Applies to:

  • Indoor units (ARTH): ARTH65KBTA / ARTH65KRTA / ARTH72KRTA / ARTH90KRTA (manual also references ARTH60KHTB / ARTH65KHTA / ARTH72KHTA / ARTH90KHTA)
  • Outdoor units (AOTH): AOTH65KBTA / AOTH65KRTA / AOTH72KRTA / AOTH90KRTA
  • Optional controllers: Wired remote controller options including 2-wire and 3-wire types (refer to applicable controller manual)

Contents


1) Safety and compliance

  • Installation and service work must be performed by appropriately licensed / authorised personnel in accordance with local regulations.
  • Isolate electrical supply before removing covers or touching terminals.
  • Do not energise the system until all installation work is complete and covers are fitted.
  • If refrigerant leakage occurs during works: ventilate immediately and remove ignition sources.
  • Use vacuum pump evacuation (do not purge with refrigerant).
  • Ensure correct grounding/earthing and earth leakage protection as required by local regulations.

2) R32 refrigerant requirements

  • R32 is a flammable refrigerant. Comply with applicable safety standards and local regulations for flammable refrigerants.
  • Only use R32/R410A-rated tools, hoses and materials.
  • Prevent moisture/foreign matter entering piping; seal pipe ends during storage/handling.
  • Leak detection must be suitable for flammable refrigerants; do not use open flame methods.

3) Tools and materials (R32/R410A rated)

  • High-pressure gauge manifold suitable for R32/R410A
  • R32/R410A charging hoses
  • Vacuum pump and appropriate adapters (as required)
  • R32/R410A compatible leak detector
  • Tube cutter, deburr tool, flare tool suitable for R32/R410A, torque wrenches for flare nuts and caps
  • Nitrogen cylinder + regulator for pressure testing

4) System overview (what powers what)

  • Indoor unit is powered from the outdoor unit. Do not provide a separate power supply to the indoor unit unless explicitly specified by local product documentation.
  • Confirm indoor-to-outdoor terminal numbering matches on both ends.
  • Route cables to avoid contact with refrigerant piping and moving parts; secure with cord clamps.

5) Refrigerant piping requirements

5.1 Copper pipe material and minimum wall thickness (R32/R410A)

  • Use seamless phosphor deoxidised copper.
  • Do not reuse existing piping (risk of contamination and incompatibility).
Outside diameterNominal sizeMinimum thickness (annealed copper)
6.35 mm1/4"0.80 mm
9.52 mm3/8"0.80 mm
12.70 mm1/2"0.80 mm
15.88 mm5/8"1.00 mm
19.05 mm3/4"1.20 mm

5.2 Line sizes (ARTH indoor unit)

Indoor model groupLiquid pipeGas pipe
ARTH60 / ARTH65 class9.52 mm (3/8")15.88 mm (5/8")
ARTH72 / ARTH90 class12.70 mm (1/2")19.05 mm (3/4")

5.3 System piping limits (AOTH outdoor reference)

  • Minimum piping length: 5 m
  • Maximum piping length:
    • 50 m (AOTH65KB / AOTH65KR class)
    • 75 m (AOTH72KR / AOTH90KR class)
  • Maximum height difference (indoor ↔ outdoor): 30 m
  • Always insulate both liquid and gas lines. Increase insulation thickness in high humidity environments.

6) Electrical requirements

6.1 Outdoor unit (AOTH) power supply

  • Confirm nameplate supply and local wiring rules before commencing.
Outdoor modelSupplyBreaker capacity (guide)Power supply cable (minimum)
AOTH65KBTA220–240V ~ 1Φ 50Hz25A4.0 mm² (Type 60245 IEC 57 or local equivalent)
AOTH65KRTA380–415V ~ 3Φ 50Hz16A4.0 mm² (Type 60245 IEC 57 or local equivalent)
AOTH72KRTA380–415V ~ 3Φ 50Hz16A4.0 mm² (Type 60245 IEC 57 or local equivalent)
AOTH90KRTA380–415V ~ 3Φ 50Hz20A4.0 mm² (Type 60245 IEC 57 or local equivalent)

6.2 Indoor-to-outdoor connection cable

  • Conductor size: minimum 1.5 mm², Type 60245 IEC 57 (or local equivalent).
  • Core requirement: 3 cores + Ground (Earth) (connect to terminals 1–2–3 + earth as labelled).
  • Limit voltage drop to less than 2%; increase conductor size if required.
  • Do not connect AC supply to communication/transmission terminals.

6.3 Wired remote controller cable (if fitted)

  • Use shielded cable and route away from mains wiring where practicable.
Controller typeConductor sizeRemarks
2-wire type0.33 to 1.25 mm²Non-polar 2-core (twisted pair recommended)
3-wire type0.33 mm²Polar 3-core

7) Outdoor unit installation (AOTH)

7.1 Location and mounting

  • Install on a base that can withstand weight and vibration; use anchor bolts and appropriate anti-vibration measures.
  • Do not install where combustible gas may accumulate or in corrosive environments.
  • Provide appropriate service clearances and airflow clearances in accordance with the installation manual.
  • Secure appropriately for local wind/weather conditions.

7.2 Drain installation (outdoor)

  • Heating operation produces drain water; connect to suitable drain where applicable.
  • Where freezing is possible, manage drain paths to prevent ice-related hazards.

8) Indoor unit installation (ARTH – duct type)

8.1 Site selection (minimum requirements)

  • Install level and on a structure capable of supporting the unit weight and vibration.
  • Provide service access for electrical cover, filter access, and drain maintenance.
  • Confirm adequate space for duct connections and condensate drainage fall.

8.2 Condensate drain – key requirements

  • Install drain hose with a continuous downward gradient of 1/100 or more; avoid rises.
  • Do not create a water trap; avoid kinks, compression, or upward loops.
  • Insulate drain hose in high humidity spaces to prevent external condensation.
  • Confirm drainage by test-filling or during commissioning; rectify any leakage before ceiling closure.

8.3 Indoor wiring (ARTH) – field notes

  • Use the specified connection cable type and secure with the cord clamp.
  • Do not splice/extend wiring in a manner that can loosen or overheat; follow local code.
  • Use ring terminals where specified; ensure correct screw torque:
Terminal screwTightening torque
M41.2 to 1.8 N·m
M52.0 to 3.0 N·m

9) Pressure test, evacuation, commissioning

9.1 Flare work – tightening torques (system)

Outside diameterFlare nut tightening torque
6.35 mm (1/4")16 to 18 N·m
9.52 mm (3/8")32 to 42 N·m
12.70 mm (1/2")49 to 61 N·m
15.88 mm (5/8")63 to 75 N·m
19.05 mm (3/4")90 to 110 N·m

9.2 Nitrogen pressure test (outdoor reference)

  • With valves closed, pressurise with nitrogen to 4.15 MPa.
  • Check all flare joints and brazed points; rectify any leakage and retest.

9.3 Vacuum evacuation

  • Evacuate to -0.1 MPa (-76 cmHg).
  • When -0.1 MPa is reached, operate the vacuum pump for at least 60 minutes.

9.4 Service valve / port cap torques (outdoor reference)

Cap / PortApplicable sizeTightening torque
Blank cap6.35 mm (1/4"), 9.52 mm (3/8")20 to 25 N·m
Blank cap12.70 mm (1/2")28 to 32 N·m
Blank cap15.88 mm (5/8")30 to 35 N·m
Blank cap19.05 mm (3/4")35 to 40 N·m
Charging port capR3212.5 to 16.0 N·m

10) Additional refrigerant charging (AOTH)

  • Only charge R32 by weight using electronic scales.
  • Charge after evacuation and confirming the system is leak-free.
  • Do not reuse recovered refrigerant.

Additional charge – guide values (beyond pre-charge length)

Outdoor model groupPre-charge lengthAdditional charge rateWorked examples (additional only)
AOTH65KB / AOTH65KR class30 m40 g/m40 m: +400 g  |  50 m: +800 g
AOTH72KR / AOTH90KR class30 m60 g/m40 m: +600 g  |  50 m: +1200 g  |  60 m: +1800 g  |  70 m: +2400 g  |  75 m: +2700 g
  • Governance: Always confirm maximum allowable total charge per the unit nameplate / latest manufacturer documentation and local code before charging.

11) Wired remote controller (optional) – quick reference

  • Wired remote controller types vary (2-wire non-polar vs 3-wire polar). Confirm the controller type before wiring.
  • Use shielded cable and keep separation from mains wiring to reduce noise pickup.
  • Controller cable sizing guide:
    • 2-wire type: 0.33 to 1.25 mm² (non-polar)
    • 3-wire type: 0.33 mm² (polar)

12) Test run and handover

12.1 Check items

  • Remote controller operation normal
  • Airflow/duct operation normal; no abnormal noise or vibration
  • Drainage is normal (no indoor water leakage / sweating)
  • No refrigerant leakage detected
  • All covers fitted and cable clamps secured

12.2 Customer guidance

  • Explain operation, setpoints, timers, and controller functions.
  • Explain filter maintenance requirements and service access locations.
  • Provide applicable operation manuals to the customer/end user.

13) Pump down (forced cooling operation) – Outdoor unit reference

  • Use pump down for relocation/disposal refrigerant recovery in accordance with the manufacturer procedure.
  • Initiate forced cooling/test run mode per controller guidance (method varies by controller type).
  • Close the liquid valve first, then close the gas valve after a short run period, then stop operation.
  • Do not proceed if refrigerant is depleted due to damaged piping; confirm leak-free condition first.

14) Error codes (ARTH indoor + AOTH outdoor + UTY-RNRT wall controller)

Important: The manufacturer tables include some errors that may be irrelevant to this specific model combination. Always validate wiring/communications first, then sensors/actuators as per standard diagnostic workflow.


14.1 UTY-RNRT (Wall controller) – Error Information codes

Error codeContents
CC.1Sensor error
C2.1Transmission PCB error
12.1Wired remote controller communication error
12.3Number excess of device in wired remote controller system
12.4Wired remote controller system start-up error
26.4Address duplication in wired remote controller system
26.5Address setting error in wired remote controller system
15.4Data acquisition error

14.2 ARTH (Indoor unit) – Lamp flash error code table (X-Y)

Format below is the indoor receiver lamp flash interpretation used in the ARTH installation manual:

  • X = OPERATION lamp (green) number of flashes
  • Y = TIMER lamp (orange) number of flashes
Error code (X-Y)Description
1-1Serial communication error
1-2Wired remote controller communication error
1-5Check run unfinished / Automatic airflow adjustment error
1-6Peripheral unit transmission PCB connection error
1-8External communication error
2-1Unit number or Refrigerant circuit address setting error (simultaneous multi-split type)
2-2Indoor unit capacity error
2-3Combination error
2-4Connection unit number error (indoor secondary unit) – simultaneous multi-split type / Connection unit number error (indoor unit or branch unit) – flexible multi-split type
2-6Indoor unit address setting error
2-7Primary unit / secondary unit setup error (simultaneous multi-split type)
2-9Connection unit number error in wired remote controller system
3-1Power supply interruption error
3-2Indoor unit PCB model information error
3-3Indoor unit motor electricity consumption detection error
3-5Manual auto switch error
3-9Indoor unit power supply error for fan motor
3-10Indoor unit communication circuit (wired remote controller) error
4-1Room temp. sensor error
4-2Indoor unit heat exchanger middle temp. sensor error
4-4Occupancy sensor error
5-1Indoor unit fan motor error
5-3Drain pump error
5-7Damper error
5-15Indoor unit error
6-1Outdoor unit reverse/missing phase and wiring error
6-2Outdoor unit main PCB model information error or communication error
6-3Inverter error
6-4Active filter error / PFC circuit error
6-5Trip terminal L error / IPM temp. error
6-8Outdoor unit rush current limiting resister temp. rise error
6-10Display PCB microcomputers communication error
7-1Discharge temp. sensor error
7-2Compressor temp. sensor error
7-3Outdoor unit Heat Ex. liquid temp. sensor error
7-4Outdoor temp. sensor error
7-5Suction gas temp. sensor error
7-62-way valve temp. sensor error / 3-way valve temp. sensor error
7-7Heat sink temp. sensor error
8-2Sub-cool Heat Ex. gas inlet temp. sensor error / Sub-cool Heat Ex. gas outlet temp. sensor error
8-3Liquid pipe temp. sensor error
8-4Current sensor error
8-6Discharge pressure sensor error / Suction pressure sensor error / High pressure switch error
9-4Trip detection
9-5Compressor rotor position detection error (permanent stop)
9-7Outdoor unit fan motor 1 error
9-8Outdoor unit fan motor 2 error
9-94-way valve error
9-10Coil (expansion valve) error
10-1Discharge temp. error
10-3Compressor temp. error
10-4High pressure error
10-5Low pressure error
10-11Heat sink temp. error
13-2Branch boxes error (flexible multi-split type)

14.3 AOTH (Outdoor unit) – LED display error code check table (condensed)

Outdoor LED interpretation aligns to the AOTH installation manual “10.2 Error code check table”. Pattern below summarises the LED display state at fault:

  • Power/Mode = blink count
  • L1 = PUMP DOWN LED (blink count)
  • L2 = LOW NOISE LED (blink count)
  • L3–L6 = ON/OFF indicators per manual table
LED patternDescriptionRemark
Power/Mode: Blink 2
L1: Blink 1
L2: Blink 1
L3: OFF
L4: OFF
L5: ON
L6: ON
Serial communication errorSerial forward transmission error immediately after operation
Power/Mode: Blink 2
L1: Blink 1
L2: Blink 1
L3: OFF
L4: ON
L5: OFF
L6: OFF
Serial communication errorSerial forward transmission error during operation
Power/Mode: Blink 2
L1: Blink 2
L2: Blink 2
L3: OFF
L4: OFF
L5: OFF
L6: ON
Indoor unit capacity errorIndoor unit capacity error
Power/Mode: Blink 2
L1: Blink 2
L2: Blink 3
L3: OFF
L4: OFF
L5: OFF
L6: ON
Incompatible series connection errorConnection forbidden (series error)
Power/Mode: Blink 2
L1: Blink 5
L2: Blink 15
L3: OFF
L4: OFF
L5: OFF
L6: ON
Indoor unit errorIndoor unit error
Power/Mode: Blink 2
L1: Blink 6
L2: Blink 1
L3: OFF
L4: ON
L5: OFF
L6: ON
Outdoor unit power supply errorOutdoor unit reverse/missing phase and wiring error
Power/Mode: Blink 2
L1: Blink 6
L2: Blink 2
L3: OFF
L4: OFF
L5: OFF
L6: ON
Outdoor unit main PCB errorOutdoor unit PCB model information error
Power/Mode: Blink 2
L1: Blink 6
L2: Blink 3
L3: OFF
L4: OFF
L5: OFF
L6: ON
Inverter PCB errorInverter error
Power/Mode: Blink 2
L1: Blink 6
L2: Blink 5
L3: OFF
L4: OFF
L5: OFF
L6: ON
IPM errorTemperature error
Power/Mode: Blink 2
L1: Blink 6
L2: Blink 5
L3: OFF
L4: OFF
L5: ON
L6: ON
IPM errorTrip terminal L error
Power/Mode: Blink 2
L1: Blink 7
L2: Blink 1
L3: OFF
L4: OFF
L5: OFF
L6: ON
Discharge temp. sensor errorDischarge temp. sensor 1 error
Power/Mode: Blink 2
L1: Blink 7
L2: Blink 2
L3: OFF
L4: OFF
L5: OFF
L6: ON
Compressor temp. sensor errorCompressor temp. sensor 1 error
Power/Mode: Blink 2
L1: Blink 7
L2: Blink 3
L3: OFF
L4: OFF
L5: ON
L6: OFF
Outdoor unit Heat Ex. sensor errorHeat Ex. center temp. sensor error
Power/Mode: Blink 2
L1: Blink 7
L2: Blink 3
L3: OFF
L4: OFF
L5: ON
L6: ON
Outdoor unit Heat Ex. sensor errorOutdoor unit Heat Ex. liquid temp. sensor error
Power/Mode: Blink 2
L1: Blink 7
L2: Blink 4
L3: OFF
L4: OFF
L5: OFF
L6: ON
Outdoor temp. sensor errorOutdoor temp. sensor error
Power/Mode: Blink 2
L1: Blink 7
L2: Blink 7
L3: OFF
L4: OFF
L5: OFF
L6: ON
Heat sink temp. sensor errorHeat sink temp. sensor error
Power/Mode: Blink 2
L1: Blink 8
L2: Blink 4
L3: OFF
L4: OFF
L5: OFF
L6: ON
Current sensor errorCurrent sensor 1 error (stoppage permanently)
Power/Mode: Blink 2
L1: Blink 8
L2: Blink 6
L3: OFF
L4: ON
L5: OFF
L6: OFF
Pressure sensor errorHigh pressure switch 1 error
Power/Mode: Blink 2
L1: Blink 8
L2: Blink 6
L3: OFF
L4: ON
L5: ON
L6: OFF
Pressure sensor errorPressure sensor error
Power/Mode: Blink 2
L1: Blink 9
L2: Blink 4
L3: OFF
L4: OFF
L5: OFF
L6: ON
Trip detectionTrip detection
Power/Mode: Blink 2
L1: Blink 9
L2: Blink 5
L3: OFF
L4: OFF
L5: OFF
L6: ON
Compressor motor control errorRotor position detection error (stoppage permanently)
Power/Mode: Blink 2
L1: Blink 9
L2: Blink 7
L3: OFF
L4: OFF
L5: ON
L6: OFF
Outdoor unit fan motor 1 errorFan motor 1 error (stoppage permanently)
Power/Mode: Blink 2
L1: Blink 9
L2: Blink 8
L3: OFF
L4: OFF
L5: ON
L6: OFF
Outdoor unit fan motor 2 errorFan motor 2 error (stoppage permanently)
Power/Mode: Blink 2
L1: Blink 9
L2: Blink 9
L3: OFF
L4: OFF
L5: OFF
L6: ON
4-way valve error4-way valve error
Power/Mode: Blink 2
L1: Blink 10
L2: Blink 1
L3: OFF
L4: OFF
L5: OFF
L6: ON
Discharge temp. 1 errorDischarge temp. 1 error
Power/Mode: Blink 2
L1: Blink 10
L2: Blink 3
L3: OFF
L4: OFF
L5: OFF
L6: ON
Compressor temp. errorCompressor 1 temp. error
Power/Mode: Blink 2
L1: Blink 10
L2: Blink 5
L3: OFF
L4: OFF
L5: OFF
L6: ON
Pressure error 2Low pressure error
Power/Mode: Blink 2
L1: Blink 10
L2: Blink 11
L3: OFF
L4: OFF
L5: ON
L6: ON
Heat sink temp. errorHeat sink temp. error

Operational note: If using UTY-RNRT, the controller “Error Information” screen may show a 2-digit error code. For indoor/outdoor functional faults, use the applicable ARTH/AOTH tables above and then proceed with standard diagnostics (power supply / phase / comms first, then sensors, then actuators).

Document control: This Solution article is intended as a consolidated, text-only field reference for KBTA/KRTA series installation. Always comply with local regulations and refer to the latest manufacturer documentation for detailed diagrams, part numbers, and regional variations.