out requirements and confirm the circuit is safe before commencing inspection or electrical testing.
1. Symptom / complaint
- Unit presents Error 13 intermittently with no consistent time pattern. The fault may occur after hours, days, or within minutes.
- Error may persist despite replacement of the indoor PCB(s) and outdoor control PCB.
- Basic cable checks may appear acceptable, including continuity and insulation-resistance tests, while the fault continues.
What Error 13 typically indicates: Communication instability between the indoor and outdoor units, and/or between indoor PCBs where applicable. With intermittent faults, the cause is frequently an intermittent connection, moisture ingress, or cable-integrity issue that only appears under load, vibration, movement, or changing environmental conditions.
2. Most common root causes
2.1 Interconnect cable or joint issues
- Water in a junction box, trunking join, or corrugated conduit can create intermittent leakage or voltage instability.
- Field examples include cuts or nicks across neutral and signal conductors, conduit containing water, and junctions concealed in walls or roof spaces.
2.2 Loose or fatigued indoor harness connections
- PCB-to-PCB harnesses can become marginal due to loose pins, partial engagement, pin back-out, poor crimping, or conductor breakage near strain relief.
2.3 Conductor damage not detected by static testing
- Continuity and insulation-resistance tests can pass while the cable is stationary and de-energised. Under vibration or thermal movement, damaged conductors can open or short momentarily.
2.4 Associated indoor electrical-load instability
- Indoor fan motor(s) operating outside specification may introduce abnormal load conditions or interference.
- Capacitor or DC-bus stability can be checked as an advanced diagnostic only where the correct method, tooling, and competency are available.
3. Diagnostic workflow - recommended order
Step 1 - Visual and physical inspection
- Inspect the indoor-outdoor interconnect at both terminal points for loose screws, stray strands, heat discolouration, corrosion, or green copper oxide.
- Inspect every junction point between the indoor and outdoor units, including roof-space junction boxes, trunking joins, conduit transitions, and concealed wall cavities.
- Ask the installer whether any concealed joints exist along the cable path.
- With power isolated, gently tug each conductor at plug and terminal entries to identify an internal break at the clamp or strain-relief point.
High-yield check: Damaged conductors and corroded joints can fail intermittently under vibration or load even when static checks appear normal.
Step 2 - Reseat and secure indoor harness connections
- Locate all indoor PCB-to-PCB harnesses.
- Unplug and reconnect each connector fully. Confirm positive engagement and locking-tab operation.
- Inspect pins for spread terminals, pin push-back, oxidation, poor crimps, and conductor damage.
- If available, substitute a known-good harness to validate the connection.
Step 3 - Check communication voltages
Measure and record DC communication voltage at both ends of the interconnect and at the cable/termination points.
| Measurement point | Example field reading |
|---|---|
| Outdoor terminal 2-3 | Approximately 20-101 VDC |
| Outdoor terminal 2 and cable | Approximately 52-61 VDC |
| Indoor terminal 2-3 | Approximately 88-121 VDC |
| Indoor terminal 2 and cable | Approximately 117-131 VDC |
Interpretation: Wide voltage fluctuation may occur depending on system state, but instability that correlates with the fault is significant. A difference between terminal measurements and terminal-plus-cable measurements may indicate a termination, contact, cable, or junction anomaly. The values above are field examples only - always record the actual readings found on site.
Step 4 - Prove or disprove the interconnect cable
If the interconnect is concealed inside a wall or cannot be easily replaced, run a temporary surface interconnect between the indoor and outdoor units where safe and approved.
- If Error 13 stops, treat the interconnect cable path, junctions, moisture ingress, or conductor damage as the likely root cause even if previous continuity and insulation-resistance tests passed.
- Return the issue to the installer to locate and rectify concealed junctions or replace the cable correctly.
Important: A static insulation-resistance test may not reveal a moisture-related fault that only appears under operating voltage, load, vibration, temperature change, or environmental conditions.
Step 5 - Secondary checks
- Indoor fan motor(s): Confirm correct operation and check for abnormal current draw or intermittent stalling.
- Capacitor / DC bus stability: Perform only when the cable and harnesses have been proven sound and the technician has the correct procedure, tooling, and competency.
4. Corrective actions based on findings
| Finding | Corrective action |
|---|---|
| Moisture or junction issue | Dry out, remake joints, re-terminate, replace corroded components, improve sealing/IP protection, and reroute wiring to avoid water traps. |
| Cable damage | Replace the interconnect run end-to-end where possible. Avoid concealed joints. |
| Loose harness or plug | Replace the harness or repair terminal/pin seating. Confirm strain relief and secure routing. |
| Temporary cable proves building wiring fault | Return to the installer to rectify concealed junctions, trunking/conduit water ingress, and replace the affected cable. |
5. Technician case documentation
Record the following before closing or escalating the case:
- Frequency and pattern of Error 13 occurrences.
- Whether indoor or outdoor PCB(s) were replaced, including part numbers if available.
- Communication voltages measured at outdoor terminal 2-3, outdoor terminal 2 and cable, indoor terminal 2-3, and indoor terminal 2 and cable.
- Confirmation of any junction boxes or hidden joins along the interconnect path.
- Result of the temporary interconnect test - Pass or Fail.
Technical reference for General Assist. Always use the applicable service documentation and site electrical-safety requirements when carrying out diagnosis.