Legacy R22 Specifications - ABT14RBA-W / ABT18RBA-W / ABT24RBA-W

This article provides technical specifications for the following matched systems:

  • ABT14RBA-W indoor with AOT14RGJ outdoor
  • ABT18RBA-W indoor with AOT18RNEL outdoor
  • ABT24RBA-W indoor with AOT24RNFL outdoor
Quick Comparison
SystemCoolingHeatingEERRefrigerant
ABT14RBA-W / AOT14RGJ4.05 kW5.00 kW2.30 W/WR22
ABT18RBA-W / AOT18RNEL5.30 kW5.60 kW2.78 W/WR22
ABT24RBA-W / AOT24RNFL6.70 kW8.00 kW2.53 W/WR22

ABT14RBA-W / AOT14RGJ

SpecificationValue
Cooling capacity4.05 kW
Heating capacity5.00 kW
Input power - Cooling1,760 W
Running current - Cooling8.0 A
EER2.30 W/W
Moisture removal2.0 L/hr
Power supplySingle phase, 240 V (220 V), 50 Hz
Compressor typeHermetic, permanent split condenser, 2 pole, single phase induction motor, rotary
Compressor codeQJ282PC24A
RefrigerantR22
Listed refrigerant charge1,900 g
Indoor fan motorMFA-14JTT
Indoor fan speed - High / Medium / Low1,030 / 890 / 770 rpm
Indoor airflow - High800 m³/hr
Indoor dimensions199 x 990 x 655 mm
Indoor weight30 kg net / 39 kg gross
Outdoor dimensions530 x 750 x 250 mm
Outdoor weight38 kg net / 40 kg gross

Refrigerant Charge by Pipe Length

Pipe LengthFull Charge
5 m1,900 g
7.5 m2,000 g
10 m2,200 g
15 m2,400 g

Additional charge guidance: 30 g per metre where applicable beyond the stated base piping criteria.

ABT18RBA-W / AOT18RNEL

SpecificationValue
Cooling capacity5.30 kW
Heating capacity5.60 kW
Input power - Cooling1,910 W
Running current - Cooling7.4 A
EER2.78 W/W
Moisture removal1.6 L/hr
Power supplySingle phase, 240 V (220 V), 50 Hz
Compressor typeHermetic, permanent split condenser, 2 pole, single phase induction motor, rotary
Compressor code2JS318D5BA02
RefrigerantR22
Listed refrigerant charge2,200 g
Indoor fan motorMFA-18JTT
Indoor fan speed - High / Medium / Low850 / 760 / 670 rpm
Indoor airflow - High640 m³/hr
Indoor dimensions199 x 990 x 655 mm
Indoor weight30 kg net / 39 kg gross
Outdoor dimensions643 x 840 x 336 mm
Outdoor weight68 kg net / 76 kg gross

Refrigerant Charge by Pipe Length

Pipe LengthFull Charge
5 m2,200 g
7.5 m2,315 g
10 m2,430 g
15 m2,660 g
20 m2,900 g

Additional charge guidance: 40 g per metre where applicable beyond the stated base piping criteria.

ABT24RBA-W / AOT24RNFL

SpecificationValue
Cooling capacity6.70 kW
Heating capacity8.00 kW
Input power - Cooling2,690 W
Running current - Cooling12.8 A
EER2.53 W/W
Moisture removal3.4 L/hr
Power supplySingle phase, 240 V (220 V), 50 Hz
Compressor typeHermetic, permanent split condenser, 2 pole, single phase induction motor, rotary
Compressor code2JS438D5BA02
RefrigerantR22
Listed refrigerant charge1,100 g
Indoor fan motorMFA-24JTT
Indoor fan speed - High / Medium / Low1,180 / 1,040 / 900 rpm
Indoor airflow - High900 m³/hr
Indoor dimensions199 x 990 x 655 mm
Indoor weight30 kg net / 39 kg gross
Outdoor dimensions700 x 900 x 350 mm
Outdoor weight71 kg net / 82 kg gross

Refrigerant Charge by Pipe Length

Pipe LengthFull Charge
5 m1,100 g
7.5 m1,175 g
10 m1,250 g

Additional charge guidance: 46 g per metre where applicable beyond the stated base piping criteria.

Legacy refrigerant note: These systems use R22. Refrigerant availability, servicing and replacement options may be restricted by current regulatory requirements. Use the applicable local regulations and service policy when planning repairs.