1. Quick summary
ItemDetail
Product nameARTG60LHTA
Product categoryHigh Static Three Phase
Operation typeReverse cycle
Cooling capacity15.00 kW rated
Heating capacity18.00 kW rated
Static pressure range60–260 Pa
Cooling operating range-15 to 46°C DB
Heating operating range-15 to 24°C DB
2. Technical specifications
SpecificationValue
Power supply400 V / 3 Ph / 50 Hz
Cooling capacity - Rated / Min–Max15.00 kW / 6.2–17.5 kW
Heating capacity - Rated / Min–Max18.00 kW / 6.2–20.0 kW
Input power - Cooling rated / max4.70 kW / 7.40 kW
Input power - Heating rated / max5.15 kW / 7.40 kW
EER / COP3.30 / 3.144
Running current - Cooling / Heating6.7 A / 7.3 A
Moisture removal2.0 L/h
Indoor sound pressure - High / Quiet45 / 36 dBA
Outdoor sound pressure - Cooling / Heating56 / 58 dBA
Outdoor sound power71 dBA
Indoor air circulation - High fan986 L/s cooling and heating
Refrigerant charge3,450 g R410A
Maximum pipe length / pre-charge75 m / 30 m
Maximum height difference30 m
Piping - Liquid / Gas9.52 mm / 15.88 mm
Seasonal performance
MetricHotAverageCold
Cooling star rating2.52.02.0
Heating star rating2.51.51.0
Residential TCSPF4.1583.8293.927
Residential HSPF3.76613.3642.867
Commercial TCSPF4.4484.4844.761
Commercial HSPF3.76613.7663.144
3. Dimensions and weights
UnitDimensions H × W × DWeight
Indoor425 × 1,250 × 490 mm54 kg
Outdoor1,290 × 900 × 330 mm104 kg
4. Duct connection dimensions
ConnectionHeight × Width
Return air325 × 865 mm
Supply air295 × 850 mm
Installation note: Dimensions above are duct connection openings, not overall cabinet dimensions. Confirm the physical unit before fabricating transitions, plenums or flexible connections.
5. Controls and communication
ItemDetail
UART communicationYes
UART ports2 ports: CN65 and CN75
Included controllerUTY-RVNYN backlit wired controller
6. What is included
Included itemDescription
ARTG60LHTAIndoor unit
AOTG60LATTOutdoor unit
UTY-RVNYNBacklit wired remote controller
7. Optional parts and interfaces
ModelDescription
UTY-ANY2Wi-Fi control – anywAiR Technology ducted controller
UTY-CDPXZCZone-control interface module, 8 zones, 24 V
UTY-CDPXZDZone-control interface module, 8 zones, 240 V
UTY-LRHYMWireless remote controller and infrared receiver kit
UTY-RNNYNWired remote controller
UTY-RSNYNSimple wired controller with mode button
UTD-ECS5AExternal control wiring kit
UTY-XCZZ1Smart-control option PCB
UTY-XSZXRemote temperature sensor
UTY-XWZXZ2External connect kit
8. Key features
FeatureDescription
Range overviewWorks at an optimum setting to create a comfortable home environment.
Zone controlAllows selected areas to be conditioned independently through a compatible zoning system.
All DCReduces electrical losses and helps lower power consumption.
Auto restartRestarts in the previous operating mode after a temporary power interruption.
Auto changeoverAutomatically selects heating or cooling according to the set temperature and room temperature.
Blue Fin heat exchangerImproves outdoor heat-exchanger corrosion resistance, particularly in coastal environments.
Connectable distributing ductSupports field-supplied branch ducts for airflow distribution.
Connectable fresh-air ductAllows introduction of outdoor air into the occupied space.
Economy modeLimits maximum operating current and suppresses power consumption.
Filter signAllows a filter reminder interval to be selected according to expected dust loading.
On/Off timerProvides a once-per-24-hour start or stop timer.
Program timerSupports ON, OFF, ON-to-OFF and OFF-to-ON schedules.
Weekly timerAllows different schedules for up to seven days.
Automatic fan speed adjustmentAutomatically changes airflow to suit changes in room temperature.