Product Information – ARTG36LHTB (SET-ARTG36LHTB)
Print
Modified on: Wed, 15 Jul, 2026 at 3:22 PM
GENERAL AIRSTAGE PRODUCT REFERENCE ARTG36LHTB SET-ARTG36LHTB | High Static Three Phase Specifications, dimensions, airflow, controls, accessories and key product features | System combination Indoor: ARTG36LHTB Outdoor: AOTG36LATT Included wired controller: UTY-RNRT Refrigerant: R410A |
| Quick navigation Quick Summary Specifications Dimensions Duct Connections Controls Included Optional Parts Features | 1. Quick summary | | Item | Detail | | Product name | ARTG36LHTB | | Product category | High Static Three Phase | | Operation type | Reverse cycle | | Cooling capacity | 10.50 kW rated | | Heating capacity | 12.10 kW rated | | Static pressure range | 60–210 Pa | | Cooling operating range | -15 to 46°C DB | | Heating operating range | -15 to 24°C DB |
| 2. Technical specifications | | Specification | Value | | Power supply | 230 V / 1 Ph / 50 Hz | | Cooling capacity - Rated / Min–Max | 10.50 kW / 5.0–11.4 kW | | Heating capacity - Rated / Min–Max | 12.10 kW / 5.1–14.0 kW | | Input power - Cooling rated / max | 3.18 kW / 5.63 kW | | Input power - Heating rated / max | 3.30 kW / 5.63 kW | | EER / COP | 3.30 / 3.747 | | Running current - Cooling / Heating | 4.6 A / 4.8 A | | Moisture removal | 1.5 L/h | | Indoor sound pressure - High / Quiet | 41 / 36 dBA | | Outdoor sound pressure - Cooling / Heating | 51 / 53 dBA | | Outdoor sound power | 67 dBA | | Indoor air circulation - High fan | 695 L/s cooling and heating | | Refrigerant charge | Not specified | | Maximum pipe length / pre-charge | 75 m / 30 m | | Maximum height difference | 30 m | | Piping - Liquid / Gas | 9.52 mm / 15.88 mm |
| Seasonal performance | | Metric | Hot | Average | Cold | | Cooling star rating | 2.5 | 2.5 | 2.5 | | Heating star rating | 2.5 | 2.0 | 2.0 | | Residential TCSPF | 4.491 | 4.045 | 4.144 | | Residential HSPF | 4.0971 | 3.937 | 3.529 | | Commercial TCSPF | 4.851 | 4.893 | 5.207 | | Commercial HSPF | 4.0971 | 4.097 | 3.747 |
| 3. Dimensions and weights | | Unit | Dimensions H × W × D | Weight | | Indoor | 400 × 1,050 × 500 mm | 39 kg | | Outdoor | 1,290 × 900 × 330 mm | 104 kg |
| 4. Duct connection dimensions | | Connection | Height × Width | | Return air | 325 × 865 mm | | Supply air | 295 × 850 mm |
| | Installation note: Dimensions above are duct connection openings, not overall cabinet dimensions. Confirm the physical unit before fabricating transitions, plenums or flexible connections. |
| 5. Controls and communication | | Item | Detail | | UART communication | Yes | | UART ports | 2 ports: CN65 and CN75 | | Included controller | UTY-RVNYN backlit wired controller |
| 6. What is included | | Included item | Description | | ARTG36LHTB | Indoor unit | | AOTG36LATT | Outdoor unit | | UTY-RVNYN | Backlit wired remote controller |
| 7. Optional parts and interfaces | | Model | Description | | UTY-ANY2 | Wi-Fi control – anywAiR Technology ducted controller | | UTY-CDPXZC | Zone-control interface module, 8 zones, 24 V | | UTY-CDPXZD | Zone-control interface module, 8 zones, 240 V | | UTY-LRHYM | Wireless remote controller and infrared receiver kit | | UTY-RNNYN | Wired remote controller | | UTY-RSNYN | Simple wired controller with mode button | | UTD-ECS5A | External control wiring kit | | UTY-XCZZ1 | Smart-control option PCB | | UTY-XSZX | Remote temperature sensor | | UTY-XWZXZ2 | External connect kit |
| 8. Key features | | Feature | Description | | Range overview | Works at an optimum setting to create a comfortable home environment. | | Zone control | Allows selected areas to be conditioned independently through a compatible zoning system. | | All DC | Reduces electrical losses and helps lower power consumption. | | Auto restart | Restarts in the previous operating mode after a temporary power interruption. | | Auto changeover | Automatically selects heating or cooling according to the set temperature and room temperature. | | Blue Fin heat exchanger | Improves outdoor heat-exchanger corrosion resistance, particularly in coastal environments. | | Connectable distributing duct | Supports field-supplied branch ducts for airflow distribution. | | Connectable fresh-air duct | Allows introduction of outdoor air into the occupied space. | | Economy mode | Limits maximum operating current and suppresses power consumption. | | Filter sign | Allows a filter reminder interval to be selected according to expected dust loading. | | On/Off timer | Provides a once-per-24-hour start or stop timer. | | Program timer | Supports ON, OFF, ON-to-OFF and OFF-to-ON schedules. | | Weekly timer | Allows different schedules for up to seven days. | | Automatic fan speed adjustment | Automatically changes airflow to suit changes in room temperature. |
| | Electrical verification required: The supplied product category identifies this model as three phase, while the supplied power-source field states 230 V / 1 Ph / 50 Hz. Confirm the correct electrical supply against the rating plate and current installation manual before quoting or installation. |
| | Product note: Confirm current accessory compatibility, controller combinations, seasonal-performance data and installation requirements against the latest product literature and technical manuals before specification or installation. |
| | GENERAL AIRSTAGE | ARTG36LHTB Product Reference |
|
Did you find it helpful?
Yes
No
Send feedback Sorry we couldn't be helpful. Help us improve this article with your feedback.