General Assist Technical Reference

Serial Communication Voltage Test

Terminal 2 (Neutral) to Terminal 3 (Signal)
This test confirms whether the DC serial communication signal is present between the indoor and outdoor units.

Quick Answer

Test pointsTerminal 2 (Neutral) to Terminal 3 (Signal)
ToolDigital multimeter capable of AC/DC voltage measurement

Expected Indoor Values

Indoor Unit FamilyExpected Voltage - Terminal 2 to 3
AST & ART/C60-120 V
ASTA & ASTB40-90 V
ASTGApproximately 200 V static
ARTG & 3-phaseApproximately 295 V static
ARTH50-250 V

Expected Outdoor Values

Outdoor Unit FamilyExpected Voltage - Terminal 2 to 3
AOTA60-120 V
AOTG3-110 V
AOTH3-110 V

What is This Test?

This is a voltage test used to confirm that the DC serial communication signal exists between the indoor and outdoor unit.

Tools Required

  • Digital multimeter capable of measuring AC and DC voltage

Procedure

  1. Disconnect the signal wire.
  2. Measure voltage between Terminal 2 (N) and Terminal 3 (Signal) at the indoor terminal block.
  3. Measure the same points at the outdoor terminal block.
  4. Record whether the voltage is stable, fluctuating, or absent.
Electrical safety: This test involves live electrical measurements. Only suitably qualified personnel should perform the test, using appropriate electrical safety procedures and test equipment.

Reference Images

Serial communication voltage test reference image 1

Serial communication voltage test reference image 2

Pass Criteria

The measured voltage is within the applicable range listed above for the indoor or outdoor unit family being tested.

If the Test Fails

ResultAction
Indoor has signal, outdoor does notInspect and repair the signal wiring and terminations. Proceed to DC bus and supply-rail checks to rule out outdoor PCB resets.
Neither end has signalTreat as a wiring or termination issue first. Confirm the correct terminals and repair or replace the interconnect if damaged.
Signal unstable / intermittentTreat as a possible PCB reset or supply-rail collapse. Isolate loads using a staged reconnect test.
Diagnostic note: Compare both ends of the communication circuit. The difference between the indoor and outdoor readings can help separate a wiring fault from a PCB or supply-related problem.