GENERAL AIRSTAGE PRODUCT REFERENCE
ARTG36LHTB
SET-ARTG36LHTB | High Static Three Phase
Specifications, dimensions, airflow, controls, accessories and key product features
System combination
Indoor: ARTG36LHTB
Outdoor: AOTG36LATT
Included wired controller: UTY-RNRT
Refrigerant: R410A
Quick navigation
Quick Summary Specifications Dimensions Duct Connections Controls Included Optional Parts Features
1. Quick summary
ItemDetail
Product nameARTG36LHTB
Product categoryHigh Static Three Phase
Operation typeReverse cycle
Cooling capacity10.50 kW rated
Heating capacity12.10 kW rated
Static pressure range60–210 Pa
Cooling operating range-15 to 46°C DB
Heating operating range-15 to 24°C DB
2. Technical specifications
SpecificationValue
Power supply230 V / 1 Ph / 50 Hz
Cooling capacity - Rated / Min–Max10.50 kW / 5.0–11.4 kW
Heating capacity - Rated / Min–Max12.10 kW / 5.1–14.0 kW
Input power - Cooling rated / max3.18 kW / 5.63 kW
Input power - Heating rated / max3.30 kW / 5.63 kW
EER / COP3.30 / 3.747
Running current - Cooling / Heating4.6 A / 4.8 A
Moisture removal1.5 L/h
Indoor sound pressure - High / Quiet41 / 36 dBA
Outdoor sound pressure - Cooling / Heating51 / 53 dBA
Outdoor sound power67 dBA
Indoor air circulation - High fan695 L/s cooling and heating
Refrigerant chargeNot specified
Maximum pipe length / pre-charge75 m / 30 m
Maximum height difference30 m
Piping - Liquid / Gas9.52 mm / 15.88 mm
Seasonal performance
MetricHotAverageCold
Cooling star rating2.52.52.5
Heating star rating2.52.02.0
Residential TCSPF4.4914.0454.144
Residential HSPF4.09713.9373.529
Commercial TCSPF4.8514.8935.207
Commercial HSPF4.09714.0973.747
3. Dimensions and weights
UnitDimensions H × W × DWeight
Indoor400 × 1,050 × 500 mm39 kg
Outdoor1,290 × 900 × 330 mm104 kg
4. Duct connection dimensions
ConnectionHeight × Width
Return air325 × 865 mm
Supply air295 × 850 mm
Installation note: Dimensions above are duct connection openings, not overall cabinet dimensions. Confirm the physical unit before fabricating transitions, plenums or flexible connections.
5. Controls and communication
ItemDetail
UART communicationYes
UART ports2 ports: CN65 and CN75
Included controllerUTY-RVNYN backlit wired controller
6. What is included
Included itemDescription
ARTG36LHTBIndoor unit
AOTG36LATTOutdoor unit
UTY-RVNYNBacklit wired remote controller
7. Optional parts and interfaces
ModelDescription
UTY-ANY2Wi-Fi control – anywAiR Technology ducted controller
UTY-CDPXZCZone-control interface module, 8 zones, 24 V
UTY-CDPXZDZone-control interface module, 8 zones, 240 V
UTY-LRHYMWireless remote controller and infrared receiver kit
UTY-RNNYNWired remote controller
UTY-RSNYNSimple wired controller with mode button
UTD-ECS5AExternal control wiring kit
UTY-XCZZ1Smart-control option PCB
UTY-XSZXRemote temperature sensor
UTY-XWZXZ2External connect kit
8. Key features
FeatureDescription
Range overviewWorks at an optimum setting to create a comfortable home environment.
Zone controlAllows selected areas to be conditioned independently through a compatible zoning system.
All DCReduces electrical losses and helps lower power consumption.
Auto restartRestarts in the previous operating mode after a temporary power interruption.
Auto changeoverAutomatically selects heating or cooling according to the set temperature and room temperature.
Blue Fin heat exchangerImproves outdoor heat-exchanger corrosion resistance, particularly in coastal environments.
Connectable distributing ductSupports field-supplied branch ducts for airflow distribution.
Connectable fresh-air ductAllows introduction of outdoor air into the occupied space.
Economy modeLimits maximum operating current and suppresses power consumption.
Filter signAllows a filter reminder interval to be selected according to expected dust loading.
On/Off timerProvides a once-per-24-hour start or stop timer.
Program timerSupports ON, OFF, ON-to-OFF and OFF-to-ON schedules.
Weekly timerAllows different schedules for up to seven days.
Automatic fan speed adjustmentAutomatically changes airflow to suit changes in room temperature.
Electrical verification required: The supplied product category identifies this model as three phase, while the supplied power-source field states 230 V / 1 Ph / 50 Hz. Confirm the correct electrical supply against the rating plate and current installation manual before quoting or installation.
Product note: Confirm current accessory compatibility, controller combinations, seasonal-performance data and installation requirements against the latest product literature and technical manuals before specification or installation.
GENERAL AIRSTAGE | ARTG36LHTB Product Reference