Outdoor communication fault — proven method to isolate PCB vs. connected components
Objective
A communication fault can be caused by:
- Signal wiring/terminal issues
- Controller PCB power instability (resets)
- A connected component dragging down a DC rail (5 V / 12 V / 15 V or the HV DC bus)
- Inverter/IPM failure affecting DC bus stability
The method below proves each section logically and safely.
1) Confirm the communication circuit first
1.1 Signal voltage test (Indoor ↔ Outdoor)
Measure between Terminal 2 (Neutral) and Terminal 3 (Signal).
Use these expected signal voltage ranges (platform-dependent):
Indoor signal expected:
- AST & ART/C: 60–120 V
- ASTA & ASTB: 40–90 V
- ASTG: ~200 V static
- ARTG & 3-phase: ~295 V static
- ARTH: 50–250 V
Outdoor signal expected:
- AOTA: 60–120 V
- AOTG: 3–110 V
- AOTH: 3–110 V
Interpretation
- Indoor signal present but outdoor absent → outdoor comm circuit / outdoor PCB supply stability / load pulling rails down.
- Neither end shows signal → wiring/polarity/termination/supply issue first.
2) Verify controller PCB power environment (before condemning it)
2.1 Main DC power input to PCB
Confirm stable DC 330–370 V present as the DC power supply feeding the main PCB/inverter system.
Instability here often presents as:
- Repeated resets
- Intermittent comms
- Random fault codes
2.2 Expected supply rails by load (critical for “PCB being dragged down”)
Use these expected rail values:
- Outdoor fan HV supply (DC motors): 330–370 V DC (Red–Black)
- Outdoor fan control supply: 15 V DC (White–Black)
- Thermistors: 5 V DC
- Pressure transducer: 5 V DC
- EEV coil: 12 V DC
- Reversing valve solenoid coil: 240 V AC (energised on heat mode)
3) Component integrity checks (power OFF unless specified)
3.1 Thermistors
Power ON (best for proving the PCB 5 V rail)
Reference DC ground (typically fan motor Black / DC negative).
- One pin will show 5 V DC supply
- The other pin will show a return voltage less than 5 V
Power OFF
- Check resistance is plausible (not open circuit / not short)
- Also check for short to earth (any sensor short to earth can damage or destabilise the controller)
3.2 EEV coil (DC)
5-wire EEV coil (12 V) — Resistance power OFF
- Red to each other wire: 45–50 Ω
- Each wire to earth: O/L
6-wire EEV coil (12 V) — Resistance power OFF
- Red to White/Orange: 45–50 Ω
- Brown to Yellow/Blue: 45–50 Ω
- All wires to earth: O/L
Practical note: check for corrosion under the coil and ensure it is correctly seated/clipped.
3.3 Pressure transducer (5 V DC)
Power ON
- Red to Black: 5 V DC supply
- Black to White:varying return voltage used to calculate pressure
- Rule of thumb example: 2.8 V ≈ 2875 kPa
Power OFF (diode test approach)
- Use the specified diode patterns for the sensor (and confirm earth = O/L). Any short to earth or abnormal diode pattern points to sensor or harness fault.
3.4 Fan motors (AC or DC)
If DC BLDC fan (multi-wire: red/black/white + signals)
Key expected values (power ON):
- Red–Black: 330–380 V DC
- White–Black: 15 V DC
Power OFF diode test (typical pattern):
- Meter Red lead → Black lead: O/L
- Meter Red lead → White lead: 0.5–1.8 V
- Meter Black lead → Red lead: 0.8–1.1 V
- Meter Black lead → White lead: 0.4–0.6 V
Important: Do not disconnect or reconnect fan plugs with power applied.
If AC fan motor
- Check winding resistance isn’t open/short
- Insulation to earth should be very high (megger if permitted)
3.5 Compressor (DC inverter)
Winding balance (power OFF)
- U–V, V–W, U–W should be equal-ish
- Typical total winding resistance is ~0.3–2.0 Ω depending on unit and temperature (10–25°C)
Insulation to earth
- Each winding to earth must be > 1 MΩ
Any imbalance or earth leakage can crash the inverter stage and indirectly cause comms faults.
4) Power electronics checks (power OFF)
4.1 IPM / Inverter module diode checks (typical expected readings)
- P to U/V/W: 0.4 V
- U/V/W to N: 0.4 V
- P to N: 0.7–0.9 V
- N to P: O/L
A failed IPM can cause DC bus instability and comm dropouts.
4.2 Diode bridge (rectifier) diode checks
- + to ~: 0.4 V
- ~ to –: 0.4 V
- + to –: 0.7–0.9 V
- – to +: O/L
5) The staged reconnect test (fastest way to find the culprit)
This is the most reliable “all components must be checked” approach.
Step 1 — Start with high-risk loads unplugged
Power up with these disconnected:
- Compressor (U/V/W)
- Fan motors
- EEV coil
Confirm:
- DC bus stable 330–370 V
- 5 V sensor rail behaves normally (thermistors + transducer plausible)
- Signal voltage between N and Signal is present and within expected band
Step 2 — Reconnect in this order
- Thermistors + pressure transducer
- EEV coil
- Fan motor 1
- Fan motor 2
- Compressor (last)
If comms drop immediately after a particular reconnection, that circuit/load/harness is pulling down a rail or introducing instability.
6) Quick mapping to your component types
- Fans: If multi-wire, treat as DC BLDC and confirm 330–380 V DC supply + 15 V DC control rail.
- Compressor (DC): confirm balanced low-ohm windings and >1 MΩ insulation; then IPM diode test.
- EEV (DC): confirm 45–50 Ω coil legs and O/L to earth.
- Solenoid coil (AC): confirm correct 240 V AC switching in heat mode and that coil isn’t open/short.